DSE Model 8620 AMF Controller Operators Manual
38
4.1.2 ANALOGUE SENSOR
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
15
Sensor Common Return
0.5mm²
AWG 20
Return feed for sensors*
16
Oil Pressure Input
0.5mm²
AWG 20
Connect to Oil pressure sensor
17
Coolant Temperature Input
0.5mm²
AWG 20
Connect to Coolant Temperature sensor
18
Fuel Level input
0.5mm²
AWG 20
Connect to Fuel Level sensor
19
Flexible sensor
0.5mm²
AWG 20
Connect to additional sensor (user configurable)
NOTE:- Terminals 20 and 21 are not fitted to the 8600 series controller.
NOTE: - It is VERY important that terminal 15 (sensor common) is soundly connected to an
earth point on the ENGINE BLOCK, not within the control panel, and must be a sound electrical
connection to the sensor bodies. This connection MUST NOT be used to provide an earth
connection for other terminals or devices. The simplest way to achieve this is to run a
SEPARATE earth connection from the system earth star point, to terminal 15 directly, and not
use this earth for other connections.
NOTE: - If you use PTFE insulating tape on the sensor thread when using earth return
sensors, ensure you do not insulate the entire thread, as this will prevent the sensor body from
being earthed via the engine block.
Содержание DSE8620
Страница 107: ...DSE8620 Operating Manual Issue 1 12 1 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4 ...
Страница 114: ...DSE Model 8620 Main Control and ATS Operators Manual 114 Website www deepseaplc com ...
Страница 121: ...DSE Model 8620 Main Control and ATS Operators Manual 121 This page is intentionally left blank ...
Страница 122: ...DSE Model 8620 Main Control and ATS Operators Manual 122 This page is intentionally left blank ...