Wiring General 

All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 
transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product 
and output loads. 

 

Risk of Electric Shock or Fire 

 

More than one disconnect switch may be required to de-energize the 
equipment before servicing. 

 

Input Class 2 Power Supplies are interconnected. Use only Class 2 
sources suitable for interconnections. 

 

 

 

 

 

All terminals are acceptable for Class 2 Circuit connections only 

 

Use copper conductors only 

 

Apply minimum 6.0 lb-in torque for tightening field wires into the terminal 
blocks 

Power 

This product is designed to use a 24VAC Class 2 power supply. A single transformer may be used to power 
multiple controllers and/or auxiliary field devices (actuators, etc.) provided the following conditions are met: 

 

All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified devices 
will damage both the transformer and connected equipment. 

 

The transformer is properly sized, including line losses for the total VA requirements. 

 

Polarity is observed between controllers (with respect to 24~ and Gnd). 

 

Each controller is grounded as shown in the diagram below. This is important to protect equipment and 
ensure a common ground reference for RS-485 communications. 

 

The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits). 

 

 

 

Make sure to ground the controller using the ground lug that is available on the 
controller. The controller uses the ground lug to establish a common reference for 
communications. If the controller is not grounded then communication problems 
may occur. 

Page 5 of 10 

Содержание DFM-1616

Страница 1: ...intended to fit a range of Central Plant type applications requiring up to 48 Inputs and 48 Outputs When the DFM 1616 is combined with the ASM 24E it forms a controller suited for Elevator Control ap...

Страница 2: ...ry with type CR2032 Equipment damage or loss of data may occur if these procedures are not followed as specified Installations requiring CE conformance All wiring for CE rated products must use an ext...

Страница 3: ...Document Edition 2 4 Board Layout Page 3 of 10...

Страница 4: ...set the address simply move the switches that add up to the controllers desired address to the ON position Example If the controller is to be address 5 on the network set the switch numbered 4 and th...

Страница 5: ...sformer may be used to power multiple controllers and or auxiliary field devices actuators etc provided the following conditions are met All devices MUST be wave rectified Mixing power between wave an...

Страница 6: ...hen 100 ft of cable length do not require network terminators LINKnet Controller Outputs with Communication Failure When using this controller special consideration must be given to the fail value of...

Страница 7: ...turns on to indicate that the controller has power applied Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate Network NET1 LINKnet RS485 Communication Status Indicato...

Страница 8: ...puts 16 Universal Inputs 10 bit jumper configurable for the following input types 0 5 VDC 0 10 VDC 10 K Thermistor Dry Contact using 10 K Thermistor jumper setting 4 20 mA Outputs 16 Universal Outputs...

Страница 9: ...999 Power Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4...

Страница 10: ...accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case t...

Отзывы: