Product Specifications 

 

Power Requirements 

 

24 VAC, 60Hz, Class 2 

Power Consumption 

 

30 VA 

Ambient Ratings 

 

32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing) 

Communication Ports 

Ethernet 

 

10 BaseT @ 10Mbps 

 

BACnet IP, BACnet over Ethernet 

 

NET1 

 

BACnet MS/TP (RS-485) 

 

Communication: 9600, 19200, 38400, 76800 bps (Default) 

 

Maximum of 99 controllers 

OR 

 

LINKnet 

 

Communication: 76800 bps 

 

Maximum of 12 LINKnet controllers including up to two DFM 
controllers 

 

NET2 

 

BACnet MS/TP (RS-485) 

 

Communication: 9600, 19200, 38400, 76800 bps (Default) 

 

Maximum of 99 controllers 

OR 

 

LINKnet 

 

Communication: 76800 bps 

 

Maximum of 12 LINKnet controllers including up to two DFM 
controllers 

 

Serial 

 

RS-232 

 

BACnet PTP 

 

Communication: 9600, 19200, 38400 (default) 

 

Service 
Port 

 

RJ-11 Jack 

 

Used with Delta Controls service tool devices (for example, CON-768) 

Inputs 

 

16 Universal Inputs (10 bit), jumper configurable for the following input types: 

 

0-5 VDC 

 

0-10 VDC 

 

10 K

 Thermistor 

 

Dry Contact (using 10 K

 Thermistor jumper setting 

 

4-20 mA 

Outputs 

 

16 Universal Outputs c/w LED status indication (including HOA status) 

 

0-10 VDC @ 20 mA maximum per output 

 

Software configurable as binary or analog 

 

Hand/Off/Auto Switches (c/w position feedback) 

Technology 

 

32 bit processor 

2 MB (16 megabit) Flash Memory 

512 KB SRAM memory 

Listings 

 

UL 916 Listed 

BTL Listed 

UL 864 Listed (DSC-1616E-UL864 model only) 

Compliance 

 

CE 

FCC 

Содержание DSC-1616

Страница 1: ...may be configured as an MS TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers The 16 universal inputs are jumper configurable and the 16 analog out...

Страница 2: ...statically sensitive device Proper ESD protection ground strap should be used when installing this product so that damage to the product does not occur Danger of explosion if the battery is incorrect...

Страница 3: ...ing The DSC 1616 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Страница 4: ...Delta Controls Page 4 of 12 Board Layout...

Страница 5: ...a Subnet of similar controllers This is the setting when the controller is connected to a BACnet MS TP network with other Subnet controllers Note This also determines where the DIP or MAC address is m...

Страница 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Страница 7: ...he proper specified cabling must be used to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers s...

Страница 8: ...ept the signal used by the input device Place the jumper for each input in the correct location on the Input Type Selector Block The diagram to the right shows the factory default selection of 10 K 4...

Страница 9: ...good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port and the red LED fl...

Страница 10: ...ation 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers Serial RS 232 BACnet PTP Communication 9600 19200 38400 default Service Port RJ 11 Jack Used with Delta Controls s...

Страница 11: ...Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4 3 1996 R...

Страница 12: ...l interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...

Отзывы: