Ethernet Communication Module IFD9507

 

DVP-PLC Application Manual

 

17

Explanations: 

Every MW records the values in 1 register. 

MW#201 MW#202 MW#203 MW#204 MW#205 MW#206 MW#207 MW#208 MW#209  MW#210

Device 1  Device 2  Device 3  Device 4 Device 5 Device 6 Device 7 Device 8 Device 9  Device 10

 

MW#211 MW#212 MW#213 MW#214 MW#215 MW#216

Device 

11 

Device 

12 

Device 

13 

Device 

14 

Device 

15 

Device 

16 

 

M W # 3 0 1 :   M o n i t o r e d   Sta t u s  

Explanations: 

Every MW records the status in a 16-bit register. 1 = normal; 0 = abnormal. 

b15 b14 b13 b12 b11 b10

b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 

Device 

16 

Device 

15 

Device 

14 

Device 

13 

Device 

12 

Device 

11 

Device 

10 

Device 

Device 

Device 

Device 

Device 

Device 

Device 

Device 

Device 

Setting up Device Address and Relay Address in Slave Mode (For Modbus TCP protocol 
only) 

MIP# 

Attribute 

Content 

Explanation 

Default

Latched

0 ~ 50 

R/W 

Corresponding 
address 

Max. 100 addresses are allowed. High 
byte for 1 address and low byte for 1 
address. 

0 Yes 

50 ~ 249 

R/W 

Relay IP address 

Total 100 IPs. Every address (1 byte) 
corresponds to 1 IP address (4 bytes). 

0 Yes 

Symbol “R” refers to read only; “R/W” refers to read and write. 

 

M I P # 0 :   C o r r e s p o n d i n g  A d d r e s s

 

Explanations: 

The low bytes of MIP#0 are for the first address, and the high byte are for the second address, and so on. 

 

M I P # 5 1   ~   # 5 2 :   C o r r e s p o n d i n g   I P  f o r   t h e   1

s t

  D e vi c e  A d d r e s s

 

Explanations: 

Example 1: If you wish to convert “192.168.0.1” into C0A80001 (hex), write A8C0 into MIP50 and H0100 into 

MIP51. 

Example 2: Data in address 1 have to correspond to 192.168.0.8. Data in address 2 have to correspond to 

192.168.0.6. To complete such settings, write H0102 into MIP0, H0800 into MIP50, HA8C0 into MIP51, H0600 

into MIP52, and HA8C0 into MIP53. 

Setting up Device Address and Other Network Settings in Slave Mode 

Parameter 

Explanation 

Device address 

Address of Modbus device 

Relay IP address 

Corresponding IP address for a device 

Priority/Time Tick 

Scale of time. Unit: ms 

Timeout Tick 

Scale of timeout 

Timeout 

Timeout = Time Tick × Timeout Tick (Unit: ms) 

Содержание Ethernet Communication Module IFD9507

Страница 1: ...IFD9507 Ethernet Communication Module Application Manual...

Страница 2: ......

Страница 3: ...structure and operation of IFD9507 can install operate wire and maintain it DO NOT connect input AC power supply to any of the I O terminals otherwise serious damage may occur Check all the wirings ag...

Страница 4: ...eneral Status Code Reference Volume 1 CIP Common Specification Appendix B 20 9 4 Connection Manager Service Request Error Codes Reference Volume 1 CIP Common Specification Table3 5 29 20 10 SETTING UP...

Страница 5: ...g up Unlocking Password 49 12 2 Password Loss Returning to Default Settings by RS 232 51 12 3 IP Filter Protection 51 12 4 Application of E Mail 53 12 5 Monitoring Mode 54 12 6 Application of Virtual...

Страница 6: ...ion under MDI MDI X auto detection it does not need to jump wire in selecting the network cable See the contents below for more detailed instructions on IFD9507 module 1 1 Features z Auto detects 10 1...

Страница 7: ...immunity ESD IEC 61131 2 IEC 61000 4 2 8KV Air Discharge EFT IEC 61131 2 IEC 61000 4 4 Power Line 2KV Digital Input 2KV Communication I O 2KV RS IEC 61131 2 IEC 61000 4 3 80MHz 1GHz 10V m 1 4GHz 2 0G...

