8.2  WITH A PROGRAMMABLE ROOM THERMOSTAT (PRT)  
OR PROGRAMMER (PROG)

 From the OFF mode, Simultaneously press and hold the 

1st and 4th buttons from the left (

i

) for 20 seconds. 

 After 10 seconds, the screen displays 

rSt1

.

Keep the button pressed until the screen displays 

rSt2

.

Release.

 Press and hold OK for 3 seconds until the rSt2 display 

flashes.

The system automatically returns to Shutdown 
(or OFF mode).

8/   RESTORING THE TECHNICAL UNIT TO 
FACTORY SETTINGS

20 s

3 s

The multizone kit offers an optional water network temperature monitoring function 
(hot and cold).
This function protects the system from overheating in the water network (protection of 
the slab and pipes) or from abnormally low temperature, which will generally lead to the 

formation of condensation on the flooring. 

 

This information is immediately sent to the end user via a defect fed back to 
the room thermostat.

Important:

 this feature still requires the connection of a safety device to the system 

(bimetallic strip on the circulator or condensation sensor) aimed to monitor the system's 

water temperature and to cut off the water flow if necessary.

Principle for the detection of excessively hot or cold water

Depending on the entered temperature limit value (to be set at the time of installation), 
the system scans the water temperature and reconciles it with the set limit value. If the 
water temperature is above (if the water is too hot) or below (if the water is too cold) the 
limit value after 30 minutes of circulator operation, the defect is detected and sent to the 
thermostat.
If a defect is found, the circulator is shut down immediately.
The system switches the thermostat to OFF mode.
The user must then contact the installer for a diagnosis or work on the heat pump or boiler 

in order to reduce the hot water flow temperature setting or feed the cold water setting 

back to the system.
The system can be restarted manually from a Master thermostat or a programmer. 
The water network's temperature monitoring function is reactivated.

9/  WATER TEMPERATURE MONITORING

Содержание DELTA 8000 BT

Страница 1: ...EN Technical unit for Delta 8000 system DELTA 8000 BT Installation instructions ...

Страница 2: ... Associating a room thermostat with a technical unit 33 6 1 With a Room Thermostat RT 33 6 2 With a Programmable Room Thermostat PRT 34 7 Configuring the technical unit 35 7 1 With a room thermostat RT 35 7 2 With a programmable room thermostat PRT or programmer PROG 36 8 Restoring the technical unit to factory settings 37 8 1 With a room thermostat RT 37 8 2 With a programmable room thermostat PR...

Страница 3: ... Red circulator and burner LEDs P and G Red valve LEDs 1 to 8 On Normal operation Relay closed Output on On Off Initial heating of the slab Relay open Output off Off Slow flashing Association mode Quick flashing Defect in progress Defect in progress 1 ON 6 5 4 3 2 DIP 8 8 7 Configuration switches Status LED Water monitoring input Circulator LED Burner LED Change over input output Valve outputs Valve...

Страница 4: ...tputs dry contact 2A Max 230V Valve outputs If you use 3 position actuators you will only be able to connect 4 valves to the technical unit switch SW3 ON If you need more outputs use another technical unit in Extension mode Valve power supply 24VAC DC or 230 V 240 V Main power supply 230 V 240 V Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Y1 SW3 OFF SW3 ON N N N N N N N N N ...

Страница 5: ...at manual PRT zone 1 PRT zone 2 PRT zone N BT Master SW1 OFF BT Extension SW1 ON 1 8 sorties 1 ON 6 5 4 3 2 DIP 8 8 7 1 ON 6 5 4 3 2 DIP 8 8 7 Bus 30m max Bus 30m max 1 8 sorties max 1 8 sorties max 1 8 sorties max BUS 1 BUS 2 BUS Bus 30m max BUS 1 BUS 2 BUS Example 3 Regulation with room by room programming PRT Programmable Room Thermostat Programmer RT zone 1 RT zone 2 RT zone N Bus 30m max BUS ...

Страница 6: ...lation Wireless programmers centralised programming Wireless programmable thermostats regulation room by room programming Window magnetic contacts activates the Frost Protection mode when a window is opened Presence absence detectors lower the temperature setting when the premises are left empty for a long period of time Outdoor temperature sensor Bus 1 8 sorties max Wireless programmer Radio bus ...

Страница 7: ...ride mode This mode overrides the 100 operation for initial heating Set switch 5 to ON On the technical unit the circulator LED and valve output LEDs are illuminat d The Status LED is off On the room thermostat RT or the programmable thermostat PRT a specific display indicates that initial heating is in progress All the switches are set to OFF by default HP Heat pump TU Technical unit 5 SWITCH CON...

Страница 8: ...t with which the thermostat is to be associated Confirm with OK The screen displays CF21 Select the transmitter and press OK The screen displays CF22 Select the limitation value and press OK to confirm To exit the current mode press or turn the dial 3 s 1 CF20 a product associated with an output also controls the following outputs in the same manner if these are not associated 7 CONFIGURING THE TE...

Страница 9: ...orm the setting Confirm with OK 1 CL04 only appears in Heat production mode SW2 OFF refer to the technical unit s manual and for underfloor heating CF21 0 or for ceiling ductable CF21 2 Passive cooling water flow for cooling heating in OFF mode 2 CL06 CL07 if the limit is exceeded or reaches switch over to OFF mode The defect comes up on the thermostat screen see Troubleshooting Water monitoring i...

Страница 10: ...the connection of a safety device to the system bimetallic strip on the circulator or condensation sensor aimed to monitor the system s water temperature and to cut off the water flow if necessary Principle for the detection of excessively hot or cold water Depending on the entered temperature limit value to be set at the time of installation the system scans the water temperature and reconciles i...

Страница 11: ...d by disturbances Move your products around to check the radio range Radio reception defect on an associated presence detector Battery of an associated window magnetic contact defective Replace the batteries of the prod uct in question Battery of an associated presence detector defective 10 TROUBLESHOOTING Main power supply 230V 240V 10 50 60 Hz Valve power supply 24V or 230V 240V 4A Max for all v...

Страница 12: ...www deltadore com 09 18 ...

Отзывы: