Fig. 4
Earth clamp with adjustable handle
earth clamp with flexible
adjustable handle
!
5.2 Using the voltage detector in an installation
After performing a functional test, the green light
"0"
illuminates indicating that the device is
ready for testing. The voltage detector can only make contact with
PHEG1...
(earthed negative pole)
:
the earth clamp with black handle (page 5) at the earthed negative pole and the
red
test elec-
trode
or
at the positive pole ... or
PHEG1...
(earthed positive pole)
:
the earth clamp with black handle (page 5) at the earthed positive pole and with the
blue
test
electrode
or
at the negative pole... or
PHEG2...
the
blue
test electrode (page 5) at the negative pole and with the
red
test electrode at the
positive pole of the part of the system to be tested.
Note:
With voltage detectors type PHEG1... the earth clamps must always be connected
before the test electrodes. Disconnection in reverse order.