INPUT WIRING & SPECIFICATIONS
CAUTION
Risk of electric shock.
Dangerous and lethal voltages may be present on the input termi-
nals. Please take appropriate precautions to ensure safety.
CAUTION
Risk of danger.
The sensor input can potentially float to dangerous and unexpected volt-
ages depending on what external circuit it is connected to. Appropriate considerations
must be given to the potential of the sensor input with respect to earth common.
8.1 - Current Input
Range
0–20mA, 4–20mA
Input impedance 1
50Ω
Maximum over-range
protected by PTC
to 24V DC
Accuracy
0.1% FSO max
Linearity & repeatability
0.1% FSO max
Channel separation
0.001% max
Ambient drift
0.003%/°C FSO typical
RF immunity
1% effect FSO typical
0/4–20mA DC is the most commonly used analog signal in industry, and is universally accepted.
As a current loop, it is unaffected by voltage drops in cables, and can be transmitted over long
distances without signal degradation.
Tx
2 Wire Loop Powered
Transmitter, 4–20mA
16 17 18
Tx
3 Wire Loop Powered
Transmitter, 4–20mA
+ Su
p
p
ly
+ Si
gnal
- Su
p
p
ly
16 17 18
Tx
4 Wire Loop Powered
Transmitter, 4–20mA
+ Su
p
p
ly
+ Si
gnal
- Si
gnal
- Su
p
p
ly
16 17 18
4–20mA