Страница 8: ...et button Ethernet indicator 2 Power indicator 7 Module name 3 Address setup rotary switch 8 RS 485 connector digital input points power input point earth point 4 Communication format baud rate setup...

Страница 9: ...finition RJ 45 sketch PIN Signal Definition 1 Tx Positive pole for data transmission 2 Tx Negative pole for data transmission 3 Rx Positive pole for data receiving 4 N C 5 N C 6 Rx Negative pole for d...

Страница 10: ...Rate for Modbus Communication Switch setting Baud rate Switch setting Baud rate 1 110 7 4 000 2 150 8 9 600 3 300 9 19 200 4 600 A 38 400 5 1 200 B 57 600 6 2 400 C 115 200 2 10 Feed through Terminal...

Страница 11: ...1 How to Install 3 2 How to Connect IFD9507 to Network Connect IFD9507 to the Ethernet hub by twisted pair cable CAT 5e IFD9507 has auto MDI MDIX function therefore IFD9507 does not need to jump wire...

Страница 12: ...I DO points DI high byte DO low byte 0x300 Yes 8 Reserved 9 R Error code Displaying the errors See the table of error codes 0 No 10 Reserved 11 R W Communication time out For setting up the communicat...

Страница 13: ...Client COM1 RS 232 setting 0 Delta Configuration 1 Modbus Mode 0 ASCII 1 RTU 00000000 0 Disable Disable Serial Master Delta configuration ASCII 00000001 1 Disable Disable Serial Master Delta configura...

Страница 14: ...to no error occurring Code Indication How to correct 01 F7 Node address of the scan module when operating normally F0 Returning to default setting F1 IFD9507 being powered F2 Power supply in low volta...

Страница 15: ...us communication datum Default 0ms For example if you wish to set up the communication delay time as 100ms manually write 100 into BR12 BR 13 Keep Alive Time s Explanations For setting up the communic...

Страница 16: ...ng the function b15 1 Enabling b15 0 Disabling R W 0 Yes b4 b14 Reserved R W 0 No b2 b3 Type of event enabled when RX alarm point is triggered b3 b2 Reserved 0 0 Trigger E Mail 0 1 Reserved 1 0 Reserv...

Страница 17: ...evice monitored No of the station to be monitored recording the address of the device monitored 0 Yes 33 200 R W Reserved 201 R Monitored value Every MB records the value in the 16 bit device 0 No 202...

Страница 18: ...be monitored 0 YES 2 R W Address of the device monitored Recording the address of the device monitored 0 YES 3 32 R W No of station monitored address of the device monitored No of the station to be mo...

Страница 19: ...e allowed High byte for 1 address and low byte for 1 address 0 Yes 50 249 R W Relay IP address Total 100 IPs Every address 1 byte corresponds to 1 IP address 4 bytes 0 Yes Symbol R refers to read only...

Страница 20: ...eption code Explanation 0x01 Illegal function 0x02 Illegal data addresss 0x03 Illegal data value 0x04 Slave device failure 0x0A Gateway path unavailable 0x0B Gateway target device failed to respond 8...

Страница 21: ...Set_Attribute_Single Used to modify an attribute 0x4E Connection Manager Object Forward_Close Closes a connection 0x54 Connection Manager Object Forward_Open Opens a connection maximum data size is 51...

Страница 22: ...the request is not supported 15 Too much data The service supplied more data than was expected 16 Object does not exist The object specified does not exist in the device 20 Invalid parameter A paramet...

Страница 23: ...the target device 0x01 0x0315 INVALID SEGMENT IN CONNECTION PATH Invalid Segment Type or Segment Value in Connection Path This extended status code is the result of a device being unable to decode the...

Страница 24: ...al 22 3 Double click on the module to be set up to enter the setup page The first page overviews the basic status of the module 4 The next page is for basic network setup Consult your ISP for relevant...

Страница 25: ...ion Manual 23 10 2 Basic Settings The basic settings include parameters such as module name network settings and serial communication The basics 1 Module name There can be many IFD9507s on the network...

Страница 26: ...the packet to the gateway and the gateway will send the packet to another subnet Incorrect setting may cause the destination equipment unable to communication to IFD9507 To see of your setting is cor...

Страница 27: ...ter Control Panel Network Connection click on Local Area Connection 2 You will see the Local Area Connection Status window Click on Properties 3 Click on Internet Protocol TCP IP 4 Enter 192 168 0 1 i...

