BEFORE 

OPERATING 

YOUR 

AIR 

EXCHANGE 

SYSTEM, MAKE SURE THAT:  

 
 
-  There  are  no  loose  objects  within  the  unit  or  the  air 
impeller.  Screws  or  any  other    objects    inside  the  fans 
can cause damage when the unit is switched on; 
 
- flexible mounting of  fans is used to   ensure  their   free   
swinging ;

 

 

-  The  coverings  of  construction-time  are  removed  from   
the outlet- and exhaust air holes. 
 
- All isolations and steam barriers are in order; 
 
-  heat  exchanger  is  in  place  and  the  summer  bypass 
plate  is  in  the  winter position:  air  is  flowing  through  the 
heat  exchanger  and  the bypass  tunnel  behind  the heat 
exchanger is closed;

 

 

-filter bags are in place  and  tightly secured  with  springs  
to the silicon sealing  to avoid a bypass flow; 

 
 
 

-noise deductors are in  place in the pressure chambers 
located  above the  fans; 
 
- The condensing water outlet is installed and the water   
is drained out; test it by  pouring small amount of water 
in the condensate basin; 
 
-  The  air  impellers  and  their  adjusters  are  in  working 
order  
 - Post-heating is regulated and working

 

Ensure that the 

overheat protector is reset if it has been activated; 

 

-necessary    settings  have  been  configured  through  the 
maintenance    and  settings  menu  on  the  unit's  control 
panel. 

 

USAGE DURING INSTALLING  

   The  air  exchange  unit  should  be  started  as  soon  as 
installation  permits.    Efficient  air  exchange  promotes 
drying  of  the  constructions  and  prevents  damage.  In 
case  channeling  has  not  been  completed,  fans  and 
adjustments  are  missing,  filter  paper  must  be  used  in 
place  of  fans  to  keep  the  channels  clean  and  provide 
sufficient counter pressure preventing overload. The unit 
must be used with full power and check the drainage of 
the  condensing  water.  The  appliance,  filters  and  heat 
exchangers  must  be  cleaned  and  the  system  adjusted 
after  the  construction  works  are  completed.  The  inner 
painted walls of the unit are easy to clean 

 
 

BASIC ADJUSTMENT OF AIRFLOW  

 
 The unit alone can not produce good interior ear in case 
the channels and fans are installed carelessly and main 
adjustments are not made.  Regulate the inlet and outlet 
fans to the planned positions and start the unit at design 
power  speed.  Measure  the  airflow  in  outside-  and 
exhaust air channels. The outlet must be 10-15% higher 
than  inlet.  Check  the  pressure level of  the  channels by 
checking from the fans and adjust it accordingly to obtain 
the  pressure level  of 10-30  Pa  for  fans  adjust  and  lock 
the pattern. Draw measuring- and adjustment records!  
 
 

USAGE AND CORRECT LEVEL OF AIR EXCHANGE  

   The  air  exchange  level  is  regulated  by  changing  the 
working  speed  of  the  air  impeller  from  the  operating 
panel.  Airflow  of  different  adjustable  positions  can  be 
seen from figure 5.  
Adjustable  position  1  is  for  basic  air  exchange  for  an 
empty house.   
Adjustable  position  2  and  3  are  normal  working 
positions.  
Adjustable position 4 and  5 are efficiency  positions  (i.e. 
for saunas).  
The correct usage positions will be found by experience 
observing the purity of the air or sultriness when coming 
in  from  outside,  observing  moisture  on  the  windows  or 
drying of the sauna.  
 
 

POST-HEATING  AND  SUMMER  BYPASS  OF  INLET 
AIR  
DIVK-700 DE

 is equipped with 2000W electrical battery 

operated by the means of TRIAC-adjuster or a water 
battery (VKL) operated by the operating device for post-
heating the heat recovered inlet air.  
The temperature of inlet air is usually regulated to +16C.  

The  temperature  may  be  adjusted  to  higher  during 

winter so there would be no draught like feeling. In case 
of  severe  frost  and  efficiency  mode  the  heating  power 
might turn out insufficient in  such circumstances, the air 
exchange should be reduced . 

