Mounting instructions 

To ensure correct mounting, and to obtain the intended functionality of your product, 
DEIF A/S recommends that you read these guidelines carefully before you mount the 
product. 
Use the correct tools for mounting, and do not exceed the recommended tightening 
torques. 
 

DEIF A/S warranty will be lost for products that are damaged because of 
incorrect tools used for mounting, or because of excessive tightening of the 
terminals and screws. 

 

Tools

 

 

Do not use electric screwdrivers 

 

Only use two fingers on the screwdriver 

 

Tightening torques 

For terminals: Max. 0.5 Nm 

 

For mounting screws: Max. 0.5 Nm 

 

 

Installation

 

Verification: 

Verify that the instrument configuration is according to application.

 

 
Aux. supply:

 Connect terminals to correct voltage. 

 

Measuring circuit:

 Connect PE to ground and P to a phase (if it is a 3-phased network –

connect to any of the phases). 
 

Warning: 

If a high-voltage “MEGGER” is used, 

the AAL-2 must be disconnected at 

terminal "P" before testing is carried out. Omitting this may result in 
damage to the AAL-2

 

Test

  

An instrument self-test can be carried out according to IEC 61557-8, as shown in 

Fig. 1

 

below. ¼ W resistance and switch ratings according to network voltages. 
 

 

 

 

3- or 4-wire networks 

2-wire networks 

 

Fig. 1 

 

Adjustment of the set point 

The requested warning set point is adjusted by means of the potentiometer on the upper 
left corner on the back of the instrument. 
If precise warning setting is wanted, connect a known resistor corresponding to the wanted 
setting between P and PE. Then adjust the potentiometer until the warning LED is 
activated. 
 

Typical setting: 

Typical warning set point: 22 k

 at 1 M range, or 220 k

 at 10 M range. 

Place the red marker pointer at the set point. 
 

 