![Deif MTR-3 Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/deif/mtr-3/mtr-3_installation-instructions-manual_2465309044.webp)
MTR-3
Installation Instructions
DEIF A/S
Page 44 of 51
Reserved
400154
153
Starting total current for PFt & Pat
400155
154
T16
2000 for 20 mA
Starting current for all powers
400156
155
T16
200 for 2 mA
Reserved
400157 400159 156
158
Temperature unit
400160
159
T1
0
°C
1
°F
Reserved
400161 400167 160
166
Starting voltage for SYNC.
400168
167
T1
5000 for 5 V (for R30015 = 500 V)
Reserved
400168 400169 168
169
Comm. average interval
400171
170
T1
0
1 period (0.02 s @50 Hz) default
1
2 periods (0.04 s @50 Hz)
2
4 periods (0.08 s @50 Hz)
3
8 periods (0.16 s @50 Hz)
4
16 periods (0.32 s @50 Hz)
5
32 periods (0.64 s @50 Hz)
6
64 periods (1.28 s @50 Hz) default
7
128 periods (2.56 s @50 Hz)
8
256 periods (5.12 s @50 Hz)
Reserved
400172 400201 171
200
COMMUNICATION
Res. for Port 1: Device Address (DNP3)
400201
200
Port 1: Device Address (Modbus)
400203
202
T1
Port 1: Baud Rate
400204
203
T1
0
Baud rate 1200
1
Baud rate 2400
2
Baud rate 4800
3
Baud rate 9600
4
Baud rate 19200
5
Baud rate 38400
6
Baud rate 57600
7
Baud rate 115200
Port 1: Stop Bit
400205
204
T1
0
1 Stop bit
1
2 Stop bits
Port 1: Parity
400206
205
T1
0
No parity
1
Odd parity
2
Even parity
Port 1: Data Bits
400207
206
T1
0
8 bits
1
7 bits
Reserved
400208 400400 207
399