background image

pH/mV TRANSMITTER

Fig.1 

Active transmitter.

Fig.3 

Passive transmitter.

����� ������� ������� �� ��� �� ��

������ �

���� �� ��� ���������

�� ���

��� ���

��
��
��
��

��

����



���

��������

��

��

��

�����

� �����

��
��
��
��

����



��������

��

��

��

��

�����

� �����

Fig.4

������ ��

��� ����

���������



������ ��

��� ����

���������

��
��
��
��

����

��

��

��

�����

� �����

��
��
��
��

��

����

��

��

��

�����

� �����

�� ���

��� ���

��

Fig.2 

Active indicator.

�� ���

��� ���

��
��
��
��

��

����



��

��

��

�����

� �����

The 

DO  9403T-R1

  pH  transmitter  converts  the  output  of  a  pH  electrode,  with 

temperature compensation, into a signal at 4÷20 mA.  The pH or Redox electrode 

input circuit is galvanically insulated against the 4÷20 mA output signal.

An LCD indicator allows viewing of the process signal value and of the various 

parameters.  The accurate design and choice of components make the instrument 

precise and reliable for a long working life.

The  instrument  works  in  conjunction  with  a  pH  or  Redox  electrode  and  a 

temperature probe (Pt100 sensor, 100 

Ω

 at 0°C).

Key functions

PRG

  Programming of the parameters is activated by pressing the PRG key. 

The 

Δ

  symbol  lights  up  on  the  display  and  the  message  P1  appears, 

indicating that the parameter P1 is being programmed. When the PRG 

key is pressed continuously, the messages P2, P3, P4, P5, P6, P7, P8, 

P9, P10 and the corresponding parameters are displayed in sequence. 

After P10 the instrument returns to normal function.

 

After the parameter concerned gas been displayed, it is possible to view 

its value by pressing the OK key. To change the parameter use the s and 

t keys.  Press the OK key again to confirm the value of the parameter.

SET

  Key for setting the relay intervention threshold. The 

Δ

 symbol and the 

REL  symbol  appear  on  the  display,  fixed  or  flashing,  indicating  the 

switching on or off threshold of relay A or of relay B.

°C/°F

  -  If  this  key  is  pressed  it  changes  the  temperature  measuring  unit  to 

degrees Celsius or degrees Fahrenheit.

 

-

 

When  pressed  together  with  the  CAL  key  it  activates  the  manual 

temperature setting function.

 

-

 

If  pressed  during  the  pH  calibration  function  it  quits  the  calibration 

function without storing the calibration.

pH/mV

 - If this key is pressed it changes the measuring unit to mV or pH.

 

-

 

When pressed together with the CAL key it activates the pH calibration 

function.

OK

 

Confirms  the  programming  parameters,  or  the  relay  SET  values,  and 

stores them.

CAL

  -  When  pressed  together  with  the  °C/°F  key  it  activates  the  manual 

temperature setting function.

 

-

 

When  pressed  together  with  the  pH/mV  key  it  activates  the  pH 

calibration function.

 

-

 

Key used to confirm pH calibration and manual temperature setting.

 

- Key for increasing the value displayed in the parameter programming 

phase.

 

-

 

During the relay SET point programming phase.

 

-

 

During the calibration phase.

 

- Key for decreasing the value displayed in the parameter programming 

phase.

 

-

 

During the relay SET point programming phase.

 

-

 

During the calibration phase.

Setting the relay SET point

-

 

Press the SET button; the 

Δ

 symbol appears on the display.

-

 

The REL symbol and the letter A also light up on the display to indicate that the 

value shown corresponds to the switching on threshold of relay A.

-

 

To change this value press the 

 and 

 keys.

-

 

Press SET; the REL symbol flashes and the letter A remains lit to indicate that 

the value shown corresponds to the switching off threshold of relay A.

-

 

To change this value press the 

 and 

 keys.

-

 

Press the SET button; the REL symbol and the letter B light up to indicate that 

the value shown corresponds to the switching off threshold of relay B.

-

 

To change this value press the 

 and 

 keys.

-

 

Press SET; the REL symbol flashes and the letter B remains lit to indicate that 

the value shown corresponds to the switching off threshold of relay B.

-

 

To change this value press the 

 and 

 keys.

-

 

Press SET, the instrument stores the set parameters and returns to normal 

function. The REL and 

Δ

 symbols disappear.

NOTE:  During  the  SET  point  setting  phase  (REL  symbol  lit  or  flashing)  the 

instrument returns to normal function if no key is pressed for 2 minutes.

PH-2

PH-3