Configuration of the warning relay function  

The relay can be reconfigured by means of two jumpers. (The original configuration is 
marked on the label). The jumpers are placed on the PCB behind the rear cover, under 
the set point potentiometer R213. 
 
The 

contact function

 can be configured to either a normally energised contact (NE) or 

a normally de-energised contact (ND). 
   

Warning delay 

It is possible to choose between 

No warning delay

 or 

4 s warning delay

 from the 

alarm occurs until the warning relay is activated.  
 
If the system has capacitance to ground, it is recommended to use the 4 s time delay in 
order to avoid “false“ warning at power-up, or when capacitive load is switched on. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Example of jumper settings: 

Warning delay = 0 s 
Warning relay = normally de-energised (ND) 
 

 

 

QUICK GUIDE

Insulation monitors, AAL-2 

 

Refer to www.deif.com for detailed information

 

Document no.: 4189320055B 