Страница 28: ...e message or error message into the subject of the E Mail When the E Mail is triggered IFD9507 will send the messages to the user by E Mail Mail settings 1 Mail alarm setup There are 3 mail alarms to...

Страница 29: ...settings Every address allows max 63 English characters For example see the figure above when Alarm 1 is triggered the E Mail will be sent to Test1 delta com tw and Test2 delta com tw When Alarm 2 is...

Страница 30: ...read will be sent back directly from the register in IFD9507 3 Serial slave mode used when in Modbus TCP protocol The instruction sent from the master is received and transferred to the network Pleas...

Страница 31: ...duct bitwise AND operation between the allowed IP and subnet mask and destination IP and subnet mask If the two values obtained are the same the subnet mask is allowed by the network For example assum...

Страница 32: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 30 1 Dest IP This is Destination IP address 2 Timeout ms Timetick Timeout tick Timeout Available time tick 20 215...

Страница 33: ...e set interval time 5 T O RPI Target to originator requested packet interval When the trigger occurs the packet is sent to the source within the set interval time 6 In Instance Target input buffer Ins...

Страница 34: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 32 1 Listen Port Destination IP Range 1 024 65 535 2 Fix Length Length of the packet to be transmitted Unit byte 3 Start Item...

Страница 35: ...33 1 3 bytes of characters as the start of a packet 4 Stop Item 1 3 bytes of characters as the stop of a packet 10 9 Virtual COM Virtual COM converts the data transmitted to RS 232 to Ethernet Select...

Страница 36: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 34 Open Virtual COM setup page...

Страница 37: ...d you will see all the devices connected on the network Select the module you need and press OK Relevant information of the device will be imported automatically Press OK to complete the setup Once th...

Страница 38: ...To prevent the set values in IFD9507 from being modified you can set up passwords to lock the settings in IFD9507 Setting up password 1 Password setup Check the Modify box to set up the password 2 Con...

Страница 39: ...not For example if you have locked IFD9507 but forget the password you have to return IFD9507 to default setting by RS 232 and all the settings will return to default ones Login password Password Ent...

Страница 40: ...ess Reset button for 2 seconds to return to default settings 11 Setting up Configuration by Homepage This section gives instructions on how to set up IFD9507 by homepage and explanations on each confi...

Страница 41: ...l 39 11 2 Basic settings The basic settings include parameters as module name network settings and series communication Please consult your Internet service provider for relevant network settings For...

Страница 42: ...bbreviation of electronic mail which transmits mails through the network IFD9507 has E Mail functions for the user to pre save a segment of text messages which can be a descriptive message or error me...

Страница 43: ...riggered by falling or rising 2 See 10 4 for how to set up SMTP server Mail From E mail Subject of Event Recipient E Mail Address columns 11 4 IP filter The IP filter is used for restricting the conne...

Страница 44: ...the column blank to disable the password protection function 2 Confirming password Enter the new password again Note Once the password is locked all the pages cannot be set up unless you unlock the p...

Страница 45: ...x Returning to default setting Returning to default setting Check Factory Setting box and click on Yes Note If you set up IFD9507 by RS 232 you can return to settings to default ones whether the passw...

Страница 46: ...address 3 Digit Selection The monitored value can be displayed in hex or decimal form 4 Monitor word Device addresses for setting up the word status of serial slave able to read the content in the cor...

Страница 47: ...e designate the station address and relay IP address Station address slave PLC address Gateway and PLC address cannot be the same Relay IP address serial master IP 11 8 Ethernet IP You can read data i...

Страница 48: ...ime exchange of messages across network 4 O T RPI Originator to target requested packet interval When the trigger occurs the packet is sent to the target within the set interval time 5 T O RPI Target...

Страница 49: ...can define your own format for data to be transmitted The items to be defined include the fixed length start item and stop item Select RS 232 or RS 485 to connect the device Switch to User Define pag...

Страница 50: ...item of data Range 1 3 When the start item and stop item are set IFD9507 will transmit data following the start item and stop item If the transmission time exceeds the Modbus time out IFD9507 will di...

Страница 51: ...d Application Setting up password by IFD9507 configuration Steps 1 Set up password in IFD9507 2 Unlock IFD9507 1 See 10 1 for the connection and how to set up the communication 2 Open the setup page a...

Страница 52: ...PLC Application Manual 50 4 Open the setup page again and IFD9507 is now locked by the password You cannot open any of the settings now Enter the password and press Confirm and you will be able to un...

Страница 53: ...lick on Yes to return to default settings in approx 5 10 seconds and the password will be cleared as well 12 3 IP Filter Protection Application Setting up IP filter protection Only connections to 192...

Страница 54: ...ication Module IFD9507 DVP PLC Application Manual 52 4 Enter 172 16 0 1 in No 2 IP and 255 255 255 0 in No 2 Netmask column Click on OK to complete the setting Only the equipment within the UP range c...

Страница 55: ...test Delta com tw 1 See 10 1 for the connection and how to set up the communication 2 Open the setup page and switch to Mail page 3 Setting up Mail page and check Mail Alarm Setup Enter SMTP server a...

Страница 56: ...nitor word functions 2 Monitor bit data in station address 1 H100 and H300 and word data in station address 1 H150 3 Monitor bit data in station address 2 H200 4 Monitor word data in station address 3...

Страница 57: ...07 DVP PLC Application Manual 55 3 The settings Note When the cache mode is enabled you do not need to modify the station address and device address You will read data from IFD9507 in which way you wi...

Страница 58: ...to connect IFD9507 to VFD E AC motor drive through the virtual COM port by VFDSoft Steps 1 Select User Define protocol and set the parameters in the serial master and serial slave to the ones consiste...

Страница 59: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 57 Open Virtual COM setup page...

Страница 60: ...7 DVP PLC Application Manual 58 Press OK and you will see all the devices connected on the network Select the module you need and press OK Relevant information of the device will be imported automatic...

Страница 61: ...Device Manger 2 Using Virtual COM in Delta VFDSoft Open Delta VFDSoft Setting up communication format COM Setup Enter the virtual COM COM2 set in the previous steps to Com Port column Next enter the...

Страница 62: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 60 Press OK and IFD9507 will be able to communicate with VFD E by VFDSoft...

Страница 63: ...ve Using Delta PLC DVP28SV11T to control AB PowerFlex 40P via IFD9507 Configure 22 COMM E IP Use AB software Driver Explorer Application to Set the PowerFlex40P 22CommE IP 1 Open Driver Explorer Appli...

Страница 64: ...elect Connect Serial Point to Point in Explore 5 Select Parameter List in 22 COMM E Ethernet IP and enter IP in IP Addr Cfg1 Cfg4 and Netmask in Subnet Cfg1 Cfg4 DCISoft configuration 1 Open DCISoft B...

Страница 65: ...IP Field 11 Select Cyclic in Trigger 12 Enter PowerFlex 40P parameter 1 4 2 2 2 byte 6 in In Instance In Size Out Instance Out Size Width Config Instance in turn 13 Press OK WPL program 1 Write contr...

Страница 66: ...4 Use WPL MODWR instruction to write 0101 set I O enable Flag 13 2 Serial Master Using AB PLC 1769 L32E to write Delta PLC DVP28SV11T bit and register via IFD9507 Configure RSLinx 1769 L32E 1 Open RSL...

Страница 67: ...it is successful it will show successful messages Configure IFD9507 1 Open DCISoft Basic configuration screen 2 Select Serial Master in Master Configuration 3 Select Static in IP Configuration 4 Ente...

Страница 68: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 66 Configure RSLogix 5000 1 Select New 2 Select controller type 1769 L32E and type Name click OK 3 Add new Ethernet module...

Страница 69: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 67 4 Select communications module 5 Select ETHERNET MODULE and click OK...

Страница 70: ...cation Manual 68 6 Enter module name Select Comm Format Data INT Enter instance 101 Size 100 Out Instance 100 Output Size 100 Configuration Instance 6 and Configuration Size 0 and IP 192 168 1 99 7 En...

Страница 71: ...to control instruction ON OFF 10 Using Move instruction move data to ENA01EIP O Data register Ex Set Delta PLC Y0 H0500 ON Send instruction MODBUS TCP 06 01 05 05 00 FF 00 1 H0006 Mov 06 to ENA01EIP...

Страница 72: ...Ethernet Communication Module IFD9507 DVP PLC Application Manual 70 11 Download this program and make the PLC 1769 L32E go online 12 Toggle Bit SW1...

Отзывы: