1-20
Ra c k I n s t a l l a t i o n G u i d e
www
.dell.com | support.dell.com
Marking the Rack
You must allow 2 U (88 mm or 3.5 inches) of vertical space for each system you install in the
two-post rack.
Universal-Hole Spacing Racks
Industry-standard two-post racks with universal-hole spacing have an alternating pattern of
three holes per U with center-to-center hole spacing (beginning at the top hole of a 1-U
space) of 15.9 mm, 15.9 mm, and 12.7 mm (0.625 inch, 0.625 inch, and 0.5 inch) for the
front and back vertical column of holes (see Figure 1-13).
F i g u r e 1 - 1 3 .
Tw o - P o s t , O p e n - F r a m e R e l a y R a c k U n i v e r s a l - H o l e S p a c i n g
Wide-Hole Spacing Racks
Some two-post racks with wide-hole spacing have an alternating pattern of two holes per U
with center-to-center hole spacing (beginning at the top hole of a 1-U space) of 31.7 mm
and 12.7 mm (1.25 inches and 0.5 inch) for the front and back vertical column of holes (see
Figure 1-14).
44 mm 1.75 inches (1 U)
15.9 mm (0.625 inch)
12.7 mm (0.5 inch)
15.9 mm (0.625 inch)
15.9 mm (0.625 inch)
Содержание PowerEdge 2650
Страница 2: ......
Страница 3: ...w w w d e l l c o m s u p p o r t d e l l c o m Dell Systems Rack Installation Guide ...
Страница 34: ...1 28 Rack Installation Guide w w w d e l l c o m s u p p o r t d e l l c o m ...
Страница 37: ...w w w d e l l c o m s u p p o r t d e l l c o m Systèmes Dell Guide d installation du rack ...
Страница 73: ...w w w d e l l c o m s u p p o r t d e l l c o m Dell Systeme Rack Installationsanleitung ...
Страница 108: ...3 32 Rack Installationsanleitung w w w d e l l c o m s u p p o r t d e l l c o m ...
Страница 111: ...w w w d e l l c o m s u p p o r t d e l l c o m Dell システム ラック取り付けガイド ...
Страница 145: ...w w w d e l l c o m s u p p o r t d e l l c o m Sistemas Dell Guía de instalación del estante ...
Страница 180: ...5 32 Guía de instalación de estante w w w d e l l c o m s u p p o r t d e l l c o m ...
Страница 183: ...7W226am0 fm Page 1 Wednesday October 16 2002 3 25 PM ...