FRONT PANEL EDITOR PARAMETERS 
 

Section

 

Parameter As Shown On Display

 

Value 

Display 

Contrast 

0 % 

 

Backlight Level 

0 % 

 

Language 

English  

 

Current Date and Time 

Day:month:year, 
hour:minute:seconds 

Engine 

Oil Pressure Low Shutdown  
(W hen Enabled) 

0.00 bar, kPa, psi 

 

Oil Pressure Low Pre Alarm  
(W hen Enabled) 

0.00 bar, kPa, psi 

 

Coolant Temperature High Pre Alarm (When 
Enabled) 

0 ºC, ºF 

 

Coolant Temp High Controlled Shutdown 
(W hen Enabled) 

0 ºC, ºF               

 

Coolant Temperature High Shutdown (When 
Enabled) 

0 ºC, ºF               

 

Start Delay Off Load 

0 h 0 m 0 s 

 

Start Delay On Load 

0 h 0 m 0 s 

 

Start Delay Telemetry 

0 h 0 m 0 s 

 

Pre Heat Temperature (When Enabled) 

0 ºC, ºF               

 

Pre Heat Timer 

0 h 0 m 0 s 

 

Post Heat Temperature (When Enabled) 

0 ºC, ºF               

 

Post Heat Timer 

0 h 0 m 0 s 

 

Cranking 

0 m 0 s 

 

Crank Rest  

0 m 0 s  

 

Safety On Delay 

0 m 0 s  

 

Smoke Limiting 

0 m 0 s  

 

Smoke Limiting Off 

0 m 0 s 

 

Warming 

0 m 0 s 

 

Cool Down Time 

0 h 0 m 0 s 

 

Under Speed Shutdown 

Active / Inactive 

 

Under Speed Shutdown  
(W hen Enabled) 

0 rpm 

 

Under Speed Warning 

Active / Inactive 

 

Under Speed Warning (When Enabled) 

0 rpm 

 

Over Speed W arning 

Active / Inactive 

 

Over Speed W arning (When Enabled) 

0 rpm 

 

Over Speed Shutdown 

0 rpm 

 

Speed Overshoot Delay 

0 m 0 s 

 

Speed Overshoot 

0 % 

 

Fail To Stop Delay 

0 m 0 s 

 

Battery Under Voltage Warning 

Active / Inactive 

 

Battery Under Voltage Warning Delay (W hen 
Enabled) 

0 h 0 m 0 s 

 

Battery Under Voltage Warning 

0 V 

 

Battery Over Voltage Warning 

Active / Inactive 

 

Battery Over Voltage Warning Delay (W hen 
Enabled) 

0 h 0 m 0 s 

 

Battery Over Voltage Warning 

0 V 

 

Charge Alternator Failure Warning 

Active, Inactive 

 

Charge Alternator Warning Delay  
(W hen Enabled) 

0 h 0 m 0 s 

 

Charge Alternator Failure Warning 

0.0 V 

 

Charge Alternator Failure Shutdown  

Active / Inactive 

 

Charge Alternator Shutdown Delay  
(W hen Enabled) 

0 h 0 m 0 s 

 

Charge Alternator Failure Shutdown  
(W hen Enabled) 

0.0 V      

 

Priming Delay 

0 s 

 

Clutch Engage Speed 

0 rpm 

 

Clutch Disengage Speed 

0 rpm 

 

Idle Speed 

0 rpm 

 

Warming Speed 

0 rpm 

 

Cooldown Speed 

0 rpm 

 

Starting 

0 rpm 

 

Priming Speed 

0 rpm 

 

Min Speed 

0 rpm 

 

Default Speed  

0 rpm 

 

Max Speed 

0 rpm 

 

Reset Default Speed on Start-up 

Active / Inactive 

 

Cooling at Idle 

0 h 0 m 0 s 

FRONT PANEL EDITOR PARAMETERS (CONTINUED) 
 

Section 

Parameter As Shown On Display 

Value 

Engine 

Delayed Engine Start 

0 h 0 m 0 s 

(continued) 

Delayed Engine Stop 

0 h 0 m 0 s 

 

Engine Speed Transient Delay 

0.0 s 

 

Selectable Speed Transfer Time 

0 m 0.0 s 

Timers 

LCD Page Timer 

0 h 0 m 0 s 

 

Scroll Delay 

0 h 0 m 0 s 

 

Engine Pre Heat Timer (When Enabled) 

0 m 0 s 

 

Engine Cranking 

0 m 0 s 

 

Cranking Rest 

0 m 0 s 

 

Safety On Delay 

0 m 0 s 

 

Smoke Limiting 

0 m 0 s 

 

Smoke Limiting Off 

0 m 0 s 

 

Engine Warming 

0 h 0 m 0 s 

 

Engine Cooling 

0 h 0 m 0 s 

 

Engine Overspeed Overshoot  

0 m 0 s 

 

Engine Fail To Stop Delay 

0 m 0 s 

 

Battery Under Voltage Warning Delay 

0 h 0 m 0 s 

 

Battery Over Voltage Warning Delay 

0 h 0 m 0 s 

 

Return Delay 

0 h 0 m 0 s 

 

DPF Ramp* 

0 s 

Schedule 

Schedule 

Active / Inactive 

 

Schedule Bank Period  

Weekly / Monthly  

 

On Load / Off Load / Auto Start Inhibit, Week, 
Start Time, Run Time and Day  
Selection (1-8) 

Press 

 to begin 

editing then up or down 
when selecting the 
different parameters. 

Active 

Main Configuration 

Press 

 to begin 

editing then up or down

 

when selecting the 
different configurations 

Config 

Alternative Config 1 

Select 

Alternative Config 2 

 

Alternative Config 3 

 

Alternative Config 4 

*Electronic Engines Only 
 
 

FIXING CLIPS 

 

NOTE: In conditions of excessive vibration, mount the module on suitable 

anti-vibration mountings.

 

 
The module is held into the panel fascia using the supplied fixing clips.  

 

Withdraw the fixing clip screw (turn anticlockwise) until only the pointed 
end is protruding from the clip. 

 

Insert the three ‘prongs’ of the fixing clip into the slots in the side of the 
module case. 

 

Pull the fixing clip backwards (towards the back of the module) ensuring all 
three prongs of the clip are inside their allotted slots. 

 

Turn the fixing clip screws clockwise until they make contact with the panel 
fascia.

 

 

 

Turn the screws a little more to secure the module into the panel fascia. 
Care should be taken not to over tighten the fixing clip screws 

 

ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR

 

 

 

The ‘running’ editor can be entered while the engine is running. All protections 
remain active if the engine is running while the running editor is entered. 

 

Press and hold the 

  (Tick) button to enter the running editor. 

 
 
RUNNING CONFIGURATION EDITOR PARAMETERS 
 

Section

 

Parameter As Shown On Display

 

Values

 

Display 

Contrast 

0 % 

 

Backlight Level 

0 % 

Dual Mutual 

Language 

English 

Engine

 

DPF Auto Regen Inhibit 

Active / Inactive 

 

DPF Manual Regen  

Active / Inactive 

 

DPF Manual Regen Cancel 

Active / Inactive 

 

 

DIMENSIONS AND MOUNTING 

 

DIMENSIONS 

240.0 mm x 181.1 mm x 42. mm 
(9.4” x 7.1” x 1.6”) 
 

WEIGHT 

0.7 kg 
(1.4 Ib) 

PANEL CUTOUT

 

220 mm x 160 mm (8.7” x 6.3”) 

 
TEMPERATURE

 

Operating:

 -40 ºC to +70 ºC  

                  (-40 ºF to +158 ºF) 
 

Storage: 

-40 ºC to +80 ºC  

               (-40 ºF to +176 ºF)

 

 

 

 

REQUIREMENTS FOR UL CERTIFICATION 

 

WARNING!: More than one live circuit exists, see diagram overleaf for further information.  

 

Specification 

Description 

Screw Terminal Tightening Torque 

  4.5 lb-in (0.5 Nm) 

Conductors 

  Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²). 

  Conductor protection must be provided in accordance with NFPA 70, Article 240 

  Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit. 

Current Inputs 

  Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.   

Communication Circuits 

  Must be connected to communication circuits of UL Listed equipment 

DC Output Pilot Duty 

  0.5 A 

Mounting 

  Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC) 

  Suitable for pollution degree 3 environments. 

 