Table 42 Input power requirements - three-phase, North American, International, Australian
Specification
North American 4-wire
connection
(3 L & 1 G)
International 5-wire
connection
(3 L & 1 N & 1 G)
200–240 VAC ± 10% L- L
nom
220–240 VAC ± 10% L- N
nom
Frequency
50–60 Hz
50–60 Hz
Circuit breakers
50 A
32 A
Power zones
Two
Two
Minimum power requirements
at customer site
l
Two 50 A, three-phase
drops per bay.
l
PDU A and PDU B require
one separate three-phase
Delta 50 A drops for
each.
Two 32 A, three-phase drops
per bay.
a. L = line or phase, N = neutral, G = ground
b. An imbalance of AC input currents may exist on the three-phase power source feeding the
array, depending on the configuration. The customer's electrician must be alerted to this
possible condition to balance the phase-by-phase loading conditions within the customer's
data center.
Best Practices for AC Power Connections
AC power specifications
131
Содержание EMC VMAX 250F
Страница 6: ...CONTENTS 6 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 10: ...TABLES 10 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 18: ...Pre planning tasks 18 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 22: ...Delivery and transportation 22 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 34: ...Specifications 34 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 42: ...Physical weight and space 42 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 110: ...Optional kits 110 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...