Warning

 

 

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring. Other detail infromation about programming and intructions is compatible with SA/SX/SC series; please see 
PLC Application Manual. For more information about the optional peripherals, please see individual product 
instuction shee or “DVP-PLC Application Manual: Special module”. 

 

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, in order to prevent hazard to users or damage the PLC.. 

 

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC. 
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly 
grounded 

. DO NOT touch terminals when power on. 

 

Introduction

 

Thank you for choosing DELTA’s PLC DVP series. The DVP-SC series has a 12-points (8 input  4 
outputs) MPU with powerful instructions (the same instruction sets as SA/SX/SC series) for use. It also has an 
8K Steps program memory and high-speed pulse inputs(X10 and X11)/outputs (Y10 and Y11). For high-speed 
pulse, total bandwidth can up to 130KHz and 100KHz maximum for single input/output. Besides, it also 
provides instructions of position control and zero point return to use with high-speed pulse output. It could 
connect all extension units of DVP-SS series for various applications.

 

 Product Profile and Outline 

 

Unit: mm 

Battery replacement:

 Battery replacement must be finished within 3 minutes, or the internal data of the PLC 

(including the program area, RTC and latched registers) could be lost or destroyed. 

 

1  Status indicators of POWER, RUN and ERROR 

12  Extension port for wire to connect extension module/unit 

2  RUN/STOP switch 

13  Mounting hole 

3  VR0: Start-up by M1178/D1178 Corresponding value  14  DIN rail track (35mm) 

4  VR1: Start-up by M1179/D1179 Corresponding value  15  Extension unit clip 

5  DIN rail clip 

16  RS-485 communication port (Master/Slave) 

6  I/O terminals 

17  DC Power input   

7  I/O point indicators 

18  2 pin removable terminal (standard accessory) 

8  COM1 (RS-232) (Rx) indicator 

19  Power input cable (standard accessory) 

9  COM2 (RS-485) (Tx) indicator 

20  Battery cover 

10  COM1 (RS-232) port 

21  Battery socket connection 

11  Nameplate 

22  Battery holder 

ENGLISH 

 Specifications 

 

   

Model 

    Item 

DVP12SC11T 

Power supply voltage 

MPU: 24V DC (-15% ~ +20%) (With DC input reverse polarity protection), 

Fuse 

2A/250V AC

 

Power consumption 

4W MAX 

Insulation resistance 

5 M

Ω

  and above at 500V DC (Between all inputs/outputs and earth) 

Noise immunity 

ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L 
and N (All DVP units should be grounded directly to the ground pole). 

Environment 

Operation: 0

°

C ~ 55

°

C (temperature), 50 ~ 95% (humidity), pollution degree 2;   

Storage: -25

°

C ~ 70

°

C (temperature), 5 ~ 95% (humidity) 

Vibration/shock resistance 

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

Weight (approx. g) 

158 

Certificates 

 

 

 

 

Input Point Electrical Specification 

Input type 

DC (SINK or SOURCE) 

Input current 

24V DC 5mA 
Off 

 On, 

X0, X1, 18.5V DC and above 
X2 ~ X5, 16.5V DC and above 
X10, X11, 18.5V DC and above 

Active level 

On 

 Off, 

X0 ~ X5, X10, X11, below 8 V DC 

Hardware 

The constant of filter time is 10ms 

X0~X5 

Software 

0 ~ 20ms (Set by D1020) 

Hardware 

The constant of filter time is 4.7us   

 

Response time 

X10, X11 

Software 

0 ~ 1,000 times (Set by D1021) 

 

 

Output Specifications

 

Output type 

Transistor 
0.3A/1 point @ 40

°

C (Room Temp.) 

Rated current 

When the output of Y0 and Y1 is high-speed pulse above 3KHz, Y0, Y1 ,Y10 and Y11 = 30mA 

Voltage specification 

5 ~ 30V DC 

Max. inductive load 

7.2W/24V 
Internal 

None 

Output protection 

Outside 

Rated value according to the load 

Y0, Y1 

9W/1 point 

Maximum loading 

Y10, Y11 

0.9W/1 point 

Off 

 On 

< 20us 
< 1us (Y10, Y11 only) 

Response time 

On 

 Off 

< 30us 
< 1us (Y10, Y11 only) 

Battery life: 

Temperature (

°

C) 

25 

50 

70 

Life (years) 

Precision of calendar timer: 

At 0

°

C/32

°

F, less than -117 seconds error per month.   

At 25

°

C/77

°

F, less than 52 seconds error per month. 

At 55

°

C/131

°

F, less than -132 seconds error per month 

 Model Name & I/O Configuration 

Input/Output Specification 

Input Unit 

Output Unit 

Model 

Power 

Points 

Type 

Points 

Type 

I/O Configuration 

24V DC 

Sink/Source 

X0~X5 

Transistor 

Y0, Y1 

DVP12SC11T  24V DC 

24VDC 

Sink/Source 

Hi-speed 
X10, X11 

Transistor 

Hi-speed 

  Y10, Y11 

S/S

X0

X1

X2

X3

X4

X5

X10

X11

C0

Y0

C1

Y1

C2

Y10

C3

Y11

 

 Installation & Wiring 

4.1 PLC Mounting Arrangements and Wiring Notes   

1.  When installing the DVP series PLC, make sure that it is installed in an 

enclosure with sufficient space (as shown on the right) to its 
surroundings so as to allow heat dissipation.   

2.  I/O signal wires or power supply should not run through the same 

multi-wire cable or conduit.   

DV P
M P U

D

D

D

D

D > 50 mm

 

3.  Please use 22-16AWG (1.5mm) wiring (either single or multiple core) 

for I/O wiring terminals. The specification for the terminals is as shown 
on the right.     

4.  PLC terminal screws should be tightened to a torque of 1.95 kg-cm (1.7 

in-lbs). 

5.  Use copper conductor only, 60/75

°

22 -1 6AW G

< 1.5m m

 

4.2 Wiring Notes 

 Environment 

1.  DO NOT store the PLC in an atmosphere that is dusty, smoky, with metallic debris or corrosive or 

flammable gases. 

2.  DO NOT store the PLC in an environment with high temperature or high humidity. 
3.  DO NOT install the PLC on a shelf or on an unstable surface. 

 Power Input Wiring 

DVP-SC series input power supply is DC input. Please take a note of listed items when operating DVP-SC 
Series. 
1.  Please make sure the power is at terminals 24V DC and 0V (power range is 20.4 ~ 28.8V DC). When 

voltage is lower than 20.4V DC, PLC will stop operating, all outputs will be Off and ERROR LED will flash 
continuously. 

2.  If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too 

long or the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the 
power is restored, the PLC will return to operation automatically. (There are latched auxiliary relays and 
registers inside of the PLC, please be aware when programming.) 

DC Input Type 

24V

2A

S/S

X0

X1

X2

20.4V~28.8V

0V

DC/DC

5V

 

 Safety Wiring

 

Since the PLC is used to control numerous devices, motion of either one device could affect the motion of other 
devices. Therefore the breakdown of a device would consequently be detrimental to the whole auto control 
system, thus the result is dangerous. Please use the recommended wiring below for the power input 
(DVPPS01/DVPPS02): 

 

Power supply for AC loads 

 

Power Circuit Protection Fuse (3A) 

 

Power indicator 

 

Emergency stop 
The machinery must provide a quick manual method 
disconnecting all system power. 

 

Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be the 
isolation unit of the power circuit to prevent the possible instability 
of the system when the power is supplied on and off.   

 

DVPPS01/DVPPS02 

 

 

Earth 

M C

MC

N

L

1

1

2

3

4

5

6

7

8

G u ar d
L im it

MC

 

 

Power supply: 
AC: 100 ~ 240V AC, 50/60Hz 

 Input Point Wiring

 

The DC power is used for DC input signal. Two types of DC wiring are used: SINK and SOURCE, defined as 
follows: 

Sink

 = Current flows into the common terminal S/S 

Source

 = Current flows out of common terminal S/S 

Sinking

S/S

X0

 

Sou rcin g

S/ S

X0

 

 

Input Point Loop Equivalent Circuit 

Wiring Loop 

DC Type 

  (DC Signal IN)   

SINK Mode 

+2 4V

24 G

S/S

X0

24V D C

S I NK

+ 5V

 

+24V

OV

Sink  Ty pe

X1

X2

S/S

X0

24 VD C

 

 

 

Input Point Loop Equivalent Circuit 

Wiring Loop 

DC Type 

  (DC Signal IN)   

SOURCE Mode 

+ 24 V

24 G

S/S

X0

24 V D C

S OU R C E

+ 5 V

 

Source Type

X1

X2

S/S

X0

+24V

OV

24VD C

 

 Output Point Wiring

 

DVP-**-**-11-T

TRANSISTOR  OUTPUT

LED

Y0

C0

LOAD

<  0.3A

T
R

G

 

1.  Two types of DVP-SC Series PLC output modules Transistor.    For the electrical specification, please refer 

to the function specification. 

2.  Please watch out the connection of common terminals while wire the outputs. Output terminal Y0 uses one 

common terminal C0, Y1 uses C1, and Y10 uses C2, Y11 uses C3, as shown below: 

C0 Y0 C1 Y1 C2 Y10 C3 Y11

 

Action indication: When the output point is active, the corresponding indicator at the front panel will be on. 

3.  Isolated circuit: The optical coupler is used to isolate signals between PLC internal circuits and input 

modules. 

 Input/Output Wiring

 

24V DC

S/ S

X0

X1

X5

X1 0

X11

Y0

C0

Y1

C1

Y1 0

C2

C3

Y11

LOAD

CH 0

CH 1

100KHz

100KHz

100K Hz

100K Hz

30 mA~0.3 A

5 VD C~ 30 V DC

High-speed pulse 
in put s

High-speed pulse 
in put s

X10 and X11 can be used as common inputs 
or inputs of high-speed counter

High-speed pulse 
outp uts

High-speed pulse 
outp uts

Y10 and Y11 can be used as common outputs or 
high-speed pulse outpus used with position control 

 

 

注意事項 

 

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與

SA/SX/SC

系列

相容,詳細說明請見

DVP-PLC

應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或

DVP-PLC

應用技術手冊【特殊模組篇】。

 

 

本機為開放型

(OPEN TYPE)

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊意

外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外衝
擊本體,造成危險及損壞。

 

 

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

產品簡介

 

DVP-SC

系列為一

12

點(

8

輸入點

  + 4

輸出點)

PLC

主機,除提供豐富的指令集(與

SA/SX/SC

指令集相同)、

8K Steps

的程式記憶體並具有高速脈波輸入

(X10

X11)

及輸出

(Y10

Y11)

,總和頻寬可達

130KHz

,單一輸入或

輸出最高可達

100KHz

。另外配合高速脈波輸出功能,提供定位控制及原點復歸指令。可連接

SS

系列全系列擴充

機,滿足各種應用場合。

 

 

產品外觀及各部介紹

 

 

尺寸單位:

mm 

電池安裝

電池安裝

電池安裝

電池安裝:

:更換電池時,請在 3 分鐘內完成,否則 PLC 內部資料(包含程式區,萬年曆及停電保持暫存器)有可

能會消失或被破壞。

 

 

電源、運行及錯誤指示燈

 

12 

擴充機連接口

 

RUN

STOP

開關

 

13 

擴充機定位孔

 

VR0

M1178

啟動/

D1178

對應值

 

14 

DIN

軌糟

  (35mm) 

VR1

M1179

啟動/

D1179

對應值

 

15 

擴充機固定扣

 

DIN

軌固定扣

 

16 

RS-485

通訊口

  (Master/Slave) 

輸出/入端子

 

17 

電源輸入口

 

輸出

/

入點指示燈

 

18 

2 pin

脫落式端子(標準附件)

 

RS-232

通訊接收

  (Rx) 

指示燈

 

19 

電源輸入連接線(標準附件)

 

RS-485

通訊傳送

  (Tx) 

指示燈

 

20 

電池蓋

 

10 

RS-232

程式輸出/入通訊口

 

21 

電池插座連接

 

11 

銘牌

 

22 

電池座

 

繁體中文

繁體中文

繁體中文

繁體中文    

 

電氣規格

 

 

 

 

機種

   

 

項目

 

DVP12SC11T 

電源電壓

 

主機:

24V DC (-15% ~ +20%)

(具直流輸入電源極性反接保護)

 

電源保險絲容量

 

2A/250V AC 

消耗電力

 

4W MAX 

絕緣阻抗

 

5 M

Ω以上(所有輸出/入點對地之間

500V DC

 

雜訊免疫力

 

ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz ~ 1GHz, 10V/m 

接地

 

接地配線之線徑不得小於電源端

L, N

之線徑(多台

PLC

同時使用時,請務必單點接地)

 

操作/儲存環境

 

操作:

0°C ~ 55°C

(溫度),

50 ~ 95%

(濕度),污染等級

儲存:

-25°C ~ 70°C

(溫度),

5 ~ 95%

(濕度)

 

耐振動/衝擊

   

國際標準規範

IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

重量(約

, g

 

158 (g) 

 

輸入點電氣規格

 

輸入形式

 

直流(

SINK

SOURCE

 

輸入電流

 

24V DC 5mA

10 ms 

Off 

 On, 

X0

X1

18.5V DC

以上

 

X2 ~ X5

16.5V DC

以上

 

X10

X11

18.5V DC

以上

 

動作位準

 

On 

 Off, 

X0 ~ X5

X10

X11

8V DC

以下

 

硬體

 

濾波時間常數

  10 ms 

一般輸入

 

X0 ~ X5 

軟體

 

D1020

可作

0 ~ 20 ms

的調整

 

硬體

 

濾波時間常數

  4.7us 

反應時間

 

高速輸入

 

X10

X11 

軟體

 

D1021

0 ~ 1,000

次的調整

 

 

輸出點電氣規格

 

輸出點形式

 

電晶體

 

0.3A/1

@ 40°C 

高速脈波輸出

3KHz

以上時

 

電流規格

 

Y0

Y1

Y10

Y11

30mA 

電壓規格

 

30V DC 

一般輸出

 

9W/1

 

最大負載

 

高速輸出

 

0.9W/1

 

一般輸出

 

Off

On 20us, On

Off 30us 

反應時間

 

高速輸出

 

Off

On 1us, On

Off 1us 

電池壽命

電池壽命

電池壽命

電池壽命:

 

溫度

  (

°

C) 

25 

50 

70 

壽命

  (

萬年曆的精度

萬年曆的精度

萬年曆的精度

萬年曆的精度(

(秒

秒):

):

):

):

 

0

°

C/32

°

F

時,每月最大誤差

  -117

秒。

 

25

°

C/77

°

F

時,每月最大誤差

52

秒。

 

55

°

C/131

°

F

時,每月最大誤差

  -132

秒。

 

Отзывы: