TYPICAL WIRING DIAGRAM
Deep Sea Electronics Ltd.
Tel:+44 (0)1723 890099
Email: [email protected]
Web: www.deepseaelectronics.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: [email protected]
Web: www.deepseausa.com
D E E P S E A E L E C T R O N I C S
DSEE800 Installation Instructions
053-090
ISSUE 3
ACCESSING THE MAIN CONFIGURATION EDITOR
•
Ensure the engine is at rest and the module is in STOP mode by pressing the
(Stop/Reset)
button.
•
Press the
(Stop/Reset) and
(Tick) buttons simultaneously.
•
If a module security PIN has been set, the PIN number request is then shown:
•
The first
‘#’
changes to ‘
0’.
Press the
(Up) or
(Down) button to adjust it to the correct value.
•
Press the
(Right) button when the first digit is correctly entered. The digit previously entered now shows
‘#’
for security.
•
Repeat this process for the other digits of the PIN number. Press the
(Left) button to move back to adjust one of the previous
digits.
•
When the
(Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct,
the PIN must be re-entered.
•
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed:
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the
(Right) or
(Left) buttons to cycle to the section to view/change.
•
Press the
(Up) or
(Down) buttons to select the parameter to view/change within the currently selected section.
•
To edit the parameter, press the
(Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
•
Press the
(Up) or
(Down) buttons to change the parameter to the required value.
•
Press the
(Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
•
To exit the editor and save the changes, press and hold the
(Tick) button.
•
To exit the editor and not save the changes, press and hold the
(Stop/Reset) button
.
NOTE: To meet UL requirements, fuse the module supply at 167% of supply current.
NOTE: The editor is exited after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the DSE Configuration Suite PC
Software, refer to DSE publication 057-203 DSEE800 Configuraiton Suite PC Software Manual.