Compound range eg –12.5 to +12.5 mbar 

(Models GR3, GR6 - range BC) 

For  normal  operation,  negative  pressure  may  be 

applied  to  the  LP  port,  whereby  the  HP  port  is  left 

open to atmosphere and the set point is between 0 

and +12.5 mbar. 

 

For  reverse  operation,  negative  pressure  may  be 

applied  to  the  HP  port,  whereby  the  LP  port  is  left 

open to atmosphere and the set point is between 0 

and –12.5 mbar. 

For positive pressures, the opposite applies. 

 

It is recommended that the minimum setting is to be 

not less than 5% of FS either side approaching zero. 

 

MAINTENANCE 

 

Inspections  should  be  carried  out  at  quarterly  to 
yearly 

intervals 

depending 

upon 

operating 

conditions. 
Where a terminal enclosure is fitted, isolate the unit 
from process and power and remove the lid.  Check 
all terminals for tightness.  Check that cable tails are 
not  fouled  or  chafed.    Check  for  internal 
condensation.  Rectify as necessary. 
It is recommended that instruments used to provide 
an  alarm  are  operated  periodically  to  ensure  they 
are functioning correctly. 
If further maintenance is required, seek advice from 
DELTA  CONTROLS  before  attempting  repair  or 
replacement of parts. 
 
Should  the  diaphragm  fail  the  process  will  vent  to 

atmosphere via a control orifice without pressurising 

the  switch  enclosure.  Periodically  ensure  the  vent 

area  does  not  become  blocked  and  vent  plug  has 

not  degraded.  Ensure  that  the  vent  area  is  not 

obstructed.

 

 

 

THE 

EQUIPMENT 

CONTAINS 

NO 

USERREPLACEABLE PARTS AND IS NOT 
INTENDED  TO  BE  REPAIRED  BY  THE 
USER.  REPAIR  OF  THE  EQUIPMENT  IS 
TO 

BE 

CARRIED 

OUT 

BY 

THE 

MANUFACTURER, OR THEIR APPROVED 
AGENTS,  IN  ACCORDANCE  WITH  THE 
APPLICABLE CODE OF PRACTICE. 

ELECTRICAL 

ISOLATION—THESE 

PRODUCTS  ARE  NOT  SUITABLE  FOR 
ELECTRICAL 

ISOLATION. 

ALWAYS 

ISOLATE  CIRCUIT  TO  CARRY  OUT  ANY 
ELECTRICAL WORK. 

 

REPLACEMENT PARTS:

 

 

Use  only  factory  authorised  parts  and  the  fitting 

instructions that are supplied. 

 

Содержание GR2

Страница 1: ... the control spring the diaphragm moves causing a push rod to actuate a snap acting micros witch Temperature model GR7 works in the same way as the Pressure models with the exception that the applied pressure comes from the expansion of a vapour enclosed in either a rigid stem or semi rigid thermal system CERTIFICATIONS Intrinsically Safe Models Intrinsically safe models carry the following label ...

Страница 2: ...All models The instruments are designed to be mounted vertically with the process connection underneath However mounting up to 45 from the vertical in any plane is acceptable although a small calibration shift may occur They can be mounted either direct to process or to a wall or panel using the back plate provided Select the mounting point so as to avoid stresses excessive shock vibration or temp...

Страница 3: ...FORE WIRING DO NOT EXCEED ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAME PLATES THE LEADS ARE FACTORY SEALED SO IT IS UNNECESSARY TO SEAL THE CON DUIT TO THE CONDUIT NIPPLE HOWEV ER THE LEADS MUST BE SUITABLY PROTECTED AGAINST MECHANICAL DAMAGE AND TERMINATED IN A SUITA BLE JUNCTION BOX OR TERMINAL FA CILITY IN ACCORDANCE WITH LOCAL AND NATIONAL CODES EACH CON DUCTOR IS PROVIDED WITH AN IDENT...

Страница 4: ...s See Fig 5 1 Isolate the instrument from process and power Adjustment may be carried out with the unit live 2 Loosen both cover screws 3 Rotate cover anti clockwise to allow access 4 Using a screwdriver rotate the range adjuster to obtain the desire setting Turn right to left to increase the setting An appropriate setting is shown by pointer against reference scale 5 Rotate cover clockwise to clo...

Страница 5: ...e not fouled or chafed Check for internal condensation Rectify as necessary It is recommended that instruments used to provide an alarm are operated periodically to ensure they are functioning correctly If further maintenance is required seek advice from DELTA CONTROLS before attempting repair or replacement of parts Should the diaphragm fail the process will vent to atmosphere via a control orifi...

Страница 6: ...PT GROUND SCREW H OR R MOUNTING HOLES FOR M5 SCREWS VENTING DEVICE WHEN FITTED H OR R PROCESS CONNECTOR UNITS DIM A NPT MALE INCHES 1 85 MM 47 OTHERS INCHES 1 46 MM 37 JUNCTION BOX CODES C D 4 MOUNTING HOLES 4 5 mm DIA SUITABLE FOR M4 SCREWS MAX HEAD DIA 7 5 mm CONDUIT ENTRY M20 x 1 5 20 0 79 15 0 0 59 45 0 1 77 171 0 6 73 ...

Отзывы: