Instruction Manual 

Negative Pressure Unit smart dec 

 

Version 2 

Page 23 

 

7.2.5.  Day / Night setting 

 

 

 
By selecting time ranges, it is possible to set on which days and at what time the set value 
in automatic mode for the minimum negative pressure in night mode is activated. 
 
 

7.2.6. Stand-by mode 

 
A negative pressure unit with SRE connect can be operated as a stand-by device 
(replacement device). If this function is activated, the device switches itself automatically 
on if a predefined negative pressure falls below the set negative pressure (for example, if 
the actual negative pressure unit fails). 
The stand-by mode is switched on in the menu by pressing the button "stand-by". 
In the field “Standby waiting time”, a delay of 0-600 seconds can be entered for power 
up. 
 

 

 
 

 

Содержание smart dec S 200

Страница 1: ...Original instruction manual Negative Pressure Units smart dec deconta GmbH Im Geer 20 46419 Isselburg S 50 S 55 S 200 S 300...

Страница 2: ...E 13 5 3 SRE connect 13 6 Assembly instruction 14 7 Initial operation 15 7 1 Control SE 15 7 1 1 Room pressurisation 15 7 2 Control SRE connect 16 7 2 1 Create your user account 17 7 2 2 Add the devic...

Страница 3: ...ially explosive atmospheres Maintenance work including removal and replacement of the filters may only be carried out by authorized persons wearing suitable protective clothing The device must be comp...

Страница 4: ...exhaust air is expelled to the open air The device is not suitable for filtering flammable gases or dusts The user must comply with the specified operating parameters of this manual The device may on...

Страница 5: ...ualified electrician CAUTION Damage due to unsuitable mains voltage The device can be damaged if it is connected to an unsuitable mains voltage Check whether the voltage indicated on the rating plate...

Страница 6: ...upplier Please note any damages on the consignment note 2 2 Transport Only transport the device in a clean decontaminated condition 2 3 Storage Store the unit in a decontaminated condition To avoid an...

Страница 7: ...00 m h 900 m h Power connection 100 120 V 230 V Power consumption 2 4 A 1 2 A Engine power 0 17 kW 0 21 kW Power cable type H07RN F 3G1 5 Protection class I Type of protection IP 54 Filter system 2 st...

Страница 8: ...onsumption 2x 4 6 A 5 5 A Engine power 2x 0 375 kW 0 75 kW Power cable type H07RN F 3G1 5 Protection class I Type of protection IP 54 Filter system 2 stage HEPA filter according to EN 1822 class H13 o...

Страница 9: ...ration the maximum volume flow the unit dimensions and the weight change The changed technical data can be taken from the following tables S 200 Air performance free blowing max 3000 m h Air performan...

Страница 10: ...ide Cardboard frame 47 mm wide Filter medium Glas fibre Synthetic Degree of separation Am 85 90 Nominal volume flow 5400m h m 5400m h m Nominal flow velocity at nominal volume 1 5 m s 1 5 m s Initial...

Страница 11: ...ter medium Micro fiberglass paper Casting compound Polyurethane Seal Polyurethane Filter class H13 or H 14 acc to EN 1822 Temperature humidity 70 C 100 RH relative humidity Filter dimensions in mm S 5...

Страница 12: ...ss H13 or H14 S 50 only H13 Energy efficient and performance optimised fan with high capacity Smooth and easy to decontaminate housing Light and sturdy housing HEPA filter acc to EN 1822 class H13 or...

Страница 13: ...ation the negative pressure unit is supplied with a control via a touch display to measure and regulate the negative pressure and or the volume flow The negative pressure is measured between the conta...

Страница 14: ...contaminated area overpressure technology prevents the penetration of contaminated ambient air into the housing Since the devices are contaminated from the outside and therefore have to be cleaned aft...

Страница 15: ...S 55 SE Control via potentiometer Connect the power supply Operate the controller S 50 S 55 Adjust the power on the display with or S 200 and S 300 7 1 1 Room pressurisation Set the required negative...

Страница 16: ...eland Israel Italy Japan Jersey Kazakhstan Kuwait Kyrgyzstan Laos Latvia Liechtenstein Lithuania Luxembourg Macau Macedonia Malaysia Malta Martinique Moldova Mongolia Montenegro Nepal Netherlands Neth...

Страница 17: ...the tab Sign Up and enter your e mail address and desired password The password must be at least 8 characters long and must meet 3 of the following 4 criteria At least 1 number At least 1 capital let...

Страница 18: ...ure Unit smart dec Version 2 Page 18 7 2 2 Add the device to your user account Turn on your device Press the button Menu Press the button Service Press the button deconta connect The page with a QR co...

Страница 19: ...smart dec Version 2 Page 19 Log in with your e mail address and with your password on the connect page Press the menu icon and then choose Devices Press the button SCAN QR CODE our recommendation or a...

Страница 20: ...button SUBMIT changes to green In order to add the device press this button Now the device is registered in your user account Alternative registration via the button SOFTWARE KEY Enter the key that ap...

Страница 21: ...nt in the clean area adjoining rooms and connect to the atmosphere connection with PE hose 8 x 1 The controller can be used in 2 different modes 7 2 3 Manual mode In manual operation the and keys are...

Страница 22: ...settings The following parameters can be set minimum negative pressure in day mode minimum negative pressure in night mode minimum volume flow in m h maximum negative pressure The automatic mode is s...

Страница 23: ...nd by mode A negative pressure unit with SRE connect can be operated as a stand by device replacement device If this function is activated the device switches itself automatically on if a predefined n...

Страница 24: ...tual current in A Middle down side displays the actual power in kW Right side displays the watt hours and below the total consumption in KWh 7 2 8 Dust sensor A filter sensor monitors the particle con...

Страница 25: ...t smart dec Version 2 Page 25 7 2 9 Service deconta connect Allocate the device to a connect account see point 7 2 2 Maintenance Settings in this menu can only be made by qualified deconta service par...

Страница 26: ...re displayed there in the set time zone default UTC 0 coordinated world time By pressing the yellow button Reset factory settings the red button Reset factory settings is activated By pressing on this...

Страница 27: ...Instruction Manual Negative Pressure Unit smart dec Version 2 Page 27 7 2 10 Software packages Display of the booked options and the expiration date of the licenses...

Страница 28: ...n 7 2 12 Alarms Alarms are visually displayed via a flashing icon on the main screen At the same time an acoustic signal sounds There are 3 different icons green checkmark there is no alarm message ye...

Страница 29: ...ive pressure The set nominal value for the minimum negative pressure could not be reached Volume flow The set nominal value for the minimum volume flow could not be reached High dust load Message filt...

Страница 30: ...nsors Please note when the sensors are switched off the particle concentration in the exhaust air is not monitored 7 2 13 Turn off the device To switch off the device press the red button OFF In order...

Страница 31: ...the filters As the filter occupancy is increased contamination of the filters the air performance decreases For filter monitoring during operation a pressure gauge is attached to the S 50 and S 55 Fo...

Страница 32: ...he filter pressure is shown in the display of the controller If the display reaches the red area please exchange pre or intermediate filter first If the display value drops by 100 Pascal or more the u...

Страница 33: ...d off Use only approved filters Do not use any residual bonding agent on the unit Remove and dispose prefilter Remove screws from the clamping bars and remove them Remove and dispose HEPA filter Check...

Страница 34: ...ive pressure too low Pre intermediate or HEPA filter contaminated Filter change as described in 8 2 Unit does not work Power source out of order Get the power source checked and repaired by a qualifie...

Страница 35: ...50274 2002 AC 2009 Low voltage switchgear and controlgear assemblies Protection against electric shock Protection against accidental direct contact with dangerous active parts EN 50274 2002 Low volta...