4
Gb
- type of protection according to EPL
Tamb
- operating temperature range
Dimensions without bushings:
150x170x65 mm (WxHxD)
Weight:
2,1 kg
Capacity of the internal memory of history: 44 days at 60s recording interval
Interval record storage memory:
60 s (adjustable range 1-255 s)
Dead band:
max 5% of range
Consumption/input at 24V (output RS485)
Warm-Up time
DEGA NSx-EL III LCD 90 mA/2,2 W
DEGA NSx-EL III LCD max. 180 s
DEGA NSx-CL III LCD 135 mA/3,3 W
DEGA NSx-CL III LCD max. 30 s
DEGA NSx-IL III LCD 115 mA/2,8 W
DEGA NSx-IL III LCD max. 15 s
DEGA NSx-SL III LCD 135 mA/3,3 W
DEGA NSx-SL III LCD max. 180 s
DEGA NSx-PL III LCD 154 mA/3,4 W
DEGA NSx-PL III LCD max. 30 s
Consumption/input at 24V (output 4-20mA)
Time to stabilize (>5day without power)
DEGA NSx-EL III LCD 110 mA/2,7 W
DEGA NSx-EL III LCD Up to several hours - based on sensor type
DEGA NSx-CL III LCD 155 mA/3,7 W
DEGA NSx-CL III LCD max. 1 h
DEGA NSx-IL III LCD 135 mA/3,3 W
DEGA NSx-IL III LCD max. 30 min
DEGA NSx-SL III LCD 155 mA/3,7 W
DEGA NSx-SL III LCD max. 5 h
DEGA NSx-PL III LCD 154 mA/3,4 W
DEGA NSx-PL III LCD max. 30 min
Response time (T90)
Sensor lifetime in a clean environment
DEGA NSx-EL III LCD max. 180 s - based on sensor type DEGA NSx-EL III LCD 2 years
DEGA NSx-CL III LCD max. 15 s
DEGA NSx-CL III LCD 2 years
DEGA NSx-IL III LCD max. 15 s
DEGA NSx-IL III LCD 5 years
DEGA NSx-SL III LCD max. 30 s
DEGA NSx-SL III LCD 2 years
DEGA NSx-PL III LCD max. 15 s
DEGA NSx-PL III LCD 1 year
Operational conditions
Ambient temperature:
-40°C to +85 °C
Relative humidity:
0-95 % RH
Air pressure:
86 - 108 kPa
Flow of ambient air:
max. 2 m/s - flow directly to the sensor in not allowed
Protection level with a cover:
IP 64, with a DEGA WATER CAP IP66 cover
Location:
BE3N2 - explosive atmoshpheres - zone 1 (2 G)
Terminology
The marking system for sensors DEGA NSx-yL III LCD:
Gas sensor DEGA NSx-yL III LCD
Series of detectors in potentially explosive atmospheres
Type of detected gas
Sensor type with linear output
Third generation product with new DEGA design
Versions with an LCD display
DEGA NSx-EL III LCD with an electrochemical sensor
They operate on the principle of change of electrical parameters on the electrodes stored in electrolyte, due to oxidation/reduction
reactions of the detected gas on it's surface. These sensors have good selectivity and the ability to detect very low concentrations of toxic
gases.
DEGA NSx-CL III LCD with a catalytic sensor (Pelistor)
They operate on the principle of catalytic combustion - gas concentration is measured based on the amount of heat released in a
controlled combustion reaction. The reaction is supported by a suitable temperature and the pressence of a catalyst. These sensors can be