Table 1: Water battery sizing chart 

 
 
 
 
 
 

 

 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

water battery  sizing chart 

coming water 

return 

water 

water flow 

air flow 

rise of the 

temperature 

total power 

70c 

40c 

108l/h 

80l/h 

-5/38 

4.1 kW 

70c 

34c 

108l/h 

120l/h 

-5/30 

5.0 kW 

50c 

28c 

108l/h 

80l/h 

-5/27 

3.1 kW 

50c 

24c 

108l/h 

120l/h 

-5/21 

3.7 kW 

35c 

23c 

108l/h 

50l/h 

-5/23 

1.7 kW 

35c 

22c 

108l/h 

60l/h 

-5/21 

1.9 kW 

Operator panel bezel removal 

With water battery (VKL) installation it should be observed  
 

- The designing must consider temperature of used water and sustainability of the heating power under 
rated conditions. - Water, reaching the appliance, must be pre-regulated after leaving the boiler. 
 - Post-heating battery is switched to the appliance from inside by a respective  copper or plastic hose.  
- The water flowing into the heating battery is connected to the operating appliance (3/8 female screw) 
that regulates the water flow into the battery.  
- The return water of the battery is connected by 10mm pressure-connector and  air fan is mounted to 
the highest point of the hose.  
- Locking fans are mounted to the outlet as well as return hoses. 

 -  The  water  battery  is  equipped  with  an  anti-freeze  thermostat  that  stops  the  inlet  air  impeller  in 

case the temperature of the water battery decreases below the limit value (approxi10c). In such 
a case the self-powered butterfly plate also closes and prevents the cold outside air from entering into 
the battery.  The axel of the butter fly  plate  must be in a vertical position.

 

Figure 7:Operator bezel removal 

DIVK-700 DE VKL 4RO(RIGHT HANDED) 

 

 DIVK-700 DE VKL 4RV(LEFT HANDED) 

 

Содержание Talteri DIVK-700DE VKL

Страница 1: ... THE RECOVERY SYSTEM TALTERI removes used air from interior and brings in fresh air Humidity and impurities are exhausted through thermal recovery unit that heats the filtered ambient air cost effectively The fresh warm air is channelled draught free and noise free into the premises in necessary quantities ENSURE THE QUALITY OF AIR EXCHANGE QUALITY CONTROLLED DIVK 700DE AND DIVK 700DE VKL ...

Страница 2: ...entilator Ø200 6 Fresh air intake from outdoors Ø200 250 7 Fresh air supply to the rooms Ø200 MACHINEPARTSAND TECHNICAL DATA 1 Exhaust air out 200mm 2 Outdoor air for the system 200mm 3 Exhaust air for the system 200mm 4 Interior air supply 200mm 5 Electricity connection 6 Main switches 7 Supply fan adjustable EC 171W 8 Exhaust fan adjustable EC 171W 9 Heat exchanger equipped with a bypass damper ...

Страница 3: ...ists and installation instructions define IV work in detail and do not need to be repeated Work specification defines necessary testings measuring and basic adjustment with proceedings reports THE REQUEST FOR QUOTATION includes total pricing considering on schedule installation according to the plan payment conditions are also extremely important IMPLEMENTATION AND MAINTENANCE TRAINING is unavoida...

Страница 4: ...lated channel and by 700 900mm high isolated roof duct Figure 3 Fireplaces like hearths ovens and sauna heating systems must have a separate isolated combustion air channels with slide coping INSTALLATION OF VENTS Income and outlet vents are installed according to the plan Special attention is needed while installing income valve since a wrong vent in a wrong place and wrong mounting will affect t...

Страница 5: ...ealed joint between the appliance and sewerage Electrical connections must be done following the installation manual and wiring scheme ELECTRICAL CONNECTIONS CAN BE DONE ONLY BY AN ENTREPRENEUR WITH RESPECTIVE INSTALLATION RIGHTS Electrical connection box can be opened from the front side below the unit by removing the screws beneath the locking covers The connection box slides out by pulling it f...

Страница 6: ...3 3x2 5 24 0 0 10 CO2 RH1 24 0 0 10 CO2 RH2 0 10 24 0 0 10 24 0 24 0 LTO BYPASS WIN TER YHT SUM MER T1 T2 T3 T4 T5 T6 FRESH SUPPLY EXTRACT EXHAUST WATER PRE HEATER POST HEATER CONTROL PANLEL 230VAC L N PE FUSE TEMPERATURE SENSORS CONTROL BOARD ECU ALARM NC YHT NO R Pulse switch switch Boosting set value 0 pre data Alter native SUPPLY FAN EXHAUST FAN KEVI 0 10 0 10 0 0 SUPPLY EXHAUST N N U U KEVI s...

Страница 7: ...liance from inside by a respective copper or plastic hose The water flowing into the heating battery is connected to the operating appliance 3 8 female screw that regulates the water flow into the battery The return water of the battery is connected by 10mm pressure connector and air fan is mounted to the highest point of the hose Locking fans are mounted to the outlet as well as return hoses The ...

Страница 8: ...1 170 165 148 142 120 105 87 77 65 58 40 35 100 qV AIRFLOW Pa 200 100 100 DIFFERENTIAL PRESSURE ACROSS TH EUNIT tuloilma 50 150 200 90 80 70 60 50 40 100 q V AIRFLOW Pa 200 100 100 50 150 200 90 80 70 60 50 40 qV AIRFLOW Pa 200 100 100 50 150 200 l s 40 50 60 70 80 90 100 l s l s INPUT POWER OF FANS W 150 250 300 350 50 SUPPLY AIRF EXTRACT AIR F5 AIRVOLUMES Soundpressurelevel ininstallation prem i...

Страница 9: ...d fans are installed carelessly and main adjustments are not made Regulate the inlet and outlet fans to the planned positions and start the unit at design power speed Measure the airflow in outside and exhaust air channels The outlet must be 10 15 higher than inlet Check the pressure level of the channels by checking from the fans and adjust it accordingly to obtain the pressure level of 10 30 Pa ...

Страница 10: ...t air impeller for the fusion period During severe cold the inlet air impeller will work in cycles Under extreme conditions humidity harsh cold the Ito element may freeze over and the anti freeze protection series are not able to defrost it If such a case occurs the machine has to be stopped opened and the cold flow stopped and the ice given the necessary time to melt Check the drainage of condens...

Страница 11: ...E AIR OUTLET AIR AND EXHAUST AIR ACCURACY OF TEMPERATURE SENSORS 2c BLINGIN YELLOW BLINGIN GREEN ACTIVATING DEACTIVATING OVERPRESSURE INTENSIFICATION AND AFTERHEATING PRESS PRESS PRESS PRESSURE COMP OFF PRESSURE COMP ON BOOSTING OFF BOOSTING ON AFTER HEATER ON AFTER HEATER OFF R MO 13 50 OUT 10 EXH 21 INLET 18 WASTE10 2 RH 60 CO2 850 ppm MO 13 50 FUNCTIONS R SETTINGS R R R R BACK EDIT SET MUOKKAA ...

Страница 12: ...e temperature Set value 15 20c The automatic mode has adjustment amplitude of approx 2 hours CO2 transmitter ON OFF switching Setting of CO2 upper limit Set value 250 1500ppm 50ppm steps RH transmitter ON OFF switching Setting of RH upper limit Set value 30 80 5 steps Regulating amplitude 5 20min Regulation of inlet air afterheating set value 1 5 30c Set value of intensification duration 0 and 5 1...

Страница 13: ...y percentage setting FACTORY SETUP SAVE FACTORY NOT IN USE NOT IN USE REMO TE CONTROL MAINTENANCE PERIOD 3 M ONTHS R M0 13 50 R FUNCTIONS SETTINGS SELECT BACK SETTINGS SELECT BACK SERVICE MENU SELECT BACK SELECT BACK SELECT BACK SERVICE MENU SERVICE MENU SERVICE MENU SELECT BACK SERVICE MENU SELECT BACK SELECT BACK SELECT BACK SERVICE MENU SERVICE MENU SERVICE MENU SELECT BACK SERVICE MENU BACK SE...

Страница 14: ...eller higher than outlet air impeller Intensification time settings 5 120min Intensification limit settings 1 4 the air impellers higher than basic speed Running speed difference of inlet and outlet air impellers 0 Air impellers working simultaneously 1 Inlet air impeller runs 1 step faster than the outlet air impeller 1 outlet air impeller runs 1 step faster than the inlet air impeller ATTENTION ...

Страница 15: ...s in the maintenance menu and the unit starts with factory speeds 3 2 Overpressurization Overpressurization state selectable from the outer switch or operation panel Outlet impeller is set on minimum inlet impeller is set to value of the maintenance menu The intensifications have no impact at this point The duration of overpressurization in minutes is selectable by the user New push from the switc...

Страница 16: ...e outside During the Summer mode the bypass plate of the cassette is activated The automatic functioning can be set with external temperature between 15 20 degrees 5 Alarms and reminders 5 1 Activation of overheat protection Information on activation of overheats protection connected to electrical post heater and preheater is received from the heater In case the protection launches the impellers a...

Страница 17: ...ight blinks green The user can reset the reminder after the filters have been changed The maintenance interval counter is reset and the new alert will be transmitted after the period has been completed again The maintenance interval can be set between 3 12 months 5 8 Filter dirty notice Differential pressure switch can be installed to the equipment that measures dirtiness of the inlet air filter b...

Страница 18: ...ture of the exhaust air rises above the set value The channels must be checked if the impeller works but the air exchange is inadequate or the temperature changes in the channels between the interior and the machine Temperature changes and humidity concentration in channels must be prevented by improving the isolation During harsh frosts in winter the equipment must be used on lower speed so the p...

Страница 19: ...19 PURE JOY FROM INDOOR AIR NOTES ...