9
Transmitter controls
Transmitters equipped with an LCD display can be controlled by the magnetic contact located on the sides of the display
Warning: calibration
required
Warning: Service is
required
Data display
Time display
Channel number
(adress)
Activated magnetic
control
Calibration icon
Communication with the
control panel in
progress
Measured value
Bar graph of the
measured value
Measured value
units
Alarm PEL (exceeding
long-term exposure
limit)
Alarm STEL
(exceeding short-
term exposure limit)
Reached alarm level
Alarm indication
- „BACK“ move backwards in the menu, reducing the value
- „FRONT“move forwards in the menu, increasing the value
- „ENTER“ confirm/enter the menu
Placing a magnet into the indent „
“ for 2s, activates the magnetic control, which is displayed by the icon „
“ on the LCD.
Reaching level 4 alarm with catalytic and semiconductor sensors causes a ratchet phenomenon, where even after recovery
from gas leak, the sensor is still in level 4 alarm and needs to be manually reset by pressing „
“.
Main menu structure:
Menu entry
|
History->-Information->-Settings->- Test->- Exit
|-----------------------<------------------------------|
Menu
Display
Description
History
Browsing the alarm history
Information
Information about transmitter settings