Installation planning
Requirements for the cable
• Maximum size for the installation cable is 4 mm
2
.
• If a new cable is to be installed, apply only cable dimensions suitable for the entire circuit,
including the fuse.
• Note the maximum current (A) for the entire circuit. Consider possible additional electrical
devices connected to the same fuse, for later current settings in the charging station.
Requirements for the installation site
• Do not install the charging station in a spot where the maximum operating temperature is
exceeded. See chapter
Technical specification
for maximum temperature.
• Ideally, the installation site should be covered.
• The installation site must not be in an area subject to flooding, close to water, or in areas
used to store objects, or containers containing liquids.
• The installation site must not be in explosive atmosphere areas.
• The installation site must offer sufficient air circulation.
• Make sure there is 55 mm of free space above the bracket so the charging unit can slide
easily on and there is space for the top cover.
55mm
Tools needed
• Installation tools for correct wiring, including stripping tool.
• Cross recessed screwdriver for wall bracket screws.
• Torx tool size Tx 15 with space for safety pin.