background image

Dell EMC Data Domain DS60 Expansion
Shelf

Hardware Guide

302-002-100
REV. 05

Содержание Data Domain DS60

Страница 1: ...Dell EMC Data Domain DS60 Expansion Shelf Hardware Guide 302 002 100 REV 05 ...

Страница 2: ... IN THIS PUBLICATION AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE USE COPYING AND DISTRIBUTION OF ANY DELL SOFTWARE DESCRIBED IN THIS PUBLICATION REQUIRES AN APPLICABLE SOFTWARE LICENSE Dell EMC and other trademarks are trademarks of Dell Inc or its subsidiaries Other trademarks may be the property of their respective owners Published in the ...

Страница 3: ...0 cabling 49 Connecting power 57 Attach the power supplies 58 Single phase power connections for 40U P current racks 58 3 phase power connections for 40U P current racks 65 Data Domain Specific Installation 81 DD4200 DD4500 and DD7200 systems 82 DD6300 DD6800 and DD9300 systems 83 DD9500 and DD9800 systems 84 I O module slot assignments 84 Post Installation Tasks 87 Power on sequence 88 Verify the...

Страница 4: ...Hardware specifications 100 CONTENTS 4 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 5: ...ta Domain Operating System release being used in your environment l DD OS Release Notes Version l DD OS Initial Configuration Guide l DD OS Administration Guide l DD OS Command Reference Guide l The Data Domain system installation and setup guides for each of the supported platforms for example DD4200 and DD9500 l For Data Domain Systems that have ES20 shelves installed Data Domain ES20 Expansion ...

Страница 6: ...m output such as an error message or script l Pathnames filenames prompts and syntax l Commands and options Monospace italic Use for variables Monospace bold Use for user input Square brackets enclose optional values Vertical bar indicates alternate selections the bar means or Braces enclose content that the user must specify such as x or y or z Ellipses indicate nonessential information omitted f...

Страница 7: ...6 302 002 100 Rev 4 6 0 New topics and cabling diagrams as they relate to supporting DD6300 DD6800 and DD9300 andDD9800 systems 03 April 2016 302 002 100 Rev 3 5 7 1 Updates to the DD4200 and DD7200 supported configurations 02 March 2016 302 002 100 Rev 2 5 7 1 Minor updates as they relate to the High Availability HA system 01 October 2015 302 002 100 Rev 1 5 7 Initial publication Revision history...

Страница 8: ...Revision history 8 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 9: ...m and mixing shelves for different systems refer to the information in Requirements for combining DS60 and ES30 shelves on page 26 for shelf configuration restrictions Note l Data Domain systems that support the DS60 shelves must be running DD OS 5 7 and later l For instructions on replacing one of the field replaceable components see the DS60 Installation and FRU Replacement Guide on the Online S...

Страница 10: ...irflow If the equipment is mounted in an enclosed as opposed to a four post open rack the front and rear doors should have 65 minimum open area for airflow Whether in an open or enclosed rack use filler panels to prevent hot air re circulation The rack design and installation should take into consideration the maximum ambient operating temperature of the equipment which is 35 C Power grounding The...

Страница 11: ...appropriate licenses Additional licensing information is available in the Data Domain Operating System Administration Guide and the Data Domain Operating System Command Reference Guide DS60 expansion shelf This section describes the shelf front panel the status lights visible from the front the interior layout of the disks the back panel and the status lights visible from the rear of the chassis F...

Страница 12: ...60 Expansion Shelf Installation and FRU Replacement Guide Disk enclosure interior The disks are visible when the DS60 is pulled out of the rack and the top cover is removed from the chassis There are also three fans in the front of the disk enclosure and each fan has a fault LED Each disk in the enclosure has two LEDs The active LED glows blue when the disk is functional The disk fault LED glows a...

Страница 13: ... empty or has a filler module Also off when the disk is powered down by command for example the result of a temperature fault l Fast blinking when the SAS drive is powered up but not spinning this is a normal part of the spin up sequence occurring during the spin up delays of a slot l On when the drive has power but is not handing any I O activity the ready state DS60 Shelf Installation Overview D...

Страница 14: ...indication to replace the drive Fan fault 1 per fan module Amber On when the fan module is faulty or as an indication to replace the fan The DD OS software manages the drives in packs groups of 15 A top down view of the chassis shows that the disks are arranged in four packs groups of 15 drives The packs are color coded pack 1 purple pack 2 is yellow pack 3 is green and pack 4 is pink A pack must ...

Страница 15: ...5 6 8 9 11 C 0 2 3 5 6 8 9 11 B 0 2 3 5 6 8 9 11 A 0 2 3 5 6 8 9 11 Although the disk numbers are physically 0 to 59 the disks are reported logically by system software commands in two ways l A range from 1 to 60 usually reported with the enclosure number e g 3 37 l The position matrix A E 1 12 For part replacement information refer to the DS60 Expansion Shelf Installation and FRU Replacement Guid...

Страница 16: ...ller power 1 per controller Green On when the Controller is powered on Controller fault 1 per controller Amber On when either the Controller or a SAS connection is faulty On during power on self test Link active 4 per controller Blue On when the host connection is active Power supply input voltage 1 per power supply Green Input power green when it is working Power supply fault 1 per power supply A...

Страница 17: ...pics l Expansion shelf cables 18 l Safety requirements 19 l Racking and cabling 20 l Rail kit 20 l Shelf cabling rules and guidelines 21 l Installing or adding DS60 shelves 24 l Requirements for combining DS60 and ES30 shelves 26 l Connecting power 57 Installing the Shelves 17 ...

Страница 18: ... SAS I O modules such as DD4200 DD4500 DD6300 DD6800 DD7200 DD9300 DD9500 and DD9800 systems The DS60 connector is referred as the HD mini SAS connector and is same as the I O module connectors These cables are available in 3M 4M and 5M lengths Use the appropriate length for the connection you are making Refer to the specific Installation and Configuration Guide of the shelves for the recommended ...

Страница 19: ...t ensure a low center of gravity l Data Domain supplied racks have an interlock that prevents more than one DS60 from being pulled out of the rack at one time This is not true for customer supplied racks Do not pull out more than one DS60 at one time otherwise there is a much greater risk of the rack tipping The following safety requirements must be considered when the unit is mounted in a rack l ...

Страница 20: ...ntroller to any shelf in the same rack Install filler panels in unused rack openings There are figures showing the various configurations through the remainder of this document These are guidelines Other sections define the rules for different systems All rules must be followed but using a recommended configuration may depend on other restrictions in a specific installation After your hardware is ...

Страница 21: ...6300 DD6800 and DD9300 and DD9500 or DD9800 systems to migrate the data using the shelf migration software feature in DD OS 5 7 or later releases l ES30 SATA shelves must be on their own chain l If ES30 SAS shelves are on the same chain as a DS60 the maximum number of shelves on that chain is 5 l DD OS 5 7 1 does not support ERSO on DD9500 HA systems l DD OS 5 7 1 does not support HA with SATA dri...

Страница 22: ...or DD Cloud Tier DD7200 128 2x4 SAS 45 2 4 288 360 DD7200 256 2x4 SAS 45 60 2 4 432 540 DD7200 ER 2 256 4x4 SAS 45 60 2 8 864 1080 DD9300 5 6 13 19214 2x4 SAS 45 60 3 4 384 480 DD9300 w Expanded Capacity 5 6 12 384 2x4 SAS 45 60 3 4 720 900 DD9300 w Expanded Capacity and w HA 5 6 384 2x4 SAS 45 60 3 4 720 900 DD9300 w Expanded Capacity and w ER 5 6 10 384 2x4 SAS 45 60 3 4 1440 1800 DD9300 w Expan...

Страница 23: ...HA 5 6 7 768 4x4 SAS 45 60 5 8 1008 240 for DD Cloud Tier 1260 300 for DD Cloud Tier Note An entry of 45 corresponds to DS60 3 models and an entry of 60 corresponds to DS60 4 models 1 This column only counts drives that have user data in the shelves For example a DS604 240 has 192TB 2 With Extended Retention software 3 DD OS 5 7 1 does not support ERSO on DD9500 HA systems 4 DD OS 5 7 1 does not s...

Страница 24: ...lowest in the rack DS60 Port 2 on that controller is connected to Port 0 of the next DS60 in the set A port on a different SAS IO Module is connected to port 0 of controller B of the last usually highest DS60 in the set In the unlikely event that any single shelf becomes completely disconnected from power or SAS cables the Data Domain controller still has a connection path to all the remaining she...

Страница 25: ...f to an existing set remove the SAS I O cable and re connect it to the current top bottom shelf The SAS I O cables are always connected to the top and bottom shelves in the set Add shelves in the installation order for your controller l For redundancy always cable Shelf Controller A to Shelf Controller A and Shelf Controller B to Shelf Controller B to create independent duplicate paths l Unused co...

Страница 26: ...ata using the shelf migration software feature in DD OS 5 7 or later releases Some of the DS60 configurations described in the following sections also include ES30 shelves for DD Cloud Tier metadata or FS15 shelves for HA Note For HA pairs that have one or more ES30 FS15 shelves the primary and standby nodes use different cables to connect to ES30 FS15 shelves The primary node uses ES30 FS15 HOST ...

Страница 27: ...set Note For redundancy a shelf set is connected to two separate SAS I O modules on the Data Domain controller and all of the shelves within a set are connected to each other via dual paths DD4200 DD4500 and DD7200 cabling There are a few rules that must be followed when adding a mixture of DS60 and other shelf types to your system CAUTION If a system does not follow all these rules it is not a le...

Страница 28: ...an contain a maximum of two DS60 shelves and if required because of other restrictions add ES30 SAS shelves up to a maximum of five shelves in that set Note The configuration rules apply also to Extended Retention systems The following figures show cabling for base systems and systems with the Extended Retention software Note It is recommended that the DS60 shelf with the greater number of drives ...

Страница 29: ...Figure 7 Recommended cabling for DD4200 3TB drives Note One DS60 shelf can have 60 drives and the second DS60 shelf can have 15 drives Installing the Shelves DD4200 DD4500 and DD7200 cabling 29 ...

Страница 30: ...e Note With four shelves two DS60 shelves can have 60 drives each and the other DS60 shelves can only have 15 drives each It is also possible to configure two full DS60 shelves and one DS60 shelf with 30 drives Installing the Shelves 30 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 31: ...Figure 9 Recommended cabling for DD4500 3TB drives Installing the Shelves DD4200 DD4500 and DD7200 cabling 31 ...

Страница 32: ...Figure 10 Recommended cabling for DD4500 3TB drives with Extended Retention software Installing the Shelves 32 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 33: ...Figure 11 Recommended cabling for DD4500 with DD Cloud Tier Installing the Shelves DD4200 DD4500 and DD7200 cabling 33 ...

Страница 34: ...Figure 12 Recommended cabling for DD4500 4TB drives Note DS60 shelf 2 will only have 30 drives Installing the Shelves 34 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 35: ...Figure 13 Recommended cabling for DD4500 4TB drives with Extended Retention software Note All three of the DS60 shelves will be full Installing the Shelves DD4200 DD4500 and DD7200 cabling 35 ...

Страница 36: ...Figure 14 Recommended cabling for DD7200 3TB drives Installing the Shelves 36 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 37: ...Figure 15 Recommended cabling for DD7200 4TB drives Note Two DS60 shelves can have 60 drives and the third DS60 shelf can only have 15 drives Installing the Shelves DD4200 DD4500 and DD7200 cabling 37 ...

Страница 38: ...Figure 16 Recommended cabling for DD7200 3TB drives with Extended Retention software Installing the Shelves 38 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 39: ...Figure 17 Recommended cabling for DD7200 with DD Cloud Tier Installing the Shelves DD4200 DD4500 and DD7200 cabling 39 ...

Страница 40: ...d cabling for DD7200 4TB drives with Extended Retention software Note Four DS60 shelves have 60 drives each and two DS60 shelves have 15 drives each Installing the Shelves 40 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 41: ...SSD cache DD6800 w Extended Retention ER 576 TB 2 DD6800 w DD Cloud Tier 384 TB 96 TB for DD Cloud Tier 2 plus 2 ES30s for DD Cloud Tier DD6800 w HA and DD Cloud Tier 384 TB 96 TB for DD Cloud Tier 2 plus 1 FS15 for SSD cache and 2 ES30s for DD Cloud Tier DD9300 384 TB 3 DD9300 w HA 720 TB 3 plus 1 FS15 for SSD cache DD9300 w ER 1440 TB 3 DD9300 w DD Cloud Tier 912 TB 192 TB for DD Cloud Tier 3 pl...

Страница 42: ... DS60 Note DD6300 only has one SAS SLIC and all DS60 connections are made to that single SAS SLIC The cabling diagrams in this section show the maximum configurations for the DD6300 DD6800 and DD9300 systems Not all systems will have all the disk shelves shown in the diagrams Installing the Shelves 42 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 43: ...Figure 19 DD6300 Installing the Shelves DD6300 DD6800 and DD9300 cabling 43 ...

Страница 44: ...Note DD6300 only has one SAS SLIC and all DS60 connections are made to that single SAS SLIC Figure 20 DD6800 and DD9300 Installing the Shelves 44 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 45: ...Figure 21 DD6800 and DD9300 with HA Installing the Shelves DD6300 DD6800 and DD9300 cabling 45 ...

Страница 46: ...Figure 22 DD6800 with DD Cloud Tier Installing the Shelves 46 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 47: ...Figure 23 DD6800 with HA and DD Cloud Tier Installing the Shelves DD6300 DD6800 and DD9300 cabling 47 ...

Страница 48: ...Figure 24 DD9300 with DD Cloud Tier or HA and DD Cloud Tier Installing the Shelves 48 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 49: ... There are a few rules that must be followed when adding a mixture of DS60 and ES30 SAS shelves to your system CAUTION If a system installation does not follow all these rules it is not a legitimate configuration Installing the Shelves DD9500 and DD9800 cabling 49 ...

Страница 50: ...D cache 14 plus 1 FS15 for SSD cache DD9800 High Availability HA 1008 TB usable 2 plus 1 FS15 for SSD cache 7 plus 1 FS15 for SSD cache DD9800 DD Cloud Tier 1008 TB usable 2x in the cloud 3 plus 1 FS15 for SSD cache and 5 ES30s or 1 DS60 and 1 ES30 for DD Cloud Tier 8 plus 1 FS15 for SSD cache and 5 ES30s or 1 DS60 and 1 ES30 for DD Cloud Tier The DD9500 base non Extended Retention and HA systems ...

Страница 51: ...nt A set can contain a maximum of four DS60s and if required because of other restrictions add ES30 SAS shelves up to a maximum of five total shelves in that set This process also applies to Extended Retention systems Note The racks are filled from the bottom to the top The cabling diagrams in this section show the maximum configurations for the DD9500 and DD9800 systems Not all systems will have ...

Страница 52: ...Figure 26 Cabling for base DD9500 and DD9800 systems Installing the Shelves 52 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 53: ...Figure 27 Cabling for HA DD9500 and DD9800systems Installing the Shelves DD9500 and DD9800 cabling 53 ...

Страница 54: ...Figure 28 Cabling for DD9500 and DD9800 systems with DD Cloud Tier Installing the Shelves 54 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 55: ...Figure 29 Cabling for HA DD9500 and DD9800 systems with DD Cloud Tier Installing the Shelves DD9500 and DD9800 cabling 55 ...

Страница 56: ...Figure 30 Cabling for DD9500 and DD9800 systems with ERSO Installing the Shelves 56 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 57: ...the rack are required See the Power Calculator to determine total system power requirements https powercalculator emc com PC3 l Do not exceed the current capacity of the power distribution unit by adding more products than it can support l For safety of personnel and to insure proper functioning of systems it is recommended that each AC circuit of the power distribution unit have a double pole AC ...

Страница 58: ...uidelines on page 21 3 Ensure the rack is grounded before connecting AC power from the main circuit 4 Attach the power supplies on the rear panel of the Data Domain controller to separate PDUs for redundant power distribution one on each side of the rack The DS60 powers on immediately after you attach one of the power supplies on the rear panel of the shelf to a PDU with power Single phase power c...

Страница 59: ...Figure 32 Recommended single phase power connections for the DD4200 DD4500 and DD7200 systems Installing the Shelves Single phase power connections for 40U P current racks 59 ...

Страница 60: ...Figure 33 Recommended single phase power connections for the DD9300 Installing the Shelves 60 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 61: ...Figure 34 Recommended single phase power connections for DD9300 with HA Installing the Shelves Single phase power connections for 40U P current racks 61 ...

Страница 62: ...Figure 35 Recommended single phase power connections for DD9800 Installing the Shelves 62 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 63: ...se cabling for DD9800 with HA Note Single phase PDU with two DD9500 units four DS60 shelves and one FS15 shelf requires two power cords on each PDU pair Installing the Shelves Single phase power connections for 40U P current racks 63 ...

Страница 64: ...Figure 37 Recommended single phase power connections for the DS60 full racked Installing the Shelves 64 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 65: ...ed for several Data Domain systems In those situations it is desirable to balance the current draw across all 3 phases The recommended 3 phase power cabling attempts to do that but an optimal configuration is dependent on the specific installation The following figures show recommended 3 phase power connections for several Data Domain systems Note The next few diagrams show recommended 3 phase del...

Страница 66: ...Figure 38 Recommended 3 phase delta power connections for the DS60 expansion shelves full racked Installing the Shelves 66 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 67: ...Figure 39 Recommended 3 phase delta power connections for DD4200 DD4500 and DD7200 systems Installing the Shelves 3 phase power connections for 40U P current racks 67 ...

Страница 68: ...Figure 40 Recommended 3 phase delta power connections for DD9300 Installing the Shelves 68 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 69: ...Figure 41 Recommended 3 phase delta power connections for DD9300 with HA Installing the Shelves 3 phase power connections for 40U P current racks 69 ...

Страница 70: ...Figure 42 Recommended 3 phase delta power connections for DD9500 system Installing the Shelves 70 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 71: ...Figure 43 Recommended 3 phase delta power connections for DD9800 Installing the Shelves 3 phase power connections for 40U P current racks 71 ...

Страница 72: ... Recommended 3 phase delta power connections for DD9800 with HA Note The next few diagrams show recommended 3 phase wye power connections Installing the Shelves 72 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 73: ...Figure 45 Recommended 3 phase wye power connections for the DS60 expansion shelves full racked Installing the Shelves 3 phase power connections for 40U P current racks 73 ...

Страница 74: ...Figure 46 Recommended 3 phase wye power connections for DD4200 DD4500 and DD7200 systems Installing the Shelves 74 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 75: ...Figure 47 Recommended 3 phase wye power connections for DD9300 Installing the Shelves 3 phase power connections for 40U P current racks 75 ...

Страница 76: ...Figure 48 Recommended 3 phase wye power connections for DD9300 with HA Installing the Shelves 76 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 77: ...Figure 49 Recommended 3 phase wye power connections for DD9500 system Installing the Shelves 3 phase power connections for 40U P current racks 77 ...

Страница 78: ...Figure 50 Recommended 3 phase wye power connections for DD9800 Installing the Shelves 78 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 79: ...Figure 51 Recommended 3 phase wye power connections for DD9800 with HA Installing the Shelves 3 phase power connections for 40U P current racks 79 ...

Страница 80: ...Installing the Shelves 80 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 81: ...each Data Domain system that supports the DS60 shelves See the appropriate description for your Data Domain system This chapter covers the following major topics l DD4200 DD4500 and DD7200 systems 82 l DD6300 DD6800 and DD9300 systems 83 l DD9500 and DD9800 systems 84 Data Domain Specific Installation 81 ...

Страница 82: ...ontain 9 0 8 available I O module slots Depending on the system there can be up to 6 Ethernet modules 4 Fibre Channel modules or 4 SAS modules in a system For I O modules containing multiple ports the bottom port is numbered as zero 0 with numbers increasing going upward Figure 52 Rear view systems without Extended Retention software option or DD Cloud Tier Note Slots 7 and 8 are used for SAS I O ...

Страница 83: ...pose embedded 1GBE host interface port DD6300 DD6800 and DD9300 have eight SLIC slots 0 7 and are 8 lane PCIe Gen3 with an assigned specific functionality The non optional SAS NVRAM and 10GBaseT SLICs are allocated to fixed slots The optional Host Interface SLICs are used for front end networking and fibre channel connections Figure 54 Rear view and SLIC slot numbering 1 Slot 0 2 Slot 1 3 Slot 2 4...

Страница 84: ...system the top section contains the 4 power supply units In the middle of the section on the left is serial number tag location To the right of the serial number tag location is the management module The lower section contains the NVRAM and the I O modules numbered 0 through 11 from left to right I O module slot assignments The following figure shows the location of the NVRAM and I O modules Figur...

Страница 85: ...Ethernet or empty Fibre Channel FC Ethernet or empty Fibre Channel FC Ethernet or empty 2 SAS SAS SAS SAS 3 SAS SAS SAS SAS 4 FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty 5 FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty 6 SAS SAS SAS SAS 7 FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty FC Ethernet or empty ...

Страница 86: ...dule slot assignments continued Slot Base configuratio n HA ER or DD Cloud Tier DD Cloud Tier and HA standby nodes in the HA pair nodes in the HA pair Data Domain Specific Installation 86 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 87: ...follow the instructions in this chapter to complete the setup This chapter covers these major topics l Power on sequence 88 l Verifying shelf installation 89 l Understanding the DS60 disk mappings 91 l Add shelf capacity licenses 92 l Add enclosure disks to the volume 95 Post Installation Tasks 87 ...

Страница 88: ...ly Fault LED is steady amber the power supply is faulty or is not receiving AC line voltage If it is flashing either a multiple blower or ambient over temperature condition has shut off DC power to the system l If the Controller Fault LED is amber either the controller or SAS connection is faulty a If there are amber LEDs reseat or replace the power cable and check the LEDs again b Reseat the SAS ...

Страница 89: ... is lost l To re enable a shelf reconnect the shelf or transfer the disks from the shelf to another empty shelf chassis and connect l If the data on a shelf is not available to the file system volume the volume cannot be recovered l Unless the same disks are available to the file system the DD OS must be re installed as directed by your contracted service provider or Online Support site http suppo...

Страница 90: ... U U U B 13 24 U U U U U U U U U U U U A 1 12 U U U U U U U U U U U U Legend State Count In Use Disks 3 U Unknown Disks 135 Total 138 disks Note Enclosure 1 is a Data Domain head unit enclosure 2 is an ES30 shelf and enclosure 3 is a DS60 shelf All disks of the newly installed shelf are in U state 3 Verify that the Data Domain system recognizes each attached enclosure shelf by entering the enclosu...

Страница 91: ... E 2 B H 2 B E Encl WWN Serial 2 N A JWXCD143700040 3 N A JWXCD143600036 4 N A APM00111103491 5 N A APM00133421015 6 N A APM00111103544 Error Message No error detected ES20 rear view CONTROLLER B CONTROLLER A OP PANEL E H H E ES30 rear view CONTROLLER B E H CONTROLLER A H E Understanding the DS60 disk mappings The 60 disks contained in a DS60 shelf are divided into four disk packs of 15 disks each...

Страница 92: ...Note DD6300 DD6800 and DD9300 and DD9800 systems can only be licensed through the Electronic Licensing and Management System ELMS Refer to the applicable Data Domain Operating System Release Notes for the most up to date information on product features software updates software compatibility guides and information about Data Domain products licensing and service An Expanded Storage license is requ...

Страница 93: ... Need DS60 CAPACITY ACTIVE license for at least 36TB 32 7TiB capacity Updating system information is done Successfully added 3 1 3 2 done And for a Data Domain system with Extended Retention storage add tier archive enclosure enclosure id Note In a single node Data Domain system storage devices are added to the active tier by default In a DD Extended Retention system you must specify the active or...

Страница 94: ...E feature for 32 7 TiB capacity DS60 7 Enter the license show command to verify the licenses for the storage shelf license show Feature CAPACITY ACTIVE License Key Model Capacity 1 xxxx xxxx xxxx xxxx xxxx xxxx xx DS60 32 7 TiB 2 xxxx xxxx xxxx xxxx xxxx xxxx xx DS60 32 7 TiB 3 xxxx xxxx xxxx xxxx xxxx xxxx xx DS60 32 7 TiB 4 xxxx xxxx xxxx xxxx xxxx xxxx xx DS60 32 7 TiB Licensed Active Tier Capa...

Страница 95: ...v v v v v v v v v 4 Pack 1 Pack 2 Pack 3 Pack 4 E 49 60 U U U U U U U U U U U U D 37 48 U U U U U U U U U U U U C 25 36 U U U U U U U U U U U U B 13 24 U U U U U U U U U U U U A 1 12 U U U U U U U U U U U U Legend State Count In Use Disks 3 v Available Disks 60 U Unknown Disks 75 Total 138 disks Note All newly added disks are in v state 10 Repeat the above steps to add licenses to other shelves Ad...

Страница 96: ...B pack 1 3 37 3 39 3 49 3 51 unknown 3 4 3 6 3 16 3 18 3 28 3 30 15 2 7 TiB DS60 32 7 TiB pack 2 3 40 3 42 3 52 3 54 unknown 3 7 3 9 3 19 3 21 3 31 3 33 15 2 7 TiB DS60 32 7 TiB pack 3 3 43 3 45 3 55 3 57 unknown 3 10 3 12 3 22 3 24 3 34 3 36 15 2 7 TiB DS60 32 7 TiB pack 4 3 46 3 48 3 58 3 60 Shelf Capacity License License Model Total Used Remaining CAPACITY ACTIVE ES30 109 1 TiB 87 3 TiB 21 8 Ti...

Страница 97: ... v v v v v A 1 12 v v v v v v v v v v v v 4 Pack 1 Pack 2 Pack 3 Pack 4 E 49 60 U U U U U U U U U U U U D 37 48 U U U U U U U U U U U U C 25 36 U U U U U U U U U U U U B 13 24 U U U U U U U U U U U U A 1 12 U U U U U U U U U U U U Legend State Count In Use Disks 3 v Available Disks 60 U Unknown Disks 75 Total 138 disks Post Installation Tasks Add enclosure disks to the volume 97 ...

Страница 98: ...Post Installation Tasks 98 Data Domain DS60 Expansion Shelf Hardware Guide ...

Страница 99: ...APPENDIX A Hardware Specifications This appendix contains the following topic l Hardware specifications 100 Hardware Specifications 99 ...

Страница 100: ...th chassis only 34 5 in 87 63 cm l Maximum depth fully configured 36 4 in 92 46 cm Shelf weight l Without FRUs installed 55 0 lb 24 7 kg l With FRUs installed 225 0 lb 102 kg Operating temperature l Ambient temperature 41o F to 104o F 5o C to 40o C l Temperature gradient 18o F hr 10o C hr l Relative humidity extremes 20 to 80 noncondensing Recommended operating relative humidity 40 to 55 nonconden...

Отзывы: