8.0  Wiring schematic

AlertMaxx2

The AlertMaxx2 is different from a standard high level alarm as the pump/s require to be fed through the unit.  

This way of connectivity allows the AlertMaxx2 to collect various different parameters directly from the pumps 

and when connected via Wi-Fi, this data can be used to intelligently plan maintenance and service schedules to 

the specific pump station it is connected to (see page 15).

Figure 1. AlertMaxx2 wiring schematic

AlertMaxx2 High Level Alarm

(DMS-269-2)

For internal wiring of the high 

level alarm, please refer to the 

AlertMaxx2 instruction manual.

- The pump is supplied with a 10m cable.

- When only using the standard 10m 

cable attached to the pump, the cable 

duct should be no longer than 6m.

- If the cable duct requires to be longer 

than 6m, please follow the cable 

extension guide to select an appropriate 

cable core diameter.

Finger Float Switch

Supplied with a 10m cable

The electrical installation must comply with the requirements of 

BS 7671:2008 ‘Requirements for

Electrical Installations’ incorporating amendment 3:2015

Separate 16 Amp RCBO’s

13 Amp Non-switched 

fused spur

Содержание AlertMaxx2

Страница 1: ...Installation Operating Manual Pump Station High Level Alarm AlertMaxx2 Foul Water DMS 299...

Страница 2: ...processed for any other purpose nor otherwise transmitted published or made available to a third party without express written consent from Delta Membranes Subject to technical modification without pr...

Страница 3: ...ng a pump to the AlertMaxx2 8 11 0 Installing a pendant float into a foul water chamber 9 12 0 Connecting a pendant float to the AlertMaxx2 unit 10 13 0 Activating testing the AlertMaxx2 unit 11 13 1...

Страница 4: ...gs Nuts 1 x Small Cable Gland Nut 2 x Small Blanking Plugs Nuts 1 x 6V Battery 2 2 AlertMaxx2 unit contents 1 x AlertMaxx2 Unit 1 x Chamber Location Sticker Sheet For AlertMaxx2 1 x Chamber Location S...

Страница 5: ...it suitable wall plugs in to the chosen wall for installation ensure correct wall plugs are used for the wall type 3 Secure the AlertMaxx2 unit to the wall using appropriate screws for the wall plugs...

Страница 6: ...AlertMaxx2 High Level Alarm DMS 269 2 For internal wiring of the high level alarm please refer to the AlertMaxx2 instruction manual The pump is supplied with a 10m cable When only using the standard...

Страница 7: ...ect the power cable to the corresponding terminal block on the main PCB figure 2 WARNING Ensure mains power is isolated before connecting and wiring to the AlertMaxx2 unit Figure 2 Connecting mains po...

Страница 8: ...AlertMaxx2 8 AlertMaxx2 1 Using the remaining cable gland previously installed in section 9 0 feed the pump cable through the gland and connect to the corresponding terminal block on the main PCB figu...

Страница 9: ...float weight 2 Using a cable tie secure the float weight to the float cable so there is 80mm of float cable between the top of the float switch and the bottom of the float weight 3 Drill a hole throu...

Страница 10: ...e AlertMaxx2 unit 4 Connect the black and blue cables from the float switch cable to the terminal strip figure 6 The brown cable should be disregarded and isolated to avoid possible shorting PLEASE NO...

Страница 11: ...error code and sound 3 Test the float switch by raising the float switch to its upright position The alarm will activate within 10 15 seconds 4 Release the float switch The sounder will stop within 3...

Страница 12: ...outside these parameters the device must be powered by an external power supply You can use the AlertMaxx2 to power external devices with a maximum voltage of 6 7V 17 0 Spares Part No Description DMS...

Страница 13: ...e SEU card Please contact PPS to rectify E4 No response from server Please contact PPS to rectify E5 Cannot find PowerMaxx The AlertMaxx2 cannot communicate with the PowerMaxx the units will continue...

Страница 14: ...tch is broken replace float switch Float cable is broken replace float switch The alarm does not activate when pressing the FUNC button for 3 5 seconds Faulty unit Alarm continuously active Float has...

Страница 15: ...3m of 4 core MaxxConnect family cable The AlertMaxx2 can only be connected to PowerMaxx PowerMaxx and Hi PowerMaxx which is running the software version 3 0 or higher This can be identified by the so...

Страница 16: ...service engineers to maintain enhance replace equipment Passionate Bespoke design manufacturing installation ensuring our equipment is fit for every requirement Service From fitting to scheduled maint...