15
Φ22.2
Φ19.05
Φ15.9
Φ12.7
Φ9.52
Φ6.35
0.35
0.25
0.17
0.11
0.054
0.022
7.2.3 Example for calculation
d
c
b
a
Indoor unit
①
②
③
④
B
A
C
Outdoor unit
D
Indoor unit:
SN
Model
Indoor unit
Cassette type
Indoor unit
Wall Mounted type
Indoor unit
Single Side Air Supply type
Indoor unit
Ducted type
Liquid Pipe:
SN
A
B
C
D
Diameter of the pipe
Φ9.52
Φ9.52
Φ9.52
Φ6.35
Length
30m
10m
5m
5m
SN
a
b
c
d
Diameter of the pipe
Φ9.52
Φ6.35
Φ6.35
Φ6.35
Length
10m
10m
10m
10m
Total length of liquid pipes:
Φ
9.52: A+B+C+a=30+10+5+10=55m
Φ
6.35: D+b+c+d=5+10+10+10=35m
Notes: if total length is less than 50 meters, there is no need to add extra refrigerant.
So, the minimum required refrigerant amount should be=(55-50)X0.054+35X0.022=1.04kg.