Chapter 5 Troubleshooting
|
Revision May 2008, ME14, SW V3.04
5-3
5.4 Low Voltage (Lv)
Low voltage
Is input power correct? Or power cut,
including momentary power loss
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Restart after reset
Check if there is any malfunction
component in
power supply circuit
or disconnection
Change defective component
and check connection
Check if voltage is
within specification
Make necessary corrections,
such as change power supply
system for requirement
Check if there is heavy load
with high start current in the
same power system
Check if Lv occurs when
breaker and magnetic
contactor is ON
Suitable
transformer
power
capacity
Check if voltage b
and - is greater than
200VDC (for 115V/230V models)
400VDC (for 460V models)
517VDC (for 575V models)
Maybe AC motor drive has malfunction.
Please contact DELTA.
Control circuit has malfunction or
misoperation due to noise. Please
contact DELTA.
Yes
Using the different power
supply for this drive and
heavy load system
Содержание VFD-M Series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 12: ...Chapter 1 Introduction Revision May 2008 ME14 SW V3 04 1 3 1 1 4 External Parts and Labels ...
Страница 17: ...Chapter 1 Introduction 1 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 21: ...Chapter 2 Installation and Wiring 2 4 Revision May 2008 ME14 SW V3 04 Good Not allowed ...
Страница 121: ...Chapter 4 Parameters 4 86 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 145: ...Appendix A Specifications A 4 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...
Страница 149: ...Appendix B Accessories B 4 Revision May 2008 ME14 SW V3 04 ...
Страница 173: ...Appendix CHow to Select the Right AC Motor Drive C 8 Revision May 2008 ME14 SW V3 04 This page intentionally left blank ...