Delta Controls DSC-1616 Скачать руководство пользователя страница 5

Document Edition 3.4 

Page 5 of 12 

Controller Configuration 

Controller Type 

Various products have the capability of being configured as one of several 

possible controller types, which represents the network level that it will reside 

on in the network architecture (Area, System, Subnet).  Other than the one 

controller acting as a router, all other controllers on the same network segment 

must be configured the same. 

Area - 

Configures the controller as an Area level controller on a network. This 

is an option only on the Ethernet model and is the setting when the controller is 

connected to an Ethernet network (typically between buildings) and is acting as 

a router from one LAN to either a network of System controllers or Subnet 

controllers. 

System

 - Configures the controller as a System level controller on a network of 

System controllers. This is the setting when the controller is connected to an 

Ethernet or BACnet MS/TP network with other System controllers or is a single 

head-end controller for a network of Subnet controllers. 

Subnet

 - Configures the controller as a Subnet level controller on a Subnet of 

similar controllers. This is the setting when the controller is connected to a 

BACnet MS/TP network with other Subnet controllers. 

Note

: This also determines where the DIP or MAC address is mapped into the 

controllers BACnet address and which other portions of its BACnet address are 

inherited when DNA is enabled. 

 

 

AREA

SYSTEM

SUBNET

 

 

Derived Network Addressing 

The 

DNA jumper

 comes ON by default. This allows the controller to 

automatically configure a BACnet controller address. This should NOT be 

removed unless you are assigning a BACnet controller number through 

software. The BACnet controller number should not be confused with the DIP 

switch setting, and each controller must still have a unique dip switch address 

even when using software to define the controller number. 

DNA

 

Controller Addressing  

The Dip Switch is a binary switch. Each individual DIP switch represents a 

unique value, which forms the controller address when added together. 

To set the address, simply move the switches that add up to the controllers 

desired address to the ON position. 

Example: If the controller is to be address 5 on the network, set the switch 

numbered 4 and the switch numbered 1 (equals 5) to the On position. 

Note

: Each controller on the same MS/TP segment must have a unique DIP 

switch address. 

 

 

 

Содержание DSC-1616

Страница 1: ...may be configured as an MS TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers The 16 universal inputs are jumper configurable and the 16 analog out...

Страница 2: ...statically sensitive device Proper ESD protection ground strap should be used when installing this product so that damage to the product does not occur Danger of explosion if the battery is incorrect...

Страница 3: ...ing The DSC 1616 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Страница 4: ...Delta Controls Page 4 of 12 Board Layout...

Страница 5: ...a Subnet of similar controllers This is the setting when the controller is connected to a BACnet MS TP network with other Subnet controllers Note This also determines where the DIP or MAC address is m...

Страница 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Страница 7: ...he proper specified cabling must be used to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers s...

Страница 8: ...ept the signal used by the input device Place the jumper for each input in the correct location on the Input Type Selector Block The diagram to the right shows the factory default selection of 10 K 4...

Страница 9: ...good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port and the red LED fl...

Страница 10: ...ation 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers Serial RS 232 BACnet PTP Communication 9600 19200 38400 default Service Port RJ 11 Jack Used with Delta Controls s...

Страница 11: ...Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4 3 1996 R...

Страница 12: ...l interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...

Отзывы: