background image

- 5 -

100.6015.10

2 OPERATION

2.1 General

The remote meter panel is designed to complement the Capital Controls’ Series 200 vacuum regulators. 

When multiple chlorine gas feed points from the same vacuum regulator are required, a remote meter 

panel is utilized. Each remote meter panel is manually set, via the rate valve, to meter the proper amount of  

chlorine gas to the feed point. The combined gas feed rate from the remote meters must not exceed the total 

feed rate capacity of  the vacuum regulator.

NOTE

: When remote meter panels are desired to be used for gas flow indication only , the rate valve at the 

vacuum regulator is used to adjust gas flow. Therefore, if  the vacuum regulator has a rate valve, the remote 

meter's rate valve should be removed and replaced with a plug.

2.2 

Installation - See Figures 1, 2, and 3

The remote meter panel must be installed in an upright and level position in order to function properly.

The remote meter panel is installed in the vacuum line between the ejector and the vacuum regulator. Locate 

the meter panel on a vertical surface convenient for observation and operation, usually in the operator’s area, 

with the point of  chlorine injection at the desired remote location. Mount the meter panel using two (2) 1/4" 

mounting screws for a 3" meter panel, or four (4) 3/8" mounting screws for a 6" meter panel. If  the surface is 

not suitable for wood screws, choose an appropriate anchor bolt to that surface.

Black polyethylene tubing is normally used for the vacuum line. Do not kink this tubing. It may be desirable 

to use tubing connectors, tees or 90° elbows to provide as direct run as possible and minimize kinking 

conditions. Use enough tubing length to allow movement of  the vacuum regulator for servicing or cylinder 

change. Connect the tubing as follows:

2.2.1  Remove the bottom vacuum inlet connector nut from the remote meter panel and slip the connector 

nut onto the vacuum tubing coming from the vacuum regulator.

2.2.2  Push the tubing onto the tubing connector and tighten the connector nut HAND TIGHT.

2.2.3  Remove the connector nut from the vacuum outlet (top) of  the remote meter and slip onto vacuum 

tubing going to the ejector.

2.2.4  Push the tubing onto the tubing connector and tighten the connector nut HAND TIGHT.

NOTE

: There may be installations where multiple meter panels may be used from one vacuum 

regulator.  If  this occurs, additional tees may be required to complete the installation.

2.2.5  Some meter panels may be provided as a complete block with a common vacuum manifold, Each 

meter would have an individual outlet.

General Design Note

: Routing vacuum tubing through unventilated conduit is discouraged. A minute 

portion of  gas flowing through tubing under vacuum conditions, will slowly diffuse at a molecular 

level through its walls and collect in the closed conduit over an extended period of  time.

Содержание 200 Series

Страница 1: ... 1 100 6015 10 Instruction Manual Series 200 Remote Meter Panels 500 PPD 10 kg h Maximum Capacity 100 PPD 2 kg h Maximum 200 PPD 4 kg h Maximum 250 PPD 5 kg h Chlorine only 500 PPD 10 kg h Maximum ...

Страница 2: ...to instruction operating manuals all instructions given on labels or attached tags should be followed Regardless of these efforts it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur It is the responsibility of the installer to ensure that the recommended installation instructions are followed It is the responsibility of the user to ensure ...

Страница 3: ... 4 SERVICE 12 4 1 Cleaning the Flowmeter Assembly 12 4 2 Rate Adjustment Valve Cleaning 12 5 TROUBLESHOOTING CHART 13 FIGURES 1 100 PPD 2 kg h Meter Panel 6 2 200 PPD 4 kg h 250 PPD 5 kg h Chlorine only Meter Panel 7 3 500 PPD 10 kg h Meter Panel 8 4 100 PPD 2 kg h Meter Panel Components 9 5 250 PPD Max 4 kg h Meter Panel Components 10 6 500 PPD 10 kg h Meter Panel Components 11 ...

Страница 4: ...nd quantity of the gas being handled 2 the complexity of the gas supply system 3 the quality and quantity of water or process liquid being used to operate the ejector s and 4 operation procedures More frequent service periods are especially indicated when venting of the VR is occurring during the one year operational period This is usually indicative of foreign debris holding the inlet valve open ...

Страница 5: ...er panel If the surface is not suitable for wood screws choose an appropriate anchor bolt to that surface Black polyethylene tubing is normally used for the vacuum line Do not kink this tubing It may be desirable to use tubing connectors tees or 90 elbows to provide as direct run as possible and minimize kinking conditions Use enough tubing length to allow movement of the vacuum regulator for serv...

Страница 6: ...100 6015 10 6 Figure 1 100 PPD 2 kg h Meter Panel ...

Страница 7: ... 7 100 6015 10 Figure 2 200 PPD 4 kg h Meter Panel ...

Страница 8: ... feeding sulfur dioxide the actual flow rate is 0 95 of the scale value For example a reading of 50 PPD 1 kg h is actually 45 PPD 0 95 kg h sulfur dioxide If feeding ammonia the actual flow rate is 0 50 of the scale value For example a reading of 50 PPD 1 kg h is actually 25 PPD 0 5 kg h ammonia Read the flowmeter scale at the center of the ball NOTE NEVER use the rate valve on the remote meter pa...

Страница 9: ... 9 100 6015 10 Figure 4 100 PPD 2 kg h Meter Panel Components ...

Страница 10: ...100 6015 10 10 Figure 5 250 PPD Max 4 kg h Meter Panel Components ...

Страница 11: ... 11 100 6015 10 Figure 6 300 6 kg h 500 PPD 10 kg h Meter Panel Components ...

Страница 12: ...n the metering ball using wood alcohol and rinse thoroughly with warm water 4 1 6 Thoroughly dry the glass metering tube Reassemble the metering stops and ball 4 1 7 Reinstall the meter assembly by tightening the meter inlet plug making sure that it is on center with the top and bottom gasket NOTE The meter gaskets can usually be reused Turn the gaskets over for best results 4 2 Rate Valve Cleanin...

Страница 13: ...onnection and remake as necessary c Replace vacuum tubing and arrange line s to eliminate 2 Flowmeter ball bounces and or maximum gas feed rate cannot be achieved during normal operation a Vacuum regulator inlet filter screen dirty b Rate valve dirty c Flowmeter dirty d Ejector water supply pressure fluctuating causing insufficient ejector vacuum Ball bouncing only a Replace gas inlet filter b Cle...

Страница 14: ... improvements may be made without notice SEP 2015 De Nora Water Technologies 3000 Advance Lane Colmar PA 18915 ph 1 215 997 4000 fax 1 215 997 4062 web www denora com mail info dnwt denora com Registered Trademark 2015 All Rights Reserved ...

Отзывы: