Use proper extension cords. Make sure your extension cord is in good condition and is a 3-wire
extension cord which has a 3-prong grounding type plug and matching receptacle which will accept the machine’s
plug. When using an extension cord, be sure to use one heavy enough to carry the current of the machine. An
undersized cord will cause a drop in line voltage, resulting in loss of power and overheating. Fig. D, shows the correct
gauge to use depending on the cord length. If in doubt, use the next heavier gauge. The smaller the gauge number,
the heavier the cord.
EXTENSION CORDS
Fig. D
Fig. D
MINIMUM GAUGE EXTENSION CORD
RECOMMENDED SIZES FOR USE WITH STATIONARY ELECTRIC MACHINES
Ampere
Total Length
Gauge of
Rating
Volts
of Cord in Feet
Extension Cord
0-6
120
up to 25
18 AWG
0-6
120
25-50
16 AWG
0-6
120
50-100
16 AWG
0-6
120
100-150
14 AWG
6-10
120
up to 25
18 AWG
6-10
120
25-50
16 AWG
6-10
120
50-100
14 AWG
6-10
120
100-150
12 AWG
10-12
120
up to 25
16 AWG
10-12
120
25-50
16 AWG
10-12
120
50-100
14 AWG
10-12
120
100-150
12 AWG
12-16
120
up to 25
14 AWG
12-16
120
25-50
12 AWG
12-16
120
GREATER THAN 50 FEET NOT RECOMMENDED
MINIMUM GAUGE EXTENSION CORD
RECOMMENDED SIZES FOR USE WITH STATIONARY ELECTRIC MACHINES
Ampere
Total Length
Gauge of
Rating
Volts
of Cord in Feet
Extension Cord
0-6
240
up to 50
18 AWG
0-6
240
50-100
16 AWG
0-6
240
100-200
16 AWG
0-6
240
200-300
14 AWG
6-10
240
up to 50
18 AWG
6-10
240
50-100
16 AWG
6-10
240
100-200
14 AWG
6-10
240
200-300
12 AWG
10-12
240
up to 50
16 AWG
10-12
240
50-100
16 AWG
10-12
240
100-200
14 AWG
10-12
240
200-300
12 AWG
12-16
240
up to 50
14 AWG
12-16
240
50-100
12 AWG
12-16
240
GREATER THAN 100 FEET NOT RECOMMENDED
3. Grounded, cord-connected machines intended for
use on a supply circuit having a nominal rating between
150 - 250 volts, inclusive:
If the machine is intended for use on a circuit that has an
outlet that looks like the one illustrated in Fig. C, the
machine will have a grounding plug that looks like the
plug illustrated in Fig. C. Make sure the machine is
connected to an outlet having the same configuration as
the plug. No adapter is available or should be used with
this machine. If the machine must be re-connected for
use on a different type of electric circuit, the re-
connection should be made by qualified service
personnel; and after re-connection, the machine should
comply with all local codes and ordinances.
IN ALL CASES, MAKE CERTAIN THE
R E C E P TA C L E I N Q U E S T I O N I S P R O P E R LY
G R O U N D E D . I F Y O U A R E N O T S U R E H AV E A
Q U A L I F I E D E L E C T R I C I A N C H E C K T H E
RECEPTACLE.
4. Permanently connected machines:
If the machine is intended to be permanently connected,
the machine should be connected to a grounded metal
permanent wiring system, or to a system having an
equipment-grounding conductor.
Fig. C
GROUNDED OUTLET BOX
CURRENT
CARRYING
PRONGS
GROUNDING BLADE
IS LONGEST OF THE 3 BLADES
THREE PHASE OPERATION
If the motor on your machine is wired for 200V, 230V, or 460V, three phase, the necessary wiring from the starter to the
power should be completed by a qualified electrician.