background image

INSTALLATION 

 

SM6000 

15 / 21 

DELTA ELEKTRONIKA B.V. 

rev. Nov. 2020 

 

series (F27_1 on P598). To avoid earth loops, use an isolated 
programming source. If this is not possible, see next 
paragraph for using the optional 

ISO AMP CARD

4.8

 

ISOLATED ANALOG  PROGRAMMING 

 

For programming via the 

ISO AMP CARD

, set DIP switch 1 

on SW1 in the position DOWN.  

 

When the ISO AMP CARD is built inside the unit, CON E has 
been removed. Use CON H instead. The pinning of CON H is 
equal to the pinning of CON E . 

 

For further operating instructions, see previous paragraph. 

4.9

 

IEEE488 / RS232 PROGRAMMING 

 

Set DIP switch 1 on SW1 in position DOWN for programming 
with the 

PSC-488

 using CON H or programming with the 

PSC-232

 using CON F and G. With DIP switch 1 in this 

position, the signals V

prog

 (pin 11) and I

prog

 (pin 3) are disabled 

on CON E. All the other signals can still be used.  

 

Set the unit in REMOTE CV for voltage programming and/or 
in REMOTE CC for current programming using the SCPI 
commands (see manual PSC) or using the REMOTE/LOCAL 
button on the unit. Push this button several times until the 
right setting is activated. Setting the unit in REMOTE or 
LOCAL will cause the output to shutdown to avoid accidental 
damage to the load. Turn it on again using the SCPI 
command or with the OUTPUT ON/OFF button. 

 

Set DIP switch 1 on SW1 in position UP to enable CON E 
again for analog programming.  
In this position voltage and current programming on CON F 
and H is disabled. The other functions and signals can still be 
programmed and read back. 

4.10

 

MONITORING OUTPUTS 

 

The 5 V level is compatible with most interfaces. 

 

The monitoring outputs can drive a meter directly (fig. 4 - 4). 

4.11

 

STATUS OUTPUTS 

 

The status outputs have a separate Ø connection (pin 8) to 
avoid unwanted offsets in the programming. This pin is 
protected with a 650 mA self resetting fuse (F27_2 on P598). 

4.12

 

DC LOAD SENSING (REMOTE SENSING) 

 

Remove the links on the SENSE BLOCK (on rear panel) and 
connect sense leads (thin 

shielded

 measuring wires) to S+ 

and S

–. See fig. 4 - 5 and fig. 4 - 6. 

 

With remote sensing the voltage on the load can be kept 
constant. The voltage drop in the load leads will be 
compensated. This feature is not recommended for normal 
use, because it can easily give problems. 

 

Max. 2 V per load lead can be compensated. Note that the 
voltage drop in the leads decreases the max. output voltage 
rating. In fig. 4 - 7 it can be seen that on a 15 V power supply 
only 11 V will be available on the load when 2x 2 V 
compensation is used. 

 

In order to prevent interference it is advisable to twist the 
sense leads. To minimize the inductance in the load leads 
keep the leads close to each other. The inductance of the 
loads leads could give a problem with pulsating loads. In this 
case a large electrolytic capacitor (C

d

) in series with a 

damping resistor (R

d

) both in parallel with the load will help 

(see fig. 4 - 6). Check that the capacitor C

in combination 

with the load leads and resistor R

d

 forms a well damped 

circuit. 

 

Since the 

voltmeter 

is internally connected to the sensing 

terminals, it will automatically indicate the 

voltage on the 

load

. Note that the voltage measured on the load will be 

lower than on the output terminals. 

 

The Over Voltage Limit measures the voltage on the output 
terminals, so the OVL setting should be increased by the total 
voltage drop in the load leads. 
 
 

 

 

fig 4 - 6 

Remote sensing with shielded wires. 

 

 

fig 4 - 7 

remote sensing, voltage drop on load leads subtracts 

from the maximum output. 

 

 

fig 4 - 8 

Charging a battery with a circuit breaker in series. 

Suggested circuit breakers for protection power supply 

Model 

Type nr. 

Brand 

Remarks 

SM15-400 

HTI102 B 100 
2pcs needed 

GE 

4 poles parallel 

SM30-200 

HTI102 B 100  GE 

2 poles parallel  

SM45-140 

HTI102 B 100  GE 

2 poles parallel 
extra parallel 
diode on output 
needed 
= OPTION 151  

SM60-100 

HTI101 B 100  GE 

No remarks 

SM70-90 

HTI101 B 100  GE 

No remarks 

SM120-50 

S281 UC-Z 50  ABB 

extra parallel 
diode on output 
needed 
= OPTION 152 

SM300-20 

S282 UC-Z 20  ABB 

2 poles in series  
extra parallel 
diodes on output 
needed 
= OPTION 153 

SM600-10 

FHL 3603013  Schneider 

Electric 

2 poles in series  
extra parallel 
diodes on output 
needed 

 

table 4 -2  

Circuit breakers for protection.  

Содержание SM 120-50

Страница 1: ...50 SM300 20 SM600 10 PRODUCT MANUAL Contents 1 Safety Instructions 2 Sicherheitshinweise 3 General 4 Installation 5 Trouble Shooting 6 Maintenance Calibration 7 EU Declaration of Conformity Product Manuals and Driver Example Software For several Applications build in Options and Interfaces there are Application Notes separate Product Manuals and Driver Example Software available on available on ou...

Страница 2: ...red safe DC power terminals and sense connections programming monitor status signals Interlock Master Slave connections ACF DCF relay all Delta Elektronika interfaces Caution 1 If a low voltage unit has both DC power terminals floating or if the DC terminals are in series with an external high AC or DC voltage the minus DC power terminal can exceed the safe value in respect to ground as specified ...

Страница 3: ...ch off the unit Disconnect the unit from the AC mains supply and from the DC power application Wait for 5 minutes to allow internal capacitors to discharge Unscrew the screws and remove the cover s Always place the cover s back before connecting the unit to the mains supply again 1 12 Environmental Conditions The Delta Elektronika power supplies safety approval applies to the following operating c...

Страница 4: ...rammierung Monitor Status Signale InterLock Master Slave Anschlüsse ACF DCF Relais Schnittstellen mit Funktionale Isolation Schnittstellen ohne Sicherheitsisolation Vorsicht 1 Falls beide DC Anschlussklemmen eines Niederspannungsgerätes potentialfrei sind oder falls die DC Klemmen in Reihe mit einer externen AC oder DC Hochspannung geschaltet sind kann die minus DC Anschlussklemme den sicheren Wer...

Страница 5: ...ungsbedingungen Die Stromversorgungssicherheitszulassung von Delta Elektronika gilt für die folgenden Betriebsbedingungen Innengebrauch Umgebungstemperatur 20 bis 50 C Maximale relative Luftfeuchtigkeit 95 nicht kondensierend bis zu 40 C 75 nicht kondensierend bis zu 50 C Höhe bis zu 2000 m Verschmutzungsgrad 2 Diese Kennzeichnung auf dem Produkt seiner Verpackung oder seiner Literatur weist darau...

Страница 6: ...and the harmonic distortion of the AC input current will be relatively low The peak inrush current is electronically limited Switching on and off repeatedly will not result in excessive currents like with NTC circuits 3 4 STANDBY AC INPUT POWER The unit consumes very little power when in standby This makes it possible to leave the AC input power on when the output is disabled using the Output On O...

Страница 7: ... by the computer 3 12 MONITORING OUTPUTS The monitor outputs give a voltage 0 5 V proportional to the output current or voltage The output current can easily be measured using the I monitor see fig 3 6 The monitor outputs are buffered with op amp s and protected with series resistors and parallel zener diodes see fig 3 7 The table in fig 3 5 shows the impedance levels of the monitoring outputs For...

Страница 8: ...to the ACF relay see fig 3 10 fig 3 10 Status relay outputs on CON D This situation gives the relay positions during fault condition fig 3 8 Location of output terminals and analog programming connector on the rear panel CON A Interlock Connector CON B Master connector for Master Slave operation output CON C Slave connector for Master Slave operation input CON D Relay Outputs contacts 1 6 CON E An...

Страница 9: ... the rise and fall time is 5 to 25 times faster see datasheet The programming source must be floating or otherwise an ISO AMP CARD must be used a non floating source will result in slope distortion When using hi speed programming it is generally not recommended to use remote sensing or serial parallel operation Consult factory for advice Note that the output ripple is higher 3 20 PULSATING LOAD To...

Страница 10: ...ld up time see fig 3 17 3 26 TURN ON DELAY The DC output voltage is available about 0 2 sec after mains switch on 3 27 AC INRUSH CURRENT The inrush current is electronically limited Repeatedly switching on and off does not change the maximum peak current Switching on and off at a fast rate can overheat the inrush current limiter With the result that the unit does not start anymore After cooling do...

Страница 11: ...llel operation in combination with Power Sink option only one unit can have a Power Sink Refer to Power Sink manual for details and restrictions 3 32 MASTER SLAVE OPERATION The Master Slave feature makes it possible to use power supplies as building blocks to form one large unit fig 3 20 Mixed parallel series operation is also possible to a maximum of 600 V The resulting combination of units behav...

Страница 12: ...ons such as variable coarse fine pitch adjustment locking of CV CC settings and a selectable start up voltage start at 0V 0A or at last settings The lower voltage units have analog potentiometers for the CV CC controls Optional they can be equipped with screwdriver adjustment for CV CC settings at the front panel or also with digital encoders option P220 See fig 3 23 for option P001 3 35 COOLING T...

Страница 13: ...ts is allowed without limitations See previous paragraph for cooling instructions 4 4 OPERATING THE UNIT FOR THE FIRST TIME Check there is no condensation on the unit If there is allow some time to dry Check there is a link between and S and between and S on the SENSE BLOCK on rear panel Check there is a link between pins of the Interlock CON A Set the CV and CC potentiometers to minimum fully ant...

Страница 14: ...ion UP the settings after mains switch on will be the same as before switching the mains voltage off 4 7 ANALOG PROGRAMMING Set DIP switch 1 of SW1 in position UP to select CON E for programming For SM300 20 SM600 10 see paragraph ISO AMP Disable Keylock Set the unit in REMOTE CV for voltage programming and or in REMOTE CC for current programming Use the REMOTE LOCAL button and push this button se...

Страница 15: ...o S and S See fig 4 5 and fig 4 6 With remote sensing the voltage on the load can be kept constant The voltage drop in the load leads will be compensated This feature is not recommended for normal use because it can easily give problems Max 2 V per load lead can be compensated Note that the voltage drop in the leads decreases the max output voltage rating In fig 4 7 it can be seen that on a 15 V p...

Страница 16: ...aster via CON B and CON C use standard UTP cables RJ45 On all units put DIP switch 4 of SW1 in position DOWN to set the units in M S series mode After turning the units on again the slaves will be in Remote CV mode and the Keylock see previous paragraph is activated This is because the unit automatically detects the presence of the RJ45 connector in CON C if this cable is connected to another unit...

Страница 17: ...o each other to have a low inductance Not following these instructions can cause instability The S and S could be connected to the load if desired but this is not recommended because of the complexity and possible instability 4 17 PARALLEL OPERATION OF FAST PROGRAMMING VERSIONS Master Slave operation is not recommended Normal parallel operation can give problems each combination has to be tested f...

Страница 18: ...emote CV and or Remote CC LED should be on The unit works OK in manual control but in programming mode the output voltage current has a large error Probably the fuse in series with Ø pin 1 of programming connector tripped the fuse F27_1 650 mA is a self resetting type see fig 5 1 To check the fuse F27_1 measure the voltage between Ø and the minus output during the fault condition The voltage shoul...

Страница 19: ... because of a bad connection Disconnect the mains wait a few minutes and try again Note the following As soon as the ACF LED is on the settings for Remote CV Remote CC and Keylock will be saved If the unit turns back on it will have the same settings For the setting of Output On Off after turning the unit back on the position of DIP switch 2 on SW1 is determining If the ACF situation lasts a few s...

Страница 20: ...brated and normally need no further calibration After installation of a new or different interface no calibration is needed Only in special situations for example after repairing a unit calibration can be necessary 6 5 METER CALIBRATION DIGITAL METERS The full scale indication can be calibrated with R25_31 and R25_36 on P596 see fig 6 2 6 6 SPECIAL CALIBRATIONS The following calibrations must be d...

Страница 21: ...e official Journal of the European Communities EN 61000 6 3 2007 Generic Emissions residential light industrial A1 2011 EN 61000 3 2 2014 Power Harmonics EN 61000 3 3 2013 Voltage fluctuation and flicker EN 61000 6 1 2007 Generic Immunity residential light industrial EN 61000 6 2 2005 Generic Immunity industrial environment EN 60950 1 2006 Safety of IT equipment A1 2010 A11 2009 A12 2011 A2 2013 E...

Отзывы: