20
BATTERY REPLACE:
This LED function is to alert user
that the batteries should be replaced. When the
microprocessor in the UPS detects a battery fault, the
buzzer beep 0.1 second every 2 seconds. (Shown as
Figure 3-10)
BATTERY LOW:
This function is to inform user the
remaining power capacity of the batteries. When batteries
reach a low level condition, the UPS alarm will beep half
second every 1.5 seconds until running out of battery
capacity. (Shown as Figure 3-11)
SHORT CIRCUIT:
When the output of the UPS shorts in
“ON-LINE mode”
or
“ON-BATTERY mode”
, the UPS will
shut down (without output voltage). As soon as the short
circuit is happened, the fault LED will light on and the UPS
alarm will sound continuously. When remove short circuit,
the UPS output will recover. If short circuit is happened in
“BYPASS mode”
, the UPS will protect itself by tripping the
input breaker and shut down. (Shown as Figure 3-12)
3-12 De-rating Power
In the range of 130Vac to 160Vac, the UPS load capacity will decrease. This
function provides a wider operating power voltage range.
Figure 3-10
Battery Replace
Figure 3-11
Battery Low
Figure 3-12
Short Circuit