19
Add-on modules
Product code
Name
Product description
40200003
DEGA NS III Relay Modul
Internal 4-relay, 250 V/10 A
40200010
DEGA NS III RS485
Internal output RS485
40200011
DEGA NS III Buzzer
Internal buzzer on PCB, 4 VDC, 7 VDC, 30 mA, 88 dB
Attachments
1. Chart for setting the detector address
address
1
2
3
4
5
1
ON
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
5
ON
OFF
ON
OFF
OFF
6
OFF
ON
ON
OFF
OFF
7
ON
ON
ON
OFF
OFF
8
OFF
OFF
OFF
ON
OFF
9
ON
OFF
OFF
ON
OFF
10
OFF
ON
OFF
ON
OFF
11
ON
ON
OFF
ON
OFF
12
OFF
OFF
ON
ON
OFF
13
ON
OFF
ON
ON
OFF
14
OFF
ON
ON
ON
OFF
15
ON
ON
ON
ON
OFF
16
OFF
OFF
OFF
OFF
ON
2.
Conversion between volumetric concentration and lower explosion limit of methane
%DMV
– level of lower explosion limit concentration in %
%obj
– volume sample of gas
4,4
– lower explosive limit of methane (4.4 % by volume)
1
2
3
4
5
17
ON
OFF
OFF
OFF
ON
18
OFF
ON
OFF
OFF
ON
19
ON
ON
OFF
OFF
ON
20
OFF
OFF
ON
OFF
ON
21
ON
OFF
ON
OFF
ON
22
OFF
ON
ON
OFF
ON
23
ON
ON
ON
OFF
ON
24
OFF
OFF
OFF
ON
ON
25
ON
OFF
OFF
ON
ON
26
OFF
ON
OFF
ON
ON
27
ON
ON
OFF
ON
ON
28
OFF
OFF
ON
ON
ON
29
ON
OFF
ON
ON
ON
30
OFF
ON
ON
ON
ON
31
ON
ON
ON
ON
ON
32
OFF
OFF
OFF
OFF
ON
3. Table of error codes
code
cause
solution
1
Sensor is not present
(EEPROM is not
communicating)
Disconnect and reconnect
the sensor, then restart the
sensor by disconnecting
and reconnecting the
power
2
Unknows sensor type
Contact the manufacturer
3
Type 2 senesor type ID not
found in the table setting
LMP91000
Contact the manufacturer -
FW update required
4
CRC does not match the
sensor EEPROM
Sensor error - contact the
manufacturer
5
LMP91000 does not respond Sensor error - contact the
manufacturer
6
The set sensor ID does not
match with the connected
sensor
Checking the configuration
of the sensor required
7
Reserved
Reserved
8
EL sensor test error
Sensor error
9
Detector is in preheating
mode
Wait a few minutes, the
detector will automatically