Chapter 4 Parameters
|
4-24
Revision May 2008, ME14, SW V3.04
(2) Fans and Pumps
Motor Spec. 60Hz
V
220
10
1.5
60.0f
Factory Settings
Set value
No.
Pr.03
60.0
Pr.04
60.0
Pr.05
220.0
Pr.06
30
Pr.07
50.0
Pr.08
1.5
Pr.09
10.0
30
50
Motor Spec. 50Hz
V
220
10
1.3
50.0f
Set value
No.
Pr.03
50.0
Pr.04
50.0
Pr.05
220.0
Pr.06
25
Pr.07
50.0
Pr.08
1.3
Pr.09
10.0
25
50
(3) High Starting Torque
Motor Spec. 60Hz
V
220
18
1.5
60.0f
Factory Settings
Set value
No.
Pr.03
60.0
Pr.04
60.0
Pr.05
220.0
Pr.06
3
Pr.07
23.0
Pr.08
1.5
Pr.09
18.0
3
23
Motor Spec. 50Hz
V
220
14
1.3
60.0f
Set value
No.
Pr.03
50.0
Pr.04
50.0
Pr.05
220.0
Pr.06
2.2
Pr.07
23.0
Pr.08
1.3
Pr.09
14.0
2.2
23
Pr.10
Acceleration Time 1
Unit: 0.1 or 0.01 sec
Pr.11
Deceleration Time 1
Unit: 0.1 or 0.01 sec
Pr.12
Acceleration Time 2
Unit: 0.1 or 0.01 sec
Pr.13
Deceleration Time 2
Unit: 0.1 or 0.01 sec
Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec
Factory Setting: 10.0
Pr.10. This parameter is used to determine the time required for the AC drive to ramp from 0
Hz to its Maximum Output Frequency (Pr.03). The rate is linear unless the S-Curve (Pr.14) is
“Enabled”.
Pr.11. This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum Output Frequency (Pr.03) down to 0 Hz. The rate is linear unless the S-
Curve (Pr.14) is “Enabled”.
Pr.12 and Pr.13: Provide an additional Accel/Decel time although Time 1 is the default. A
Multi-Function input terminal must be programmed to select Accel/ or Decel/ Time 2 and the
terminal must be closed to select Accel/Decel Time 2 (See Pr.38 to Pr.42).
In the below diagram, suppose the Maximum Output Frequency is 60 Hz (Master Freq),
Minimum Output Frequency (start-up) is 1.0 Hz, and accel/decel time 1 is 10 seconds. The
actual time for the AC drive to accelerate from start-up to 60 Hz is 9.83 seconds (deceleration
time is also 9.83 seconds), can be determined by the formula.
Содержание VFD-M Series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Страница 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Страница 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 145: ...Appendix A Specifications A 4 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...