Delta Controls
Access Door Module
Page 3 of 26
O
THER
R
ELEVANT
D
OCUMENTS
•
Access Control System Technical Reference Manual
•
Access Control System V3.30 Release Notes
•
RS-485 Network Installation Guide (DOC818-11)
•
ORCAview Operator Guide
•
V3.30 ORCAview Technical Reference Manual
•
V3.30 Release Notes
•
Delta Controls System Description
P
RODUCT
S
PECIFICATIONS
Power Requirements
•
24 VAC, 50/60Hz, 75 VA (dedicated transformer) Class 2 Device
•
4A Slow Blow Fuse for controller and device power
•
7.0 AH Lead Acid Battery Connection (for battery charging and battery back-up of the controller, as
well as all devices connected and powered from the controller)
•
DC Power out +14 VDC @ 0.25A with a resetable fuse (can supply one Access System Manager
with battery backup)
•
Card reader power +5 VDC @ 50mA or +12 VDC @ 160mA for each card reader individually fused
with a resetable fuse
•
Door Lock power +12 VDC @ 350mA for each lock individually fused with a resetable fuse
•
Auxiliary DC Power out +12 VDC @ 50mA fused with a resetable fuse
Ambient Ratings
•
32º to 131º F (0º to 55º C)
•
10 to 90% RH (non-condensing)
Communication Ports
NET1 - Main LAN (LINKnet)
•
Communications Speed @ 76,800 BPS
•
Maximum one Access Door Modules per Access System Manager (ASM)
•
Visual LED status of network activity