SAFETY INSTRUCTIONS

Page 2 - 1

2  SAFETY INSTRUCTIONS SM3300 Interfaces

1

Caution

The following safety precautions must be observed during all phases of operation, service and repair of this equipment.
Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture
and intended use of this equipment and may impair the built-in protections within. Delta Elektronika shall not be liable for
user’s failure to comply with these requirements.

2

Installation Category

The Delta Elektronika power supplies have been evaluated to installation category II (Over voltage category II).

3

Grounding of Mains Input

This product is a safety Class 1 instrument. To minimize shock hazard, the instrument chassis must be connected to the AC
Power Supply mains through a three or four conductor power cable for resp. a single or three phase unit, with the ground
wire firmly connected to an electrical ground (safety ground) at the power outlet.

For instruments designed to be hard-wired to supply mains, the protective earth terminal must be connected to the safety
electrical ground before another connection is made. Any interruption of the protective ground conductor, or disconnection of
the protective earth terminal will cause a potential shock hazard that might cause personal injury.

4

Grounding of Power Output

If the output of a unit is specified to deliver maximum 60VDC, and either the negative or positive power output is grounded,
the voltage on the power outputs and sense connections can be considered safe.

Caution 1:

If a low voltage unit has both power outputs floating, or if the output is in series with an external high AC or DC

voltage, the negative power output can exceed the safe value in respect to ground as specified in the above warning!

Caution 2

: Although a high voltage unit is set to a safe voltage below 60VDC, for safety it must always be considered as high

voltage unit!  Wrong operation, a programming error or an external defect can result in an unsafe high output voltage.

For more information and schematics regards Grounding and Safety, see the special application note

"Safe operation of a

power supply" on the Delta Elektronika website.

5

Fuses

Fuses must be changed by authorized Delta Elektronika service personnel only, for continued protection against risk of fire.

6

Input Ratings

Do not use an AC Supply which exceeds the input voltage and frequency rating of this instrument. The input voltage and
frequency rating of the Delta Elektronika power supply series are stated in de accompanying datasheet.

7

Live Circuits

Operating personnel must not remove the instrument cover. No internal adjustment or component replacement is allowed by
non Delta Elektronika qualified personnel. Never replace components with the power cable connected. To avoid injuries,
always disconnect power, discharge circuits and remove external voltage sources before touching components.

8

Parts Substitutions & Modifications

Parts substitutions and modifications are allowed by authorized Delta Elektronika service personnel only. For repairs or
modifications the unit must be returned to a Delta Elektronika service facility.

Warning:

When the positive power output can exceed 60VDC in respect to the negative output, additional external
measures must be taken to ensure safety isolation of the power outputs and sense connections.

Warning:

When the negative power output of the unit can exceed 60VDC / 42.4Vpk in respect to ground, additional
external measures must be taken to ensure safety isolation of the power outputs and sense connections.

The standard LAN and Interlock connectors and optional interfaces are at ground level and can be considered
safe if the negative power output of the unit does not exceed 1000VDC / 707Vpk in respect to ground.

Содержание INT MOD ANA

Страница 1: ...SM 3300 Interfaces INT MOD SIM INT MOD CON INT MOD SER INT MOD DIG INT MOD ANA ...

Страница 2: ......

Страница 3: ...le with other Delta Elektronika 15p analog interfaces Factory calibrated for optimum accuracy Analog controller interface INT MOD ANA Features 8 inputs Logic high 2 5 30V Logic low 0V 8 Open Drain outputs 0 30V max 200mA Programmable via Ethernet or sequences Digital user I O INT MOD DIG Features 4 relays with make and break contacts Additional floating Interlock with 24V enable system Programmabl...

Страница 4: ...onfigurable Ri 13 5 mΩ 54 5 mΩ 115 mΩ 1 35 Ω 5 45 Ω Response time Ri Output Voltage load 0W Output current step Rise time 10 90 Fall time 90 10 13 5 mΩ 16 5 V 20 200 A 3 ms 3 ms 54 5 mΩ 33 66 V 10 100 5 50 A 1 25 1 25 ms 1 25 1 25 ms 115 mΩ 50 100 V 6 6 66 3 3 33 A 2 25 2 25 ms 2 25 2 25 ms 1 35 mΩ 165 330 V 2 20 1 10 A 2 25 2 25 ms 2 25 2 25 ms 5 45 mΩ 330 660 V 1 10 0 5 5 A 2 5 2 25 ms 2 5 2 25 ...

Страница 5: ...e 24VDC 15 30VDC 12kOhm Insulation prog connectors internal circuits prog connectors earth 1000 VDC Reinforced isolation acc EN60950 1 EN61010 1 max 60VDC Safety EN 60950 EN 61010 Operating Temperature 20 to 50 C Humidity max 95 RH non condensing up to 40 C max 75 RH non condensing up to 50 C Storage temperature 40 to 85 C Mounting Pluggable SM3300 interface slots 1 2 3 and 4 See paragraph Hardwar...

Страница 6: ...prog connectors earth 1000 VDC Reinforced isolation acc EN60950 1 EN61010 1 max 60VDC Safety EN 60950 EN 61010 Operating Temperature 20 to 50 C Humidity max 95 RH non condensing up to 40 C max 75 RH non condensing up to 50 C Storage temperature 40 to 85 C Mounting Pluggable SM3300 interface slots 1 2 3 and 4 See paragraph Hardware Installation in this manual Maximum 4 per unit Programming connecto...

Страница 7: ... open 7 Ohm max 30V 200mA Insulation prog connectors internal circuits prog connectors earth 1000 VDC Reinforced isolation acc EN60950 1 EN61010 1 max 60VDC Safety EN 60950 EN 61010 Operating Temperature 20 to 50 C Humidity max 95 RH non condensing up to 40 C max 75 RH non condensing up to 50 C Storage temperature 40 to 85 C Mounting Pluggable SM3300 interface slots 1 2 3 and 4 See paragraph Hardw...

Страница 8: ...hm Power Sink Overload 5 V logic 1 Ro 500 Ohm AC Fail 5 V logic 1 Ro 500 Ohm DC Fail 2 5 V logic 1 Ro 500 Ohm 2 output voltage 5 beyond set point Remote ShutDown with 5V 1 mA or relay contact Insulation prog connector internal circuits prog connector earth 1000 VDC Reinforced isolation acc EN60950 1 EN61010 1 max 60VDC Safety EN 60950 EN 61010 Operating Temperature 20 to 50 C Humidity max 95 RH no...

Страница 9: ...cified in the above warning Caution 2 Although a high voltage unit is set to a safe voltage below 60VDC for safety it must always be considered as high voltage unit Wrong operation a programming error or an external defect can result in an unsafe high output voltage For more information and schematics regards Grounding and Safety see the special application note Safe operation of a power supply on...

Страница 10: ...n condensing up to 50 C Altitude up to 2000 m Pollution degree 2 Caution risk of electrical Shock Instruction manual symbol The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual Protective ground conductor terminal o Off supply I On supply WEEE Waste Electrical Electronic Equipment 1 Correct Disposal of this Product Applicable in the Eu...

Страница 11: ... be inserted in slot 2 3 or 4 See figure 3 1 The simulation interface cannot be used in combination with an an alog interface Please remove the analog interface if installed be fore using the simulation interface Unscrew the 2 torx T10 screws and remove the slot cover Insert the interface and place the 2 screws back to secure the inter face 5 UNIT CONFIGURATION The unit will automatically detect t...

Страница 12: ...r the simulation W m table 3 2 6 2 DYNAMIC EFFICIENCY TEST The simulation module can run a dynamic mppt efficiency test as specified in the EN50530 annex B To run this test extra parameters are required These parameters are specified in table 3 3 The dynamic efficiency test uses the same configuration parameters as described in chapter but varies the irradiation levels of these parameters specifie...

Страница 13: ...ication also ren ders the photovoltaic curve calculated with the entered values The application reads the voltage and current measure ments of the power supply and displays these in the graph Figure 3 5 shows the Photovoltaic Simulation application To calculate a new photovoltaic curve enter all required parameters and click Calculate If one of the parameters changes in the window the calculation ...

Страница 14: ... web interface and the simulation interface au tomatically corrects the output voltage 9 LEADLESS SENSING SIMULATION The simulation interface can automatically compensate for voltage drops over the leads without using sense leads This simulation type has three different modes o Calculate resistance In this mode the resistance of the cable is calculated by means of the materials electrical resistiv...

Страница 15: ...upply programming source is the correct slot Check the simulation interface is in the corresponding simulation type and simulation mode Check the simulation interface configuration When the simulation type has been changed all settings are cleared to pre vent unpredictable behavior 11 3 INTERFACE DOES NOT CORRECT THE OUTPUT VOLTAGE OR CURRENT Check if the simulation type is enabled Check the simul...

Страница 16: ...it manual how to do this 4 HARDWARE INSTALLATION Warning Never make connections to the Power Input the Power Output or the Sense Connector when the SM3300 unit is connected to the mains supply Safety covers are used to cover these in and outputs INSERT INTERFACE IN THE UNIT Switch off the unit Disconnect the unit from the mains supply Wait for 3 minutes to allow internal capacitors to discharge Se...

Страница 17: ...nt is 2A Pinning CON M 6 Relay 1 NC 5 Relay 1 NO 4 Relay 1 Common 3 Relay 2 NC 2 Relay 2 NO 1 Relay 2 Common Pinning CON N 6 Relay 3 NC 5 Relay 3 NO 4 Relay 3 Common 3 Relay 4 NC 2 Relay 4 NO 1 Relay 4 Common INTERLOCK ENABLE CON K The Interlock input pin 1 is initially connected to pin 3 common Replace the link by two wires and a switch for example a cabinet door switch when its function is requi...

Страница 18: ...face back in position 4 HARDWARE INSTALLATION Warning Never make connections to the Power Input the Power Output or the Sense Connector when the SM3300 unit is connected to the mains supply Safety covers are used to cover these in and outputs INSERT INTERFACE IN THE UNIT Switch off the unit Disconnect the unit from the mains supply Wait for 3 minutes to allow internal capacitors to discharge Selec...

Страница 19: ...he optional Power Sink also the programming down speed is nearly load independent With optional high speed programming the rise and fall time is 5 to 25 times faster Note that with this option the output ripple is higher 8 MONITORING VIA SERIAL INTERFACE Via the programming command MEASURE the voltage current or power can be monitored See the manual Ethernet Sequencer Programming SM3300 for detail...

Страница 20: ...upply is in the required mode CV or CC When programming a voltage the unit must be in CV mode when programming a current the unit must be in CC mode 10 CALIBRATION Calibration of the interface is not applicable 11 Settings Settings via the web page Bustype USBcom Device channel nr ch 1 Baudrate bps 9600 Data bits 8 Stop bits 1 Flowcontrol None Parity bits None Slewrate Disabled Termination Disable...

Страница 21: ...r to the SM3300 unit manual how to do this 4 HARDWARE INSTALLATION Warning Never make connections to the Power Input the Power Output or the Sense Connector when the SM3300 unit is connected to the mains supply Safety covers are used to cover these in and outputs INSERT INTERFACE IN THE UNIT Switch off the unit Disconnect the unit from the mains supply Wait for 3 minutes to allow internal capacito...

Страница 22: ...o pin 10 or pin 15 The user inputs have a working range of 2V 30V use a common zero and have an impedance of approximately 22kOhms The maximum load of the 5V is 100mA See figure 6 4 and table 6 1 for the pinning of CON F USER OUTPUTS CONNECTOR CON G The 8 user outputs are Open Drain with common zero When an output is TRUE it is pulled down to 0V Otherwise the output is open The output impedance is...

Страница 23: ...quired refer to the SM3300 unit manual how to do this 4 HARDWARE INSTALLATION Warning Never make connections to the Power Input the Power Output or the Sense Connector when the SM3300 unit is connected to the mains supply Safety covers are used to cover these in and outputs INSERT INTERFACE IN THE UNIT Switch off the unit Disconnect the unit from the mains supply Wait for 3 minutes to allow intern...

Страница 24: ...om a low to a high output voltage is nearly load independent See the unit s specifications Programming down to a low voltage takes more time on lighter loads This is caused by the output capacitors which can only be discharged by the load because the power supply cannot sink current With the optional Power Sink also the programming down speed is nearly load independent With optional high speed pro...

Страница 25: ...e unit If the input is high the RSD icon is shown in the display see fig 7 8 It is also possible to use a relay contact or a switch to shut the unit down see fig 7 9 In standby mode the power supply consumes very little power Note also via Eth or other interfaces RSD can be activated 11 REFERENCE VOLTAGE A 5 114V reference voltage is available on the connector This reference can be used to control...

Отзывы: