Chapter 5.
Servicing the Rack Cabinet
5-17
5.5.
Installing a PDU
Each PDU is delivered with mounting brackets for vertical and/or horizontal
installation in the cabinet.
Note
Vertical Installation
Up to six PDUs can be installed vertically in the cabinet flange space (3
right and 3 left).
Important
Before choosing a location for a PDU, check power cable
length from the servers and devices you want to connect to
the PDU.
Before proceeding to install the PDU, check that the circuit
breaker switch is OFF.
Required Tools
•
Hex wrench
•
PDU fixtures
Procedure: Horizontal Installation
1. Select the required location in the cabinet.
2. Install 2 cage nuts (A) over the required rack fixture holes on each side of
the cabinet.
3. Align the PDU fixture holes with the rack fixture holes on the left and right
sides of the cabinet.
4. Insert the bolt and washer assemblies in the top and bottom PDU fixture
holes (B) and tighten with the hex wrench.
Содержание M3S2G8
Страница 4: ......
Страница 20: ......
Страница 46: ...4 14 Installation and Service Guide 4 Stick some wire saddles on the inside of the door Rear view ...
Страница 48: ...4 16 Installation and Service Guide 4 Install the door central part on the outside of the door Front view ...
Страница 60: ...4 28 Installation and Service Guide 4 Install the door central part on the outside of the door Front view ...
Страница 67: ...Chapter 4 Servicing the Doors 4 35 4 Stick some wire saddles on the inside of the door Rear view ...
Страница 69: ...Chapter 4 Servicing the Doors 4 37 4 Install the door central part on the outside of the door Front view ...
Страница 80: ...5 4 Installation and Service Guide 5 Proceed in the same way from the rear of the cabinet ...
Страница 84: ...5 8 Installation and Service Guide 5 Proceed in the same way from the rear of the cabinet ...
Страница 96: ......
Страница 100: ......
Страница 106: ......