3.14 APPLICABLE STANDARDS
BS 4884-1
This document conforms to BS4884-1 1992 Specification for presentation of
essential information.
BS 4884-2
This document conforms to BS4884-2 1993 Guide to content
BS 4884-3
This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1
(Minimum temperature)
-30
°
C (-22
°
F)
BS EN 60068-2-2
(Maximum
temperature)
+70
°
C (158
°
F)
BS EN 60950
Safety of information technology equipment, including electrical business
equipment
BS EN 61000-6-2
EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection
provided by enclosures)
IP65 (front of module when installed into the control panel with the supplied
sealing gasket)
IP42 (front of module when installed into the control panel WITHOUT being
sealed to the panel)
UL508
NEMA rating
(Approximate)
12 (Front of module when installed into the control panel with the supplied
sealing gasket).
2 (Front of module when installed into the control panel WITHOUT being
sealed to the panel)
IEEE C37.2
(Standard Electrical
Power System Device
Function Numbers and
Contact Designations)
Under the scope of IEEE 37.2, function numbers can also be used to
represent functions in microprocessor devices and software programs.
The 8000 series controller is device number 11L-8000 (Multifunction device
protecting Line (generator) – 8620 series module).
As the module is configurable by the generator OEM, the functions covered
by the module will vary. Under the module’s factory configuration, the device
numbers included within the module are :
2 – Time delay starting or closing relay
6 –Starting circuit breaker
27AC – AC undervoltage relay
27DC – DC undervoltage relay
30 – annunciator relay
42 – Running circuit breaker
50 – instantaneous overcurrent relay
51 – ac time overcurrent relay
52 – ac circuit breaker
59AC – AC overvoltage relay
59DC – DC overvoltage relay
62 – time delay stopping or opening relay
63 – pressure switch
74– alarm relay
81 – frequency relay
86 – lockout relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
Содержание DSE8620
Страница 107: ...DSE8620 Operating Manual Issue 1 12 1 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4 ...
Страница 114: ...DSE Model 8620 Main Control and ATS Operators Manual 114 Website www deepseaplc com ...
Страница 121: ...DSE Model 8620 Main Control and ATS Operators Manual 121 This page is intentionally left blank ...
Страница 122: ...DSE Model 8620 Main Control and ATS Operators Manual 122 This page is intentionally left blank ...