DSEE800 Installation Instructions

 

053-090 

ISSUE 3 

 

ACCESSING THE MAIN CONFIGURATION EDITOR 
 

 

Ensure the engine is at rest and the module is in STOP mode by pressing the 

 (Stop/Reset) 

button. 

 

Press the 

 (Stop/Reset) and 

  (Tick) buttons simultaneously. 

 

If a module security PIN has been set, the PIN number request is then shown:

 

 

 

The first 

‘#’

 

changes to ‘

0’.

 Press the 

 

 (Up) or 

 (Down) button to adjust  it to the correct value. 

 

Press the 

 (Right) button when the first digit is correctly entered. The digit previously entered now shows 

‘#’

 for security. 

 

Repeat this process for the other digits of the PIN number. Press the 

 (Left) button to move back to adjust one of the previous 

digits. 

 

When the 

  (Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, 

the PIN must be re-entered.

 

 

If the PIN has been successfully entered (or the module PIN has not been enabled),  the editor is 
displayed: 

 

 

EDITING A PARAMETER 

 

Enter the editor as described above. 

 

 

Press the 

 (Right)  or 

 (Left) buttons to cycle to the section to view/change. 

 

Press the 

 

 (Up) or 

 (Down) buttons to select the parameter to view/change within the currently selected section. 

 

To edit the parameter, press the 

  (Tick) button to enter edit mode. The parameter begins to flash to indicate editing.  

 

Press the 

 

 (Up) or 

 (Down) buttons to change the parameter to the required value. 

 

Press the 

 (Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved. 

 

To exit the editor and save the changes, press and hold the

 (Tick) button. 

 

To exit the editor and not save the changes, press and hold the 

 (Stop/Reset) button

 

 

NOTE: To meet UL requirements, fuse the module supply at 167% of supply current.

 

NOTE: The editor is exited after 5 minutes of inactivity to ensure security. 

NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to 

ensure security. 

NOTE:  More comprehensive module configuration is possible using the DSE Configuration Suite PC 

Software, refer to DSE publication 057-203   DSEE800 Configuraiton Suite PC Software Manual.

 