Inspections must be performed only by the operator of the system themselves.
Maintenance and repairs must be performed by qualified specialists only (see 1.8).
The time intervals listed for inspection and maintenance work as well as the specified work steps should be followed
by the operator in their own interest!
7.1.
Inspections
If defects/damage are observed on the
break tank system
during the inspection, please contact your contract partner/dealer.
7.1.1.
Aquaform AQF storage tank
Inspect the storage tank for leakproofness, cleanliness, damage and sediment residues. Clean
external dirt with a wet towel and standard dishwasher detergent.
Time interval: yearly
When cleaning, take care to ensure that liquids cannot get on electrical parts.
7.1.2.
Checking water connections
Check the drinking water and process water connection for damage, leakproofness and for porous or worn
spots. If necessary, replace hoses/pipes and seal. Time interval: half-
yearly
7.1.3. Mechanical float valve
Check the mechanical float valves for functioning. Open the process water consumer and wait until the fill level in the
break tank
system
has fallen so that the ball valve is open. Close the process water consumer again and wait until the ball valve closes again.
Time interval: half-
yearly
7.1.4. Functioning of immersion pressure pump
Check pressure accumulation, leakproofness, pumping and flowing noises as well as functioning. Open process water
consumers and thus start immersion pressure pump.
Time interval: half-yearly
7.1.5. Dry-run protection of the immersion pressure pump
Shut off drinking water feed and open process water consumers until storage tank is pumped empty. The integrated dry-run
protection switches the immersion pressure pump off automatically. Next, open the drinking water feed again and close the process
water consumers. The dry-run protection will automatically reset after 3 min.
Time interval: half-
yearly
7.2. Service
The
break tank system
must be disconnected from the mains network (main switch
OFF
position) during
maintenance and repair work. The
break tank system
is not available during the tasks.