Chapter 6 Storage & Maintenance
12
Chapter 6 : Storage & Maintenance
The unit contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In
this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it
to your dealer in the replacement battery packing material.
z
z
Storage
Before storing, charge the unit 4 hours. Store the unit covered and upright in a
cool, dry location. During storage, recharge the battery in accordance with the
following table:
Storage Temperature Recharge Frequency
Charging Duration
-25°C ~ 40°C
Every 3 months
1 ~ 2 hours
40°C ~ 45°C
Every 2 months
1 ~ 2 hours