The overheat protection has been activated in case the 

barrier  temperature  has  risen  +90  C  (for  instance,  in 
case  of  power  failure).  Reset  the  overheat  temperature 
by  pressing  the  switch  under  the  threaded  contact 
protection.  
During summertime, the Ito-exchanger element on  the 
bypass plate will be closed so the exhaust air will not 
warm up the inlet air.   
For summer time it is recommended to install EU.7 bag 
filter, which efficiently  filters pollen and other fine 
particles among others. 

INTRODUCTION OF THE AIR EXCHANGE 

Содержание Talteri DIVK-700DE VKL

Страница 1: ... THE RECOVERY SYSTEM TALTERI removes used air from interior and brings in fresh air Humidity and impurities are exhausted through thermal recovery unit that heats the filtered ambient air cost effectively The fresh warm air is channelled draught free and noise free into the premises in necessary quantities ENSURE THE QUALITY OF AIR EXCHANGE QUALITY CONTROLLED DIVK 700DE AND DIVK 700DE VKL ...

Страница 2: ...entilator Ø200 6 Fresh air intake from outdoors Ø200 250 7 Fresh air supply to the rooms Ø200 MACHINEPARTSAND TECHNICAL DATA 1 Exhaust air out 200mm 2 Outdoor air for the system 200mm 3 Exhaust air for the system 200mm 4 Interior air supply 200mm 5 Electricity connection 6 Main switches 7 Supply fan adjustable EC 171W 8 Exhaust fan adjustable EC 171W 9 Heat exchanger equipped with a bypass damper ...

Страница 3: ...ists and installation instructions define IV work in detail and do not need to be repeated Work specification defines necessary testings measuring and basic adjustment with proceedings reports THE REQUEST FOR QUOTATION includes total pricing considering on schedule installation according to the plan payment conditions are also extremely important IMPLEMENTATION AND MAINTENANCE TRAINING is unavoida...

Страница 4: ...lated channel and by 700 900mm high isolated roof duct Figure 3 Fireplaces like hearths ovens and sauna heating systems must have a separate isolated combustion air channels with slide coping INSTALLATION OF VENTS Income and outlet vents are installed according to the plan Special attention is needed while installing income valve since a wrong vent in a wrong place and wrong mounting will affect t...

Страница 5: ...ealed joint between the appliance and sewerage Electrical connections must be done following the installation manual and wiring scheme ELECTRICAL CONNECTIONS CAN BE DONE ONLY BY AN ENTREPRENEUR WITH RESPECTIVE INSTALLATION RIGHTS Electrical connection box can be opened from the front side below the unit by removing the screws beneath the locking covers The connection box slides out by pulling it f...

Страница 6: ...3 3x2 5 24 0 0 10 CO2 RH1 24 0 0 10 CO2 RH2 0 10 24 0 0 10 24 0 24 0 LTO BYPASS WIN TER YHT SUM MER T1 T2 T3 T4 T5 T6 FRESH SUPPLY EXTRACT EXHAUST WATER PRE HEATER POST HEATER CONTROL PANLEL 230VAC L N PE FUSE TEMPERATURE SENSORS CONTROL BOARD ECU ALARM NC YHT NO R Pulse switch switch Boosting set value 0 pre data Alter native SUPPLY FAN EXHAUST FAN KEVI 0 10 0 10 0 0 SUPPLY EXHAUST N N U U KEVI s...

Страница 7: ...liance from inside by a respective copper or plastic hose The water flowing into the heating battery is connected to the operating appliance 3 8 female screw that regulates the water flow into the battery The return water of the battery is connected by 10mm pressure connector and air fan is mounted to the highest point of the hose Locking fans are mounted to the outlet as well as return hoses The ...

Страница 8: ...1 170 165 148 142 120 105 87 77 65 58 40 35 100 qV AIRFLOW Pa 200 100 100 DIFFERENTIAL PRESSURE ACROSS TH EUNIT tuloilma 50 150 200 90 80 70 60 50 40 100 q V AIRFLOW Pa 200 100 100 50 150 200 90 80 70 60 50 40 qV AIRFLOW Pa 200 100 100 50 150 200 l s 40 50 60 70 80 90 100 l s l s INPUT POWER OF FANS W 150 250 300 350 50 SUPPLY AIRF EXTRACT AIR F5 AIRVOLUMES Soundpressurelevel ininstallation prem i...

Страница 9: ...d fans are installed carelessly and main adjustments are not made Regulate the inlet and outlet fans to the planned positions and start the unit at design power speed Measure the airflow in outside and exhaust air channels The outlet must be 10 15 higher than inlet Check the pressure level of the channels by checking from the fans and adjust it accordingly to obtain the pressure level of 10 30 Pa ...

Страница 10: ...t air impeller for the fusion period During severe cold the inlet air impeller will work in cycles Under extreme conditions humidity harsh cold the Ito element may freeze over and the anti freeze protection series are not able to defrost it If such a case occurs the machine has to be stopped opened and the cold flow stopped and the ice given the necessary time to melt Check the drainage of condens...

Страница 11: ...E AIR OUTLET AIR AND EXHAUST AIR ACCURACY OF TEMPERATURE SENSORS 2c BLINGIN YELLOW BLINGIN GREEN ACTIVATING DEACTIVATING OVERPRESSURE INTENSIFICATION AND AFTERHEATING PRESS PRESS PRESS PRESSURE COMP OFF PRESSURE COMP ON BOOSTING OFF BOOSTING ON AFTER HEATER ON AFTER HEATER OFF R MO 13 50 OUT 10 EXH 21 INLET 18 WASTE10 2 RH 60 CO2 850 ppm MO 13 50 FUNCTIONS R SETTINGS R R R R BACK EDIT SET MUOKKAA ...

Страница 12: ...e temperature Set value 15 20c The automatic mode has adjustment amplitude of approx 2 hours CO2 transmitter ON OFF switching Setting of CO2 upper limit Set value 250 1500ppm 50ppm steps RH transmitter ON OFF switching Setting of RH upper limit Set value 30 80 5 steps Regulating amplitude 5 20min Regulation of inlet air afterheating set value 1 5 30c Set value of intensification duration 0 and 5 1...

Страница 13: ...y percentage setting FACTORY SETUP SAVE FACTORY NOT IN USE NOT IN USE REMO TE CONTROL MAINTENANCE PERIOD 3 M ONTHS R M0 13 50 R FUNCTIONS SETTINGS SELECT BACK SETTINGS SELECT BACK SERVICE MENU SELECT BACK SELECT BACK SELECT BACK SERVICE MENU SERVICE MENU SERVICE MENU SELECT BACK SERVICE MENU SELECT BACK SELECT BACK SELECT BACK SERVICE MENU SERVICE MENU SERVICE MENU SELECT BACK SERVICE MENU BACK SE...

Страница 14: ...eller higher than outlet air impeller Intensification time settings 5 120min Intensification limit settings 1 4 the air impellers higher than basic speed Running speed difference of inlet and outlet air impellers 0 Air impellers working simultaneously 1 Inlet air impeller runs 1 step faster than the outlet air impeller 1 outlet air impeller runs 1 step faster than the inlet air impeller ATTENTION ...

Страница 15: ...s in the maintenance menu and the unit starts with factory speeds 3 2 Overpressurization Overpressurization state selectable from the outer switch or operation panel Outlet impeller is set on minimum inlet impeller is set to value of the maintenance menu The intensifications have no impact at this point The duration of overpressurization in minutes is selectable by the user New push from the switc...

Страница 16: ...e outside During the Summer mode the bypass plate of the cassette is activated The automatic functioning can be set with external temperature between 15 20 degrees 5 Alarms and reminders 5 1 Activation of overheat protection Information on activation of overheats protection connected to electrical post heater and preheater is received from the heater In case the protection launches the impellers a...

Страница 17: ...ight blinks green The user can reset the reminder after the filters have been changed The maintenance interval counter is reset and the new alert will be transmitted after the period has been completed again The maintenance interval can be set between 3 12 months 5 8 Filter dirty notice Differential pressure switch can be installed to the equipment that measures dirtiness of the inlet air filter b...

Страница 18: ...ture of the exhaust air rises above the set value The channels must be checked if the impeller works but the air exchange is inadequate or the temperature changes in the channels between the interior and the machine Temperature changes and humidity concentration in channels must be prevented by improving the isolation During harsh frosts in winter the equipment must be used on lower speed so the p...

Страница 19: ...19 PURE JOY FROM INDOOR AIR NOTES ...

Отзывы: