Air Curtain Refrigerator Service and Installation Manual
For customer service, call (800) 733-8829 or (800) 733-8948, Fax (989) 773-3210, www.delfield.com
8
To change the other parameters (Second Level) follow these steps:
Step 1
and
Press and hold SET and DOWN for 10 seconds. The display will show dSPL
Step 2
Press SET to change the parameter
Step 3
or
Press UP or DOWN to change the options, time or temperature for the
current parameter
Step 4
Press SET to accept the new value
Step 5
Press DOWN to go to the next parameter. Then go back to Step 2. After the
last parameter is displayed ( ALHi), the display will go back to the normal
operating condition
Note : to scroll down the parameters without changing them, press the DOWN button.
List of Parameters
Here is a list of the parameters that can be changed in the Second Level of programming, as well as their
options and ranges.
Parameter
Display
Symbol
Description
Range/Options
Delfield
Settings
Display Status
dSPL
Information shown on the display
during operating conditions
tDAy – time -of-day
rSP° - Zone
temperature
(refrigerated space)
CyCL – cycle between
time and zone
temperature
Epr° - evaporator coil
temperature
Clock Format
CLHr
Format of the time (12 or 24
hours mode)
12Hr – AM/PM format
24Hr – 24 hour format
12Hr
Temperature
Format
°dSP
Temperature degrees
°F – degrees
Fahrenheit
°C – degrees Celsius
° F
Defrost Type
dFtP
Type of defrost used in the
application
ELEC – electric heater
defrost/off cycle
HgAS – hot gas
ELEC
Fan Status During
Defrost
EFAN
Enable or not the evaporator fan
during defrost
no – fan is turned off
during defrost
yES – fan remains on
during defrost
CFAN
Enable or not the condenser fan
during defrost
no – fan is turned off
during defrost
yES – fan remains on
during defrost
no
rSP°
yES
ERC2 Control Instructions,
continued