Configuration of the warning relay function
The relay can be reconfigured by means of two jumpers. (The original configuration is
marked on the label). The jumpers are placed on the PCB behind the rear cover, under
the set point potentiometer R213.
The
contact function
can be configured to either a normally energised contact (NE) or
a normally de-energised contact (ND).
Warning delay
It is possible to choose between
No warning delay
or
4 s warning delay
from the
alarm occurs until the warning relay is activated.
If the system has capacitance to ground, it is recommended to use the 4 s time delay in
order to avoid “false“ warning at power-up, or when capacitive load is switched on.
Example of jumper settings:
Warning delay = 0 s
Warning relay = normally de-energised (ND)
QUICK GUIDE
Insulation monitors, AAL-2
Refer to www.deif.com for detailed information
Document no.: 4189320055B