4
•
Assembling the control panel
Refer to the assembly sheet provided with the
instructions for the boiler.
•
Installing the boiler sensor
Refer to the assembly sheet provided with the
instructions for the boiler.
Electrical connections shall be carried out
by a qualified professional only.
The electrical wiring has been carefully
checked in the factory and the internal
connections of the control panel must not
be modified in any event.
Electrical connections shall be made respecting the
information given on the electrical diagrams delivered
with the equipment and the directives given in the
instructions.
The electrical connection must comply with applicable
standards and regulations in force. The equipment
must be powered by a circuit with an omni-pole switch
with an opening distance greater than 3 mm.
Electrical connections
8575N066A
GT 120 A, GT 1200 A
All connections are made on the terminal blocks
provided for this purpose at the back of the boiler
control panel.
The connecting cables may be brought inside the boi-
ler through the cut-outs provided in the boiler back
panel, which may be used along with purchased cable
channels.
Fasten the cables to the rear plate of the control panel by
means of the cable clamps (cable clamps supplied in a
separate pack) after mounting them on the plate.
IMPORTANT: The maximum current that can be
switched per output is 2 A cos.
ϕ
= 0,7 (= 450 W inrush
current less than 16 A).
Sensor cables must be separated from
cables in 120V circuits.
- In the boiler: use two cable glands on each side of
the boiler for this purpose.
- Outside the boiler: use two cable channels or
cableways with a minimum distance of 10 cm
between them.
Sensor
connection
side
120V connec-
tion side
5. ASSEMBLY, ELECTRICAL CONNECTIONS AND FITTER SETTINGS