Changing the default settings:  

The SIM-2 can be reconfigured by means of four jumpers. (The original configuration is marked on 
its  label). The jumpers are placed on the PCB behind the rear cover, under the set point 
potentiometer. See below drawing for clarification. 
 
DIP#1 = STANDARD/CUSTOM 
DIP#2 = 500 uF/2000 uF 
DIP#3 = 0 to 1 

MΩ/0

 to 10 

MΩ

 

DIP#4 = ND/NE 
 

DIP#1

  can be  set to OFF (STANDARD)  and  the SIM-2 will load its settings from hard-coded 

memory area. If set to ON (CUSTOM), the SIM-2 will load its settings from a configurable memory 
area, used for custom settings, set up by DEIF when ordered. 

DIP#2

  can be set to either OFF (500  uF) or  ON (2000  uF). The chosen setting will determine the 

maximum leakage capacitance. Please note that this will also change the measuring time. 

DIP#3

 can be configured for OFF (measuring range 0 to 1 

MΩ), with 22

 

kΩ on the scale c

entre or 

set to ON (measuring range 0 to 10 

MΩ), with 220

 

kΩ on the s

cale centre. Please notice that a 

change in measuring range also involves a change of scale. 

DIP#4

  settings will determine the SIM-2 relay  output.  If set to OFF (ND), the  output will be 

configured as a normally de-energised contact. If set to ON (NE), the output will be configured as a 
normally energised contact.

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

QUICK GUIDE 

Insulation monitor, SIM-2 

 

Refer to www.deif.com for detailed information

 

 

Document no.: 4189330019A 

 

IMPORTANT - Use electrostatic discharge protection!  

Sufficient care must be taken to protect the PCB against static discharges during the configuration. Once 
the unit is installed and connected, these precautions are no longer necessary. 

 