![Deka Fahrenheit 2V NB Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/deka/fahrenheit-2v-nb/fahrenheit-2v-nb_installation-and-operation-manual_2465436012.webp)
12
TERMINAL ASSEMBLY
CONT.
4. Connect side terminal plate to side terminal plate connectors.
Side terminal bracket and side terminal connectors may have
to be adjusted to insure plate and connectors are flush. Use
1/4-20 x 1.25" hardware.
7. Install Side Terminal Shield to Side Terminal Plate using
¼-20 screws.
Tighten but do not torque hardware.
Complete Assembly
5. Connect side terminal plate to terminal plate bracket using
1/4-20 x 1.00" hardware. Bolts should be installed loosely
for future adjustments.
6. After all parts are installed and alignment is confirmed,
torque all bolts.
Consult “Hardware Torque Requirements”
(pg 5) for proper torque values.
8. Side Terminal Plate is designed to use up to 0.50" dia. bolt
and a maximum 1.75" centers and 1.188" min., 2 hole lug.
Plate is capable of handling 4 runs of cable.
Lug Positioning Options:
Maximum of four cable lugs can be installed per terminal plate.
Lug Hardware not included.
2600_Fahrenheit-2V-NB-mod_I&O.indd 12
2600_Fahrenheit-2V-NB-mod_I&O.indd 12
2/22/22 2:45 PM
2/22/22 2:45 PM