DeLonghi WIR2 Скачать руководство пользователя страница 6

If the actual Btu/Hr used is less than the max-
imum Btu/Hr the space can support, the space
is an unconfined space. You will need no addi-
tional fresh air ventilation.

VENTILATION AIR
Ventilation Air From Inside Building

This fresh air would come from an adjoining
unconfined space.
When ventilating to an adjoining unconfined
space, you must provide two permanent open-
ings: one within 12”  of the ceiling and one
within 12” of the floor on the wall connecting
the two spaces (see options 1 and 2, figure 2).
Follow the 

National Fuel gas Code

ANSI

Z223.1/NFA 54, section air for combustion
and ventilation 

for required size of ventilation

grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grilles
or ducts. You must provide two permanent open-
ings: one within 12”of the ceiling and one within
12” of the floor. Connect these items directly to the
outdoors. These spaces include attics and crawl
spaces. Follow the 

National Fuel gas Code

ANSI

Z223.1/NFA 54, section air for combustion and
ventilation 

for required size of ventilation grills or

ducts.

IMPORTANT: Do not provide openings for inlet
or outlet air into attic has a thermostat-con-
trolled power vent. Heated air entering the
attic will activate the power vent.

6

WARNING: if the area in which the heater
may be operated is smaller than that defined
as an unconfined space or if the building is of
unusually tight construction, provide adequate
combustion and ventilation air by one of the
methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 section 5.3 or
applicable local codes.

Ventilation 

grills into adjoining

room, 

Option 1

Or remove
door into 
adjoining room, 
Option 3

Ventilation 
grills into adjoining
room, 
Option 2

12"

12"

Fig.2  Ventilation Air from Inside Building

Ventilated attic

Outlet air

Outlet 

air

Inlet 

air 

Inlet air 

Ventilated 

crawl space

To crawl 

space

To attic

Fig.3 Ventilation Air From Outdoors

GB  29-01-2004  16:33  Pagina 6

Содержание WIR2

Страница 1: ... suppli er WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy gen from the room in which it is insta...

Страница 2: ...s heater Improper use of this heater can cause seri ous injury or death from burns fire explo sion electrical shock and carbon monoxide poisoning DANGER Carbon monoxide poisoning may lead to death WARNING Any change to this heater or its control can be dangerous WARNING Do not use any accessory not approved for use with this heater Due to high temperatures the appliance should be located out of tr...

Страница 3: ...sed or stored under dusty conditions 9 Do not use heater if any part has been under water Immediately call a qualified service technician to inspect the room heater and to replace any part of the con trol system and any gas control which has been under water 10 Turn off and unplug heater and let cool before servicing Only a qualified service person should service and repair heater 11 Operating hea...

Страница 4: ...following ventilation classification 1 Unusually Tight Contruction 2 Unconfined Space 3 Confined Space The information on page 4 through 6 will help you classify your space and provide adequate ventilation Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must...

Страница 5: ...ly the space volume by 20 to deter mine the maximum Btu Hr the space can support ________ volume of space x 20 51 200 maximum Btu Hr the space can support Example 2560 cu ft volume of space x 20 51 200 maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appli ances in the space Vent free heater ____________ Btu Hr Gas water heater ____________ Btu Hr Gas furnace ____________ ...

Страница 6: ...to the outdoors These spaces include attics and crawl spaces Follow the National Fuel gas Code ANSI Z223 1 NFA 54 section air for combustion and ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic has a thermostat con trolled power vent Heated air entering the attic will activate the power vent 6 WARNING if the area in w...

Страница 7: ...eat source If you have a central heating system you may run system s circulating blower while using heater This will help circulate the heat throughout the house In the event of a power outage you can use this heater as you primary heat source WARNING A qualified service person must install heater Follow all local codes WARNING maintain the minimum clearances shown in figure 4 if you can provide g...

Страница 8: ...gas pressure heater regula tor damage could occur Install the external regulator with the vent pointing down as shown in figure 6 Pointing the vent down pro tects it from freezing rain or sleet 8 WARNING This appliance requires a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator WARNING A qualified service person must connect heater to gas supply Follow all local codes WARNIN...

Страница 9: ...nat ural gas or using compressed air 4 Check all joints of gas supply piping sys tem Apply a non corrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fit tings for leaks 9 WARNING Use pipe joint sealant that is resist ant to liquid petroleum LP gas WARNING test all gas pip...

Страница 10: ...al gas open main gas valve locat ed on or near gas meter For propane LP gas open propane LP supply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve thermostat gas valve see figure 8 9 or 10 Apply a non corrosive leak detection fluid to all joints Bubbles form ing show a leak 5 Correct all leaks at once 6 Light heater see operating...

Страница 11: ...ollow the safety information If you don t smell gas go to the next step 5 Turn thermostat control knob counterclock wise to the pilot position Press in thermostat control knob for 5 seconds see fig 11 Note you may be running this heater for the first time after hooking up to gas supply If so you may need to press in control knob for 30 seconds or more This will allow air to bleed from the gas syst...

Страница 12: ...tion Shutting off heater Turn thermostat control knob clockwise to the OFF position INSPECTING HEATER Check pilot flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure 13 shows a correct pilot flame pattern Figure 14 shows an incorrect pilot flame pat tern The incorrect pilot flame is not touching the thermocouple This will cause the thermo couple to cool When the thermocouple co...

Страница 13: ...16 shows a incorrect burner flame pattern If burner flame pattern is incorrect as shown in figure 16 turn heater off see to turn off gas to appli ance page 12 see troubleshooting pages 16 through 18 13 correct burner fig 16 fig 15 incorrect burner GB 29 01 2004 16 33 Pagina 13 ...

Страница 14: ...e the pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes 2 Inspect burner pilot for dust and dirt 3 Blow air through the ports slots and holes in the burner 4 Never insert objects into the pilot tube Clean the pilot assembly also A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly see figure 14 With the unit off light...

Страница 15: ...al numbers of your heater how heater was malfunctioning Type of gas used natural gas purchase date Usually we will ask you to return the defective part to the factory Heater ratings in british thermal units per hour BTUH Model Model Setting Input BTUH Type gas Pressure regulator setting Orifice Drill size n of radiators Inlet gas pressure inches of water LP GAS NAT GAS pilot ON pilot ON 400 13660 ...

Страница 16: ... combustion 1 Burner orifice is clogged or damaged 2 Low line pressure 3 Ods pilot is partially clogged 1 Open window and or door for ventilation 2 Contact local natural gas company 3 Clean ODS pilot see cleaning and maintenace page 14 Gas odor even when con trol knob is in OFF posi tion 1 Gas leak See warning statement at top of page 2 Thermostat control valve defective 1 Locate and correct all l...

Страница 17: ...tion 1 Turn on gas supply or open equipment shutoff valve 2 Fully press in control knob while pressing ignitor button 3 Continue holding down control knob Repeat igniting opera tion until air is removed 4 Clean ODS pilot see cleaning and maintenance page 14 or replace ODS pilot assembly 5 Replace gas regulator 6 Turn control knob to pilot position When ignitor button is pressed in there is a spark...

Страница 18: ... odor dur ing initial operation 1 Residues from manufacturing processes 1 Problem will stop after a few hours of operation Heater produces whistling noise when burner is lit 1 turning control knob to HIGH position when burner is cold 2 Air in gas line 3 Air passageways on heater blocked 4 Dirty or partially clogged burner ori fice 1 Turn control knob to LOW position and let warm up for a minute 2 ...

Страница 19: ...ce or accidents Also con sequential and incidental damages resulting from the use of this product or ari sing out of any breach of contract or breach of this warranty are not recoverable under this warranty Some states do not allow the exclusion or limitation of inci dental or consequential damages so the above limitation may not apply to you How Do You Get Service If repairs become necessary or s...

Отзывы: