LP GAS HOOK-UP
–
DELSOL
G
AS
G
RILL
DELSOL grill for the use of LP gas comes equipped with its own regulator, which
MUST NOT
be removed. Install the factory-supplied hose and regulator assembly as shown. Connect the
3
/
8
” flare
end of the hose to the grill coupling using a ¾” open wrench. Do not apply pipe sealant to the
3
/
8
” flare
connection. Connect the regulator to the LP cylinder hand tighten it, do not use a wrench. Check for
leaks using soapy water solution. (Reference page 8 for leak test procedure).
Note:
An enclosure for LP gas cylinder must be vented on the level of the cylinder valve and at floor
level. The effectiveness of the opening(s) for purposes of ventilation shall be determined with the LP gas
supply cylinder in place. This shall be accomplished by one of the following:
a.
One side of the enclosure shall be fully open; or
b.
For an enclosure having four sides, a top and a bottom:
1.
At least two ventilation openings at cylinder valve level shall be provided in the sidewall,
equally sized, spaced at 180 degrees (3.14 rad), and unobstructed. Each opening shall
have a total free area of not less than 1/2 square inch per pound (7.1 cm
2
/kg) of stored
fuel capacity and not less than a total free area of 10 square inches (64.5 cm
2
).
2.
Ventilation opening(s) shall be provided at floor level and shall have a total free area of
not less than ½" square inch per pound (7.1 cm
2
/kg) of stored fuel capacity and not less
than a total free area of 10 square inches (64.5 cm
2
). If ventilation openings at floor
level are in a sidewall, there shall be at least two openings. The bottom of the openings
shall be at floor level and the upper edge no more than 5 inches (127 mm) above the
floor. The openings shall be equally sized, spaced at 180 degrees (3.14 rad) and
unobstructed.
! WARNING !
DO NOT STORE SPARE LP-GAS CYLINDER UNDER OR NEAR THIS APPLIANCE.
NEVER FILL THE CYLINDER BEYOND 80 PERCENT FULL.
FAILURE TO DO SO, A FIRE CAUSING DEATH OR SERIOUS INJURY MAY OCCUR.