LED Indication
Network Condition
Possible Problem
Multiple errors on one or
more segments.
A wiring error or shorted
wiring exists on segment.
More than one device is
communicating at the same
time.
A group of devices using the
same power source are not
sharing a common ground.
Segment communications
is being blocked by the
DZNR.
DZNR is attempting to correct
a segment fault by blocking
that port for 120 seconds.
If the DZNR shows network instability and/or frequently locks out, do not attempt a flash
upgrade to any devices on the network. The flash load could fail and the device will
require factory service.