Register table for the actual measurements (VERSION 1)
Parameter
PLC
Modbus Reading
Address
Address
Function
Type
Start
End
Start
End
DYNAMIC DEMAND VALUES
Time Into Period (minutes)
300502
300502
501
501
04
T1
I1
300503
300504
502
503
04
T5
I2
300505
300506
504
505
04
T5
I3
300507
300508
506
507
04
T5
Apparent Power Total (St)
300509
300510
508
509
04
T5
Active Power Total (Pt) -
(positive)
300511
300512
510
511
04
T6
Active Power Total (Pt) -
(negative)
300513
300514
512
513
04
T6
Reactive Power Total (Qt) - L
300515
300516
514
515
04
T6
Reactive Power Total (Qt) - C
300517
300518
516
517
04
T6
MAX DEMAND SINCE LAST RESET
I1
300519
300520
518
519
04
T5
I2
300525
300526
524
525
04
T5
I3
300531
300532
530
531
04
T5
Apparent Power Total (St)
300537
300538
536
537
04
T5
Active Power Total (Pt) -
(positive)
300543
300544
542
543
04
T6
Active Power Total (Pt) -
(negative)
300549
300550
548
549
04
T6
Reactive Power Total (Qt) - L
300555
300556
554
555
04
T6
Reactive Power Total (Qt) - C
300561
300562
560
561
04
T6