Air Curtain Refrigerator Service and Installation Manual
For customer service, call (800) 733-8829 or (800) 733-8948, Fax (989) 773-3210, www.delfield.com
10
High
Temperature
Alarm
ALHi
High temperature setpoint that
will make the alarm do off and
the error message appear on the
display
Range: from -40 to
60°F or -40 to 23°C
60°F
Important note: To change from degrees C to F or vice-versa, the user must reprogram all the
parameters that are related to the temperature. The unit does not convert parameters automatically
from degrees F to C or vice-versa.
Example 1 – To adjust the time -of -day
Press and hold SET for 5 seconds
Press SET again
Press Up or DOWN until the correct time appears on the display
Press SET to accept the new time
Press DOWN twice to exit the programming mode
Example 2 – To set one defrost a day, at 11:59 PM
Press and hold SET and DOWN for 10 seconds
Press DOWN five times to get to the Defrost Interval ( dFin)
Press SET to change the parameter
Press DOWN until tdAy appears on the display
Press SET to accept the option
Press DOWN seven times to go to the Number of Defrosts ( noDF)
Press SET to change it
Press UP or DOWN until 1 appears on the display
Press SET to accept the change
Press DOWN to go to Defrost Start Time ( dEF1)
Press SET to change the time
Press UP or DOWN until the 11:59 PM appears on the display
Press SET
Press DOWN ten times to exit the programming level
ERC2 Control Instructions,